Open access peer-reviewed chapter - ONLINE FIRST

Air Cooling in Steam Plant Condenser Using Refrigeration System for Improving Vacuum Pump Performance

By Ahmed Hegazy and Abraham Engeda

Submitted: July 17th 2018Reviewed: December 22nd 2018Published: February 14th 2019

DOI: 10.5772/intechopen.83787

Downloaded: 97

Abstract

Modifying the steam plant condenser by incorporating a vapor compression refrigeration system, which is utilized to chill the water used for cooling the condenser air cooler, is proposed in this work. Hence a considerable drop in air temperature is obtained, and more steam associated with air is condensed resulting in reducing both steam lost and vacuum pump power. A thermodynamic analysis is developed for working out the performance of the proposed hybrid system. The results obtained using this analysis showed that for a condensate subcooling of 3°C the total work saving due to this modification has maximums of 38.5, 33.9 and 28.9% and occur at temperature reduction below the condensate temperature of 12, 10, and 8°C when the temperature of steam admitted to the condenser is 20, 30, and 40°C, respectively. The savings in steam lost through the vacuum pump in these cases amount to 87.7, 84, and 79.2%, respectively. It is recommended to select the decrease in condenser air temperature in the range of 4°C higher than those decreases, at which the minimum total work comes about, as the saving in steam lost becomes fairly greater (5–7%), while the maximum increase in minimum total work is 3%.

Keywords

  • steam plant condenser
  • vapor compression refrigeration system
  • condenser air cooler
  • vacuum pump
  • power saving

1. Introduction

The primary purpose of the steam condenser in a steam plant is to convert the turbine exhaust steam into water for reuse in the boiler and to create and maintain vacuum at the turbine exhaust. This is achieved by cold water circulation through tube bundles and condensing the steam on their outer surfaces. Referable to the large reduction in the specific volume on changing from steam to condensate, a vacuum is formed within the condenser. Getting to this vacuum continuously as minimum as possible is very important for the steam plant to attain the highest possible power from the turbine. A rise in the condenser pressure can be produced due to the existence of air, ammonia, and other noncondensable gases [1]. This rise in pressure in the condenser results in lowering the useful turbine power and in turn the plant efficiency degenerates [2, 3, 4, 5].

The presence of air lowers the partial pressure of steam and therefore brings down the saturation temperature of steam, which leads to increasing evaporation enthalpy (latent heat), and therefore, more cooling water will be required in the condenser. In addition, this gives rise to increasing condensate subcooling, which is undesirable because it means that the excess heat removed for this purpose serves no useful process and entails providing additional boiler firing [6]. Thus, continuous removal of the air and noncondensable gases from the condenser is very critical for maintaining the plant efficiency possibly high. Beside this task, the air extraction system prevents air blanketing of condenser tubing that could dramatically reduce the heat transfer and stop the condensing process. Also, it reduces the condensate-dissolved oxygen levels that could lead to corrosion of boiler tubing.

The air and noncondensables are extracted from the bottom of the condenser, where the temperature is the lowest, by using vacuum pump. The air and noncondensables sucked by the vacuum pump contain a relatively big amount of noncondensed steam; each kilogram of air can contain more than 2 kg of water vapor [7]. This results in increasing the parasitic work of the pump. In condenser design, it is considered reducing the subcooling of the condensate possibly to the lowest degree to minimize heat removal. For reducing the amount of steam mixed with the air sucked by the air pump, the steam condenser has a portion of tubes near the air pump suction screened off and the condenser tubes in this portion contain the coldest water, and the number of cooling tubes is increased. Hence, the temperature of the air drops below that of the outlet condensate, and more steam associated with the air is condensed so that the mass flow rate of the air and steam mixture drawn by the air pump is reduced and, in turn the power of the dry pump is lowered.

The air extraction system (vacuum pump) can be centrifugal compressor, steam jet ejector air ejector, or water ring pump [8, 9]. A hybrid system of these components is preferred as they offer several advantages toward minimizing venting equipment size and save parasitic consumption [7]. The power required for operating these equipment sorts is dependent on both the rates of air and the noncondensables and noncondensed steam sucked by the vacuum pump. The temperature decrease of the air in the condenser air cooler is limited when the normal cooling water is used. For obtaining considerable drop in air temperature it is proposed in this work to modify the condenser by incorporating a refrigeration system into the condenser. This system is utilized to chill the cooling water, which is used for cooling the air in the condenser rather than the normal cooling water. Of course the use of the refrigerant directly to cool the air exploiting the air cooler as an evaporator for the refrigeration system and circulating the cold liquid refrigerant of this system through the tubes of the air cooler will be more efficient than using the chilled water. However, this configuration calls for redesigning the air cooler to be adapted for receiving and evaporating the refrigerant, which will be expensive for already existing power plants. The latest configuration can be taken into consideration for the design of the new plants.

