Open access peer-reviewed chapter

Building-Integrated Thermoelectric Cooling-Photovoltaic (TEC-PV) Devices

By Himanshu Dehra

Submitted: October 10th 2017Reviewed: February 15th 2018Published: July 11th 2018

DOI: 10.5772/intechopen.75472

Downloaded: 365

Abstract

Photovoltaic driven thermoelectric cooling devices are of great importance in terms of alternative cooling sustainable technologies. Depending on Peltier effect of the thermoelectric cooling (TEC), heating and cooling is achieved by applying a voltage difference in the thermoelectric module. Theoretical design considerations of building-integrated thermoelectric cooling-photovoltaic (TEC-PV) devices are analyzed. System design of a TEC-PV device is investigated with varying fresh outdoor ventilation rates. Integrated design with ceiling suspended, wall mounted, rooftop and active façade TEC-PV devices is considered in the analysis. The effect of voltage, air flow rate and height of fin heat transfer surface is also investigated. Expressions along with results for theoretical exergy of a TEC-PV device are also provided.

Keywords

  • thermoelectric cooling
  • TEC-PV device
  • HVAC
  • heat sink
  • solar energy
  • energy efficiency

1. Introduction

Thermoelectric module is a sold-state energy conversion device made up of thermocouples, which are wired in series electrical circuit and parallel thermal junctions. A thermocouple consists of N-type and P-type semi-conductor elements, so as to generate thermoelectric cooling (viz., Peltier-Seebeck effect) when a voltage difference in appropriate direction is applied through the connected circuit. Thermoelectric cooling has benefits of high reliability, no moving parts, compact size, no requirement of thermo-fluid and light weight of thermoelectric modules. The direct current (DC) required to power thermoelectric cooling (TEC) modules can be easily fed by solar powered photovoltaic (PV) devices. In this way energy conservation is achieved through utilization of available solar energy. With application of low voltage DC power source in a TEC module, heat transfer takes place from one side to the other side. In this way, TEC module’s one side is cooled and other side is heated. In a TEC module, electric current drifts from N-type element to P-type element [1]. The temperature of the cold junction gradually decreases with heat transfer mechanism from environment to cold junction at a lower temperature. This heat transfer mechanism takes place with passing of transport electrons from a low energy level inside the P-type thermocouple element to a high energy level inside the N-type thermocouple element through the cold junction. Simultaneously, transport electrons transmit absorbed heat to hot junction at a higher temperature. This extra generated heat is dissipated to heat sink, whereas transport electrons return to a lower energy level in the P-type semiconductor element, viz., the Peltier effect takes place (see Figure 1).

Figure 1.

Principle of thermoelectric cooling.

There is constant development and efforts made for making thermoelectric air-conditioning systems in technical competence with vapor-compression technology. The performances of thermoelectric and conventional vapor compression air-conditioners have been compared by Riffat and Qiu [2]. Results have shown that the COPs of vapor compression and thermoelectric air-conditioners are in between 2.6–3.0 and 0.38–0.45, respectively. However, thermoelectric air conditioners have several other capabilities compared to vapor-compression technology. TEC modules can be built into a planar structure on walls and false ceiling and are quiet in operation especially suitable for small offices and mini apartments. Cosnier et al. [3] have presented numerical and experimental results of a thermoelectric air-cooling and air-heating system. The maximum cooling power of 50 W per module, with a COP varying between 1.5 and 2 was reached with electrical current of 4 A and maintaining 5°C temperature difference between the hot and cold sides. Cheng et al. [4] have investigated a solar-driven thermoelectric cooling module with a waste heat regeneration unit for green building applications. Their results have shown that TEC system was able to produce 16.2°C temperature difference between the ambient and building zone. However, the TEC COP was relatively low, varying from 0.2 to 1.2 in this study.

Gillott et al. [5] investigated TEC devices for small-scale space’s air conditioning building application. A thermoelectric cooling unit was built for 220 W cooling capacity with a maximum COP of 0.46 with input electrical current of 4.8 A for each TEC module. Arenas et al. [6] and Vázquez et al. [7] developed an active thermal window (ATW) and transparent active thermoelectric wall (PTA) for room cooling application for building retrofit applications. In these devices, thermoelements embedded on window glass transfer heat through the glass in order to cool the room. A full-size prototype ATW was installed in a window frame (100 × 100 cm), which was able to generate up to 150 W of cooling power while glass transparency decreased by about 20%. Their work was patented [8]. Most of TEC devices directly cool down the indoor air. Shen et al. [9] investigated a novel thermoelectric radiant air-conditioning system (TE-RAC). The TE-RAC system employs thermoelectric modules as radiant panels for indoor cooling, as well as for space heating by easily reversing the input current. Their analysis of a commercial thermoelectric module, TEC1-12706 with a ZT value of 0.765, have obtained a maximum cooling COP of 1.77 with an electric current of 1.2 A while maintaining cold side temperature at 20°C.

The cooling effect in the TEC module is dependent on parameters such as electric current, the hot and cold side temperatures, the electrical contact resistance between the cold side and the surface of TEC device, thermal and electrical conductivities of thermoelement and thermal resistance of the heat sink on the hot side of TEC module. The required cooling capacity with maximum electric current determines the number of thermoelements in a TEC module. The main disadvantage of thermoelectric cooling module is its poor coefficient of performance (COP), predominantly in large capacity applications [10]. The COP and the cooling capacity of the TEC module can be predicted using the standard module theory based on one dimensional (1-D) heat balance equations, with the assumptions of negligible thermal and electrical contact resistances. The COP estimated from the standard module theory is determined from the hot and cold side temperatures of TEC module and figure of merit, ZT of the thermoelectric material. The design of thermoelectric cooling system is based on temperature difference across the hot and cold sides of the TEC module and the required cooling capacity.

In this chapter, one dimensional (1-D) energy balance model is presented for evaluating system design of a prototype thermoelectric cooling – photovoltaic (TEC-PV) device. The prototype consists of an integrated design with ceiling suspended, wall mounted, rooftop and active façade TEC-PV devices.

2. Energy balance model

The total energy efficiency of photovoltaic driven thermoelectric cooling devices can be increased with enhancement of photovoltaic system efficiency and with the use of thermoelectric materials with better performance. The COP of thermoelectric air conditioning devices powered through photovoltaic modules is typically not higher than 0.6 [10]. With consideration of photovoltaic system efficiency ηpv, the total energy efficiency of the system is given by the product of ηpv and COP. Mathematically it is written as:

ETECPV=ηpv×COPE1

The values of ETEC-PV are typically lower than 6%.

Commercial thermoelectric materials are alloys such as Bi2Te3, PbTe, SiGe and CoSb3 [11]. Bi2Te3 is the most commonly used thermoelectric material. The commercially available thermoelectric materials have highest ZT values around 1.0.

For a particular thermoelectric module with fixed hot/cold side temperatures, the maximum COP at optimum current is given by [11]:

COPmax,cool=TcThTc1+ZTmThTc1+ZTm+1E2

where ZTm is the figure-of-merit for thermoelectric material at mean hot and cold side temperature Tm. In calculation of COP, a mean temperature between the hot and cold junction temperatures (with fixed hot side temperature of 300 K with ZTm = 1) of the thermoelectric module (TEM) is used.

A steady state energy balance model of thermoelectric cooling is used for energy performance assessment. The absorbed (Qc) heat flux and released (Qh) heat flux are obtained using Eqs. (3) and (4) respectively. The electric power (P) required to power thermoelectric module (TEM) is obtained from the difference between the absorbed and released heat fluxes (Eq. (5)). In these equations, α, R and K are the Seebeck coefficient, electrical resistance, and thermal conductance of the thermoelectric module. Whereas, I, is the electric current and N is the number of thermocouple legs in the thermoelectric module. The TEM is made up of several thermocouple legs. Thermoelectric leg characteristics are responsible for the resulting TEM performance. R and K are calculated using Eqs. (6) and (7) respectively considering the leg length (L), leg section area (S), thermal conductivity (λ) and electrical resistivity (ρ). The coefficient of performance (COP) of the TEM is the ratio between the absorbed heat and total electric power (including fan power) obtained from Eq. (8). In this chapter, a thermocouple leg made of bismuth telluride (Bi2Te3) is considered and its properties are shown in Table 1 [12]. The thermal resistance between the thermoelectric module and fin plate is assumed to be 0.0161 K/W [12].