The concept of using dry ammonia for cooling steam plant condenser is described in Ref. [10]. This concept states that the condenser cooling water is replaced by liquid ammonia, which evaporates as it acquires heat from the condensing steam. The heat of condensation absorbed by the ammonia is rejected in an air cooled condenser of a refrigeration machine into the surrounding atmosphere. This concept was tested and well documented [11, 12, 13, 14, 15, 16, 17], with the participation of several major equipment vendors (Baltimore Air Coil, the Trane Company, Curtiss-Wright, CB&I, and Union Carbide). In addition, the concept of using vapor compression refrigeration system (VCRS) combined with steam plant condenser was studied in detail in [14, 15, 16, 17, 18, 19]. The results of these studies showed significant rise in net power as well as efficiency of the steam plant. However, for realizing this combined system, a relatively huge VCRS is required, which leads to material increase of the combined system cost. In the current study, a relatively small VCRS is required as it serves to cool only the air contained in the air cooler of steam plant condenser. This leads to lessening the temperature of the air and water vapor mixture in the air cooler, resulting in condensing some of the water vapor. Hence, the mass flow rate of the air and water vapor mixture extracted from the steam condenser is decreased and consequently the power consumed by the vacuum pump lessens. Meanwhile, water vapor leaving the steam condenser and lost to the surroundings is reduced. In general, this contributes to contracting both the power consumed in the auxiliary systems of the steam plant and the steam consumption.

2. Conception of the modified steam plant condenser

The steam plant condenser is typically a shell and tubes heat exchanger. Figure 1 depicts a section through a steam plant condenser. The steam leaving the plant turbine enters the condenser at its top with temperature Tci and flows around the outer surface of the cooling tubes in which cooling water is circulated. Heat is transferred from the steam into the cooling water where steam condenses and the condensate is extracted out of the condenser at the bottom with temperature Tce. A segment of the condenser (called air cooler) is shielded for cooling the air associated with the condensate and leaked from the environment. This segment is possibly located near the inlet of cooling water, and the number of the cooling tubes is increased in it, so that the air associated with some water vapor collected in this section is cooled to a temperature Tvpi, which is lower than that of the condensate. This will lead to decreasing the mass rate of water vapor, the air pulled by the vacuum pump connected to this segment. As a result, the energy used up by the vacuum pump for extracting the air and its accompanying water vapor to the environment are decreased. In the current study, it is suggested to circulate chilled water within the cooling pipes of the cooling air section, so that the temperature of the air and accompanying steam is further reduced.

Figure 1.

A schematic section through steam plant condenser.

Figure 2 illustrates a configuration for the modified steam plant condenser that enables the use of chilled water to lower the temperature of the air cooler section. The cooling water (a) coming from a water body (river, sea, …) or a cooling tower is fed into the header (e) where it is distributed to the most of the cooling water tubes of the condenser. It helps to cool the steam exhausting out of the plant turbine. This cooling water is called here normal cooling water. While being heated up, it exits the cooling tubes into the header (f). The warmer normal cooling water (b) is extracted from the header (f) and pumped back to the water body or the cooling tower. The chilled water (c) is fed to the header (g) and it flows through the cooling tubes of the air cooling part of the steam condenser. This chilled water acts as a coolant for air along with some water vapor collected in the air cooler. This leads to cooling the mixture of the air and water vapor to a temperature lower than that of the condensate. The temperature of the chilled water is raised as it flows through the cooling tubes due to heat transfer from the mixture of air and steam in the air cooler. As a result, some of the steam contained in the mixture is condensed and flows down the condenser to the hot well. The warm chilled water goes into the header (h), from which it is transmitted backward to a chiller. Finally, the rest of the air and water vapor mixture in the air cooler is sucked by a vacuum pump and expelled into the atmosphere. The vacuum pump is not shown in Figure 2.

Figure 2.

A configuration of the modified steam plant condenser. a, normal cooling water in; b, normal cooling water out; c, chilled water in; d, chilled water out; e–h, headers.

3. Description of the studied combined system

In the current study, a vapor compression refrigeration system (VCRS) is used to chill the cooling water used for cooling the air cooler of the above described steam condenser. Hence, Figure 3 shows a schematic of the studied combined system. The refrigeration cycle is made up of a two-stage compression system (c) and (d) (these are also designated by I and II, respectively); a refrigerant condenser (e); two throttling valves (f) and (h); a flash tank (g) for intercooling and flash gas removal; a liquid-line/suction-line heat exchanger (LLSL-HE) (b); and an evaporator (a), which acts at the same time as a heat exchanger for chilling the cooling water used in the air cooler. In this system, the low-pressure refrigerant leaving the evaporator (a) is heated in the liquid suction heat exchanger (b) as it absorbs heat from the higher-temperature liquid refrigerant coming from the flash chamber (g). It is drawn by the first-stage compressor (c) where its pressure is raised to the intermediate pressure of the flash chamber. It is sent to the flash chamber (g) in which it is mixed with the refrigerant coming out of the throttle valve (f) and it gets cooled. The refrigerant vapor is separated from the liquid refrigerant and it is drawn by the second-stage compressor (d) and its pressure is elevated to the condenser pressure. The high-pressure refrigerant leaving the compressor (d) flows through the refrigerant condenser (e) where it is condensed and it streams further to the throttle valve (f) where its pressure is reduced to the intermediate pressure of the flash chamber, and it is fed into the flash chamber. The liquid refrigerant leaving the flash chamber is fed to the liquid suction HE (b). Here it is cooled as it gives a portion of its sensible heat to the refrigerant vapor departing the evaporator (a). The cooled liquid refrigerant is reduced in pressure to the evaporator pressure on running through the throttle valve (h). The refrigerant is then run to the evaporator/water chiller to cool down the warm water coming from the air cooler. The low-pressure vapor refrigerant leaving the evaporator/water chiller (a), completes the refrigeration cycle. This refrigeration cycle has been selected among the available refrigeration cycles due to its simplicity and relatively high efficiency.

Figure 3.

A schematic of the combined proposed steam plant condenser and vapor compression refrigeration system. _____, water; _ _ _, refrigerant; a, refrigerant evaporator/HE; b, liquid suction HE; c, refrigerant compressor I; d, refrigerant compressor II; e, refrigerant condenser; f, throttle valve I; g, flash chamber; h, throttle valve II.

4. Thermodynamic analysis of the studied combined system

For the following analysis of steam and air flow through the plant condenser, it is assumed that both fluids are ideal gases. Since the steam and air flow inside the condenser are at relatively very low pressure, they can be considered behaving to acceptable accuracy as ideal gases. Referring to Figures 1 and 2, the steam exhausting the plant turbine (it is usually slightly wet) enters the condenser with temperature Tci and dryness fraction xci. Knowing the temperature Tci, both the saturation pressure ps,ci (it equals the partial pressure of the steam) and specific volume vs,ci of the saturated steam at condenser inlet can be fixed. Given the steam mass flow rate ṁst,tentering the turbine, the mass flow rate ṁst,ciof the steam at condenser entry can be calculated by:

ṁst,ci=xciṁst,tE1

The volume flow rate V̇st,ciat inlet to the condenser, by Dalton’s law, is equal to the volume flow rate V̇a,ciof the associated air [20] and is obtained from the following equation:

V̇st,ci=V̇a,ci=ṁst,civs,ciE2

The partial pressure pa,ci of the air at entry to the condenser is calculated by:

pa,ci=ṁaRaTci+273.15V̇a,ciE3

Inserting Eqs. (1) and (2) into Eq. (3) and designating the mass ratio ṁa/ṁst,tby β, it follows that:

pa,ci=βRaTci+273.15xcivs,ciE4

The total pressure pc,t at condenser entry is equal to the sum of the partial pressure pa,ci of the air and the saturation pressure ps,ci of the steam entering the condenser. It is taken constant throughout the condenser, since the velocity of steam flow is small. Hence, the total absolute pressure pc,t inside the condenser is given as:

pc,t=ps,ci+pa,ciE5

The condensate temperature Tce at condenser outlet is usually ΔTce lower than the steam temperature Tci at condenser inlet (i.e., Tce = TciTce). Knowing the temperature Tce, the saturation pressure ps,ce and specific volume vs,ce of the steam corresponding to this temperature can be determined. If the condenser is not screened, then the partial pressure pa,ce of the air leaving the steam condenser with condensate is given as:

pa,ce=pc,tps,ceE6

The volume flow rate V̇a,ceof the air to be dealt by the vacuum pump at the exit of the steam condenser can be determined by:

V̇a,ce=ṁaRaTce+273.15pa,ceE7

Hence, the mass flow rate ṁst,ceof steam associated with the air is assessed by:

ṁst,ce=V̇a,cevs,ceE8

Dividing both sides of Eq. (8) by ṁst,tand inserting Eq. (7) into Eq. (8), it follows that:

γ=ṁst,ceṁst,t=βRaTce+273.15pa,cevs,ceE9

In the case of screening the steam condenser and cooling the air, the temperature Tvpi of the air and water vapor mixture sucked by the vacuum pump is ΔTvpi lower than the condensate temperature Tce at steam condenser outlet (i.e., Tvpi = TceTvpi). Knowing the temperature Tvpi, the corresponding saturation pressure ps,vpi and specific volume vs,vpi can be fixed. The partial pressure pa,vpi and volume flow rate V̇a,vpiof the air and mass ratio δ ṁst,vpi/ṁst,tat inlet of the vacuum pump can be determined using Eqs. (6), (7) and (9), respectively, by replacing the subscripts ce by vpi and γ by δ. Accordingly, it follows that pa,vpi, V̇a,vpi, and δ are given by:

pa,vpi=pc,tps,vpiE10
V̇a,vpi=ṁaRaTvpi+273.15pa,vpiE11

and

δ=ṁst,vpṁst,t=βRaTvpi+273.15pa,vpivs,vpiE12

Regarding the VCRS, the p-h diagram of its cycle is illustrated in Figure 4. The numerals of Figure 4 correspond to the points 1–10 given in Figure 3. It is to be considered here that the refrigerant condenser is cooled exactly as it is conducted with the steam plant condenser. Consequently, it is assumed here that the refrigerant leaving the refrigerant condenser has a temperature equal to that of the condensate in the steam plant condenser (i.e., T5 = Tce). Considering this fact and knowing the subcooling ΔTrc,sub of the refrigerant condenser, the pressure of the refrigerant in the condenser (e) can be fixed. The evaporator temperature T9 = T10 is defined according to the temperature required by the chilled water at inlet to the air cooler of the steam condenser. T9 as well as T10 is ΔTe less than the temperature Tcw,aci (i.e., T9 = T10 = Tcw,aci − ΔTe) of the chilled water entering the steam condenser air cooler. Hence, the pressure of the refrigerant in the evaporator is the saturated one corresponding to the temperature T9/T10. Knowing the refrigerant pressures in the evaporator (a) and condenser (e), the adiabatic efficiencies ηrco,I and ηrco,II and mechanical efficiencies ηm,rco,I and ηm,rco,II of the compressor I (c) and II (d), respectively, and the effectiveness εLLSL of the LLSL-HE, the states of the different points of the VCRS cycle can be determined as explained in any refrigeration text book (e.g., [21]).

Figure 4.

p-h diagram of the VCRS cycle of the studied refrigeration system.

For obtaining the value of the mass ratio ζ ṁcw/ṁst,tof the chilled water flow rate through the air cooling segment and steam flow rate crossing the turbine, Figure 5 shows the mass flow rates of air mixture and chilled water, and their temperatures through this segment. An energy balance for the air cooler leads to the following equation:

ṁacp,aTceTvpi+ṁst,aciṁst,vpiLHatsaturationpressureps,vpi=ṁcwCwTcw,aceTcw,aciE13

Figure 5.

Mass flow and temperature of air, steam, and chilled water through the air-cooling segment.

It is to be noticed here that the sensible heat of the condensed steam in the air cooler was neglected as it is relatively very small, and ṁst,aciis equal to ṁst,,ce.

Solving Eq. (13) to get ṁcw/ṁaand multiplying both sides of the resulted equation by ṁa/ṁst,t, the ratio ζ(ṁcw/ṁst,t) is obtained as:

ζ=ṁcwṁst,t=βcp,aTceTvpi+γδxLHatsaturationpressureps,vpicwTcw,aceTcw,aciE14

For determining the mass ratio ṁr,I/ṁcwof the refrigerant and cooling water, a heat balance is performed for the evaporator/water HE (a), which yields to:

ṁr,Ih10h9=ṁcwCwTcw,aceTcw,aciE15

From which it follows that:

ṁr,Iṁcw=CwTcw,aceTcw,acih10h9E16

Multiplying both sides of Eq. (16) by the mass ratio ṁcw/ṁst,t, the mass ratio ξI (ṁr,I/ṁst,t) is worked out as:

ξI=ṁr,Iṁst,t=ζCwTcw,aceTcw,acih10h9E17

The mass ratio ζ is obtained from Eq. (14). A heat balance of the flash chamber (Figure 3) yields:

ṁr,IIh6+ṁr,Ih2=ṁr,Ih7+ṁr,IIh3E18

It follows from Eq. (18) that:

ṁr,IIṁr,I=h2h7h3h6E19

Multiplying both sides of Eq. (19) by ṁr,II/ṁr,I, it follows that the mass ratio ξII (ṁr,II/ṁst,t) of the refrigerant flow rate through the compressor II to the steam flow rate of the steam turbine is given by:

ξII=ṁr,IIṁst,t=ṁr,IIṁr,Ixṁr,Iṁst,t=ξIṁr,IIṁr,I=ξIh2h7h3h6E20

From Eqs. (17) and (20), the mass ratio ξt can be found as:

ξt=ṁr,tṁst,t=ξIxξII=ζCwtcw,acetcw,acih10h91+h2h7h3h6E21
ξt=ṁr,tṁst,tE22

The characteristic parameters describing the performance of the refrigeration cycle are given as:

qrc=ξIIh4h5E23
wrco,I=ξIηm,co,Ih2h1=ξIηm,rco,Iηi,rco,Ih2sh1E24
wrco,II=ξIIηm,rco,IIh4h3=ξIIηm,rco,IIηi,rco,IIh4sh3E25
wrco,t=wrco,I+wrco,IIE26
qe=ξIIh10h9E27
COP=ξIIh10h9/ξIh2sh1/ηco,Iηm,co,I+ξIIh4sh3/ηco,Iηm,co,IIE28

The hybrid system proposed in the current work can lead to two benefits, the first benefit is a decrease in the mass flow rate of steam lost in venting the air from the SPC, and the second one is a reduction in mass flow rate of air and steam mixture drawn by the vacuum pump and hence the pump power is lowered. However, a new energy consumption comes out, which is the total work (wrco,t) of the two compressors employed in the VCRS. To be capable to judge the goodness of the proposed hybrid system, both the energies used for venting the air from SPC and for operating the compressors of the refrigeration system should be determinable. The total work wrco,t of the two refrigerant compressors can be determined using Eqs. (24)(26). As for the work consumed for venting process, there are some vacuum pumps that can be utilized for this function, among which centrifugal compressor is the most effective and efficient instrument for performing this task. It is selected here only for the sake of judgment of the hybrid system goodness. In venting the air and steam mixture out of the steam condenser without air cooling, the specific vacuum pump (compressor) work wvp,wac referred to each kilogram of steam flow through the steam turbine can be expressed by aid of any thermodynamics text book (e.g., [20]) as:

wvp,wac=kmRmTceβ+γkm1ηm,vpηi,vppatmptkm1km1E29

where km and Rm are the isentropic exponent and gas constant, respectively, of the air steam mixture. They are given by [20]:

km=βCp,a+γCp,stβCv,a+γCv,stE30
Rm=βRa+γRstβ+γE31

When the steam condenser is fitted with air cooler, the air extracting compressor work wvp is given by:

wvp,ac=kmRmTvpiβ+δkm1ηm,vpηi,vppatmptkm1km1E32

km and Rm are calculated in this case by aid of Eqs. (30) and (31), respectively, by replacing γ by δ.

The total specific work wt (wrco,t + wvp,ac) employed for cooling and driving out steam condenser air is calculated by summing up Eqs. (26) and (32).

5. Results and discussion

The thermodynamic analysis developed in Section 4 for predicting the condensation rate in the steam plant condenser due to air cooling is first validated with the experimental data of reference [22]. In this work, experiments were conducted in a 2-m-long square cross-sectional channel (0.34 m × 0.34 m) to study the heat and mass transfer in the condensation of water vapor from humid air. The air flowing inside the channel was cooled by cold water flowing outside and adjoining only one side (0.34 m × 2 m) of the channel. Experimental data were obtained from five tests at various operating conditions as shown in Table 1. The thermodynamic analysis in Section 4 was slightly modified to be adapted for using the data given in Table 1 for computing the condensation rate. For solving the equations in this analysis and finding out the rate of condensation, the commercial computer package EES [23] was used. The thermal properties of the humid air at different conditions were found using the built-in functions available in the EES package. The condensation rate computed from the present model is displayed in Figure 6, which shows satisfactory agreement with the experimental data of Ref. [22] since the maximal discrepancy does not exceed 10%.

TestInlet humid air temperature Tha,in (°C)Velocity of humid air vha (m/s)Inlet relative humidity of humid air φAverage cooling flux qc,av (kW/m2)
182.661.461007.3
280.612.021009.0
379.132.5297.8310
478.733.0187.3511.1
575.023.5996.5512.5

Table 1.

Experimental conditions from Ref. [22].

Figure 6.

Comparison of the predicted and experimental values of condensation rate for all the tests of Ref. [22].

The thermodynamic analysis developed in Section 4 for performance prediction of the combined system proposed in this work necessitates knowing some basic design and operational data, which is listed in Table 2. It is to be noticed here that the values of isentropic and mechanical efficiencies of the compressors involved in this study have been selected close to the practical values of compressors in use in industry [24]. The results presented hereafter are based on these data. All parameter values given in Table 2 will be kept unchanged except for the case where the effect of a specific parameter is to be examined; it is handled as a variable.

ParameterValue
Mass ratio (β)0.0003
Compressor isentropic efficiency (ηi,rco,I, ηi,rco,II, ηi,vp)0.85
Compressor mechanical efficiency (ηm,rco,I, ηm,rco,II, ηm,vp)0.75
Dryness fraction of steam entering the SPC (xci)0.9
Effectiveness of the liquid suction HE (εLLSL)0.8
Temperature difference (Tci − T5), °C0
Temperature difference (Tcw,ace − Tcw,aci), °C4
Temperature difference (Tcw,aci − T10), °C4
Temperature difference (Tcw,ace − Tvpi), °C4
Temperature difference ΔTce, °C3
Subcooling of the refrigerant condenser (ΔTrc,sub), °C3

Table 2.

Basic design and operational data of the proposed combined steam plant condenser and refrigeration system.

The refrigerant of the refrigeration system is selected to be ammonia. The physical properties of air, water, steam, and ammonia needed for computation are predicted using the built-in functions of the commercial computing package EES [23], which is used for solving the equations of the analysis of Section 4.

In Figure 7, the mass ratio γ is plotted versus the temperature Tci for values of ΔTce of 1, 3, and 5°C. It is seen from Figure 7 that γ runs linearly with very low rate with Tci. This can be explained as follows: since β is constant, the mass rate of steam condensed because cooling the air depends mainly on ΔTce and it is very little dependent on Tci. Of course the condensed steam rate in the air cooler is a pit higher at higher Tci. For constant β and Tci, the amount of steam associated with the condenser air and, in turn, the rate of condensed steam decrease progressively with ΔTce. This accounts for the remarkable drop in γ with an increase in ΔTce as shown in Figure 7. In contrast, the amount of steam associated with the condenser air and consecutively the rate of condensed steam for constant β and ΔTce are almost unvarying with Tci. This explains the very low rate of increase in γ with rising Tci.

Figure 7.

Effect of condensate temperature on the extracted steam mass rate by the vacuum pump without air cooler. ———, ΔTce = 1°C; — — —, ΔTce = 3°C; ………, ΔTce = 5°C.

It is worth noting here that in Figures 814, which will be displayed in this section, the small values of temperature difference ΔTvpi close to zero represent the case in which there is virtually no air cooler is employed. These values are not practical as the refrigeration system will be useless. Yet these values are included in these images just for illumination. In Figure 8, the mass ratio δ is drawn against the temperature difference ΔTvpi for temperature Tci of 20, 30, and 40°C. It is seen from Figure 8 that δ declines with an increase in ΔTvpi where the rate of declination is relatively high at small values of ΔTvpi and it decreases progressively with ΔTvpi and becomes immaterially small for values of ΔTvpi greater than 12°C. This is brought about due to the large drop in steam content in the air and likewise the rate of steam condensed as the temperature Tvpi falls down. It is also seen from Figure 8 that Tci has almost negligible effect on δ as the amount of steam mixed with the condenser air and in turn the rate of condensed steam for constant β and ΔTvpi are almost invariable with Tci.

Figure 8.

Dependence of the mass of steam associated with air on the air temperature at vacuum pump entrance. ———, Tci = 20°C; — — —, Tci = 30°C; ………, Tci = 40°C.

Figure 9.

Saving percentage in steam mass associated with air when using air cooler. ———,Tci = 20°C; — — —, Tci = 30°C; ……… Tci = 40°C.

Figure 10.

Relationship between the mass of chilled cooling water required for steam condenser air cooler and the air temperature at vacuum pump entrance. ———, Tci = 20°C; — — —, Tci = 30°C; ………, Tci = 40°C.

Figure 11.

Effect of the air temperature at vacuum pump entrance on refrigerant mass rate when using air cooler. ———, Tci = 20°C; — — —, Tci = 30°C; ………, Tci = 40°C.

Figure 12.

Effect of the air temperature at vacuum pump entrance on coefficient of performance of the refrigeration system. ———, Tci = 20°C; — — —, Tci = 30°C; ………, Tci = 40°C.

Figure 13.

Specific work dependence on the air temperature at vacuum pump entrance. ———, wvp,wac; — — —, wvp,ac; ………, wrco,t; —. —, wt.

Figure 14.

Saving percent in specific work due to refrigeration cooling of steam condenser air cooler. ———, Tci = 20°C; — — —, Tci = 30°C; ……… Tci = 40°C.

Figure 9 illustrates the saving percentage (γ − δ) × 100/γ in the steam amounts to be condensed in the air cooler and not sucked by the vacuum pump as steam. It is clear from Figure 9 that this saving has a reversed trend to that of the mass ratio δ, it is equal to zero at ΔTvpi = 0, and it increases steeply with ΔTvpi. The rate of increase in this saving with ΔTvpi falls increasingly with the rise in ΔTvpi where it becomes inconsiderably small at ΔTvpi of 12°C.

It follows from Figures 8 and 9 that the amount of steam to be condensed in the air cooler is relatively high at small values of ΔTvpi and the rate of increase in this amount falls progressively with ΔTvpi. Therefore, the amount of the cooling chilled water and in turn the refrigerant needed for chilling the cooling water takes the same trend of the percentage saving (γ − δ) × 100/γ (see Figure 9). Figures 10 and 11 show the mass ratios ζ and ξt, respectively, as a function of ΔTvpi.

In Figure 12, the coefficient of performance COP of the refrigeration system is plotted versus the temperature difference ΔTvpi for Tci of 20, 30, and 40°C. Figure 12 discloses distinctly that COP decreases sharply with ΔTvpi. This is ascribed mainly to the falling value of the evaporator temperature of the refrigeration system and the increasing temperature difference between the refrigerant condenser and the evaporator. The temperature Tci has almost a negligible effect on COP as the temperature difference between refrigerant condenser and evaporator alters with ΔTvpi and not with Tci.

The specific works wvp,wac, wrco,t, wvp,ac as well as wt are plotted in the diagrams of Figure 13 versus ΔTvpi for temperature Tci of 20, 30, and 40°C. Although wvp,wac is independent of ΔTvpi, it is represented on the diagrams of Figure 13 as horizontal lines for the sake of comparison. It can be seen from Figure 13 that wvp,wac decreases with an increase in Tci, which is caused mainly due to the drop in pressure ratio of the vacuum pump. The specific work wvp,ac is reduced steeply with ΔTvpi until a value of ΔTvpi around 12°C; then, the rate of decrease in wvp,ac diminishes remarkably. This can be interpreted as follows: on the one hand, at low temperature difference ΔTvpi, the amount of steam mixed with air is relatively high as can be seen from Figures 8 and 9, which results in relatively high mass rate of the mixture of air and water vapor flowing through the vacuum pump, and therefore, greater pump work wvp,ac is obtained. As ΔTvpi is raised, the amount of steam flowing with air dwindles and so the mass flow rate through the pump declines, which gives rise to decreasing the pump work wvp,ac. On the other hand, the pressure ratio through the vacuum pump is raised with ΔTvpi and hence the work wvp,ac is increased. However, the increase in wvp,ac is relatively small at low values of ΔTvpi compared to the work decrease due to the drop in pump mass flow rate. Therefore, the pump work wvp,ac falls off with relatively high rate, as ΔTvpi grows. As the mass flow induced by the pump declines and the pressure ratio through the pump grows with increasing ΔTvpi, the effect of the former parameter diminishes, while the effect of the latter parameter grows up and the net result is a considerable drop in the rate of decrease in wvp,ac. The specific work wrco,t rises almost linearly with ΔTvpi. This is attributed mainly to the declination of the refrigeration system COP (see Figure 12). The rate of increase in wrco,t is almost independent of the temperature Tci.

The saving percentage (wvp,wac − wt) × 100/wvp,wac in work by using refrigeration system for cooling the air contained in the steam condenser is plotted in Figure 14 versus ΔTvpi for Tci of 20, 30, and 40°C. It is seen from Figures 13 and 14 that the sum of the specific works wvp,ac and wrco,t (i.e., the total specific work wt) has a minimal value (maximum saving in the total work sum wt). This minimum value depends on the value of Tci and it is less than the corresponding wvp,wac according to the temperature Tci by 38.5, 33.9, and 28.9% at ΔTvpi of 12, 10, and 8°C for Tci of 20, 30, and 40°C, respectively. Also, it is seen from Figures 13 and 14 that wt is maximally higher than the minimal value corresponding to Tci by 3% when ΔTvpi is 4°C higher than its value at which the minimal total specific work occurs. On the contrary, the saving in the steam lost increases depending on Tci in the range of 5–7%. Therefore, it is more advantageous to choose values for ΔTvpi higher than those at which the minimal total work occurs in the range of 4°C, as it results in fairly less lost steam rate to be drawn by the vacuum pump and inconsiderable increase in the total work. Higher values than 4°C cause inconsiderably small increase in saving the lost steam, but the total work is significantly raised.

It is to be mentioned here that the parameters γ, δ, ζ, ξt, wvp,wac, wvp,ac, wrco,t, and wt are displayed in Figures 7, 8, 10, 11, and 13 for the value for β of 0.0003. These parameters are directly proportional to the mass ratio β. This is explained as follows: the mass of steam mixed with each kilogram of air and condensed and in turn the amount of cooling normal/chilled water used for cooling a kilogram of air and condensing the steam as well as the amount of refrigerant utilized for chilling the cooling water are dependent only on the initial and final air temperatures of the cooling process. Therefore, the parameters mentioned above are directly proportional to the mass ratio β. On the contrary to that, the saving percentages (γ − δ) × 100/γ and (wt − we) × 100/we in the amount of steam to be condensed and total work, respectively, are independent of β.

6. Conclusions

The current work is concerned with the use of vapor compression refrigeration system (VCRS) for chilling cooling water used with the air cooler of the steam plant condenser (SPC). A thermodynamic analysis is developed for working out the performance of the hybrid system of VCRS and SPC. The results obtained using this analysis showed that subcooling of the SPC condensate can cause considerable reduction in steam rate associated with the air induced by the vacuum pump. However, this is possibly avoided as it represents heat loss in the condensate heat content, which should be compensated in the plant boiler. In addition, the results of this work led to drawing the following conclusions for condensate subcooling of 3°C, which represents a reasonable and practical subcooling of the condenser condensate.

  1. Temperature reductions of the condenser air of 5, 10, and 15°C below the condensate temperature result in reducing steam rate lost in venting air from the condenser relative to the loss when using no air cooler, by around 69, 85, and 90%, respectively.

  2. The total work saving when using chilled water for cooling the air in the condenser air cooler from that in case of no air cooling is applied, has maximums of 38.5, 33.9, and 28.9% and occurs at temperature decrease below the condensate temperature of 12, 10, and 8°C when the temperature of steam admitted to the condenser is 20, 30, and 40°C, respectively. In these cases, the savings in steam lost in venting process amount to 87.7, 84, and 79.2%, respectively.

  3. Selecting the reduction in condenser air temperature in the range of 4°C higher than that temperature reduction, at which the minimum total work occurs, is very advantageous where the saving in steam lost becomes fairly greater while the saving in total work is slightly lower than the minimum total works; in the range of 5–7 and maximally 3%, respectively.

Nomenclature

COPcoefficient of performance of the refrigeration system
Cpspecific heat capacity at constant pressure (kJ/kg K)
Cwspecific heat capacity of water (kJ/kg K)
hspecific enthalpy (kJ/kg)
kisentropic exponent
LHspecific latent heat (kJ/kg)
mass flow rate (kg/s)
ppressure (kPa)
qrelative heat transfer rate (kW/kg)
Rgas constant (kJ/kg K)
Ttemperature (°C)
vspecific volume (m3/kg)
Vair velocity (m/s)
volume flow rate (m3/s)
xdryness fraction (−)
wspecific work (kJ/kg)
Greek letters
βmass ratio ṁa/ṁst,t (−)
γmass ratio ṁst,ce/ṁst,t (−)
δmass ratio ṁst,vp/ṁst,t (−)
ΔTcetemperature difference of steam at condenser inlet and exit (K/°C)
ΔTetemperature difference of chilled water at air cooler inlet and saturated refrigerant in VCRS evaporator (K/°C)
ΔTrc,subsubcooling in the refrigerant condenser
ΔTvpitemperature difference of condensate in hot well and air entering the vacuum pump (K/°C)
εheat exchanger effectiveness (−)
ζmass ratio ṁcw/ṁst,t (−)
ηiisentropic efficiency of the compressor (−)
ηmmechanical efficiency of the compressor (−)
ξI, ξII, ξtmass ratios ṁr,I/ṁst,t,ṁr,II/ṁst,t, and ṁr,I+ṁr,II/ṁst,t, respectively (−)
φrelative humidity (−)
Subscripts
aair
acwith air cooler
aceair cooler exit for chilled water
aciair cooler inlet for chilled water
atmatmospheric
av.average
csteam condenser, cooling
cesteam condenser outlet
cisteam condenser inlet
cwchilled water
eevaporator
hahumid air
iisentropic
ininlet
mair and steam mixture, mechanical
rrefrigerant
rcrefrigerant condenser
rcorefrigerant compressor
ssaturated steam
ststeam
tsteam turbine, total pressure, total work
vpvacuum pump
vpivacuum pump inlet
wwater
wacwithout air cooler
1–10state numbers of the refrigerant of the refrigeration cycle
I, IIrefrigerant compressor no. I and II, respectively
Abbreviations
LLSL-HEliquid-line/ suction-line heat exchanger
SPCsteam plant condenser
VCRSvapor compression refrigeration system

Download

chapter PDF

© 2019 The Author(s). Licensee IntechOpen. This chapter is distributed under the terms of the Creative Commons Attribution 3.0 License, which permits unrestricted use, distribution, and reproduction in any medium, provided the original work is properly cited.

How to cite and reference

Link to this chapter Copy to clipboard

Cite this chapter Copy to clipboard

Ahmed Hegazy and Abraham Engeda (February 14th 2019). Air Cooling in Steam Plant Condenser Using Refrigeration System for Improving Vacuum Pump Performance [Online First], IntechOpen, DOI: 10.5772/intechopen.83787. Available from:

chapter statistics

97total chapter downloads

More statistics for editors and authors

Login to your personal dashboard for more detailed statistics on your publications.

Access personal reporting

We are IntechOpen, the world's leading publisher of Open Access books. Built by scientists, for scientists. Our readership spans scientists, professors, researchers, librarians, and students, as well as business professionals. We share our knowledge and peer-reveiwed research papers with libraries, scientific and engineering societies, and also work with corporate R&D departments and government entities.

More About Us