Qc=NαITC0.5RI2KΔTE3
Qh=NαITH+0.5RI2KΔTE4
P=QhQc=NαIΔT+RI2E5
R=LSρE6
K=SLλE7
COPcooling=QcPE8
Conductivity thermal (W/m-K)λT=62605277.7T+0.4131T2104
Resistivity electrical (Ω·m)ρT=5112163.4T+0.6279T21010
Seebeck coefficient (Volts/K)αT=2224930.6T+0.9905T2109

Table 1.

Bismuth telluride (Bi2Te3) properties.

In order to investigate the operating energy consumption in summer, a thermoelectric cooling-photovoltaic (TEC-PV) device is simulated for building data as per Table 2, representing sunny, hot and humid outdoor air condition. Properties of TEC-PV device is provided in Table 3. Table 4 provides thermal design properties of TEC-PV device.

Outdoor air conditionSunny, hot and humid (DBT: 33–35°C, RH: 75%)
Floor area9 m2
Room volume27 m3
U-value of exterior wall0.44 W/m2 K
U-value of roof0.126 W/m2 K
Window to wall ratio0.3
Lighting power density0.6 W/ft2
Infiltration0.3 ACH
Operation schedule07:00 to 17:00 hours
Indoor air conditionDry bulb temperature (DBT): 23°C, RH: 55%
Room sensible heat factor0.950.90.80.7
Ventilation rate20 m3/h40 m3/h90 m3/h120 m3/h
Peak sensible cooling load1 kW
Peak latent cooling load0.05 kW0.12 kW0.28 kW0.48 kW

Table 2.

Building data.

TEC moduleTEC1-12710Photovoltaic module
Operational voltage12 V DCTotal power required1.8 kW
Current max10.5 AmpArea required18 m2
Voltage max15.2 VRoof area9 m2
Power max85 WSouth façade area9 m2
Nominal power60 WNominal power300 W
Thermocouples127Number of PV modules8
Dimensions40 × 40 × 3.5 mmOn roof4
Total number of TEC modules30On façade4
Placement positionInside ceiling ductWall mountedBattery backup10.8 kWh
TEC modules1020Battery @ 12 V DC900 AH

Table 3.

Thermoelectric cooling (TEC)-photovoltaic (TEC-PV) device properties.

ParameterValues
Thermal resistance of cold side0.1 K/W
Thermal resistance of hot side0.7 K/W
TEM thermal conductivity0.51 W/K
TEM electrical resistance2.236 Ω
Aluminum thermal conductivity230 W/m-K
Thickness of aluminum sheet1.6 mm
Insulation thickness40 mm
Insulation thermal conductivity0.05 W/m-K
Insulation specific heat capacity500 J/kg-K
Thermal contact resistance0.1 m2K/W
Fin thickness1 mm
Fin profile length20 mm
Fin spacing3 mm
Number of fins (cold side) per TEC module10
Number of fins (hot side) per TEC module10
Thermal resistance (cold side fins)1.2 K/W
Thermal resistance (hot side fins)0.76 K/W
Thermal resistance between TEM and fin plate0.0161 K/W
Height of solar PV wall mounted exhaust duct3000 mm
Width of solar PV wall mounted exhaust duct2 Nos.@ 1500 mm
Absorption coefficient of PV panel0.9
Thickness of PV ventilated exhaust duct150 mm
Density of PV panel2300 kg/m3
Specific heat capacity of PV panel750 J/kg-K
Thickness of PV panel5 mm
Number of TEC modules with ceiling suspension duct (position 1)10 covering 1.60 m2
Number of TEC modules on wall (position 2)20 covering 3.60 m2
Heat transfer fluidAir
DC power for each fan1.5 W
Number of DC fans on supply side2
Number of DC fans on exhaust side2
Maximum ventilation rate per fan60 m3 h−1

Table 4.

Thermal design properties of TEC-PV device.

2.1. Thermoelectric dehumidification

The room sensible heat factor (RSHF) is defined as the ratio of sensible cooling load to total cooling load (Eq. (9)).

RSHF=QsenQsen+QlatE9

Relative humidity is a key control parameter for thermal comfort inside a room. The performance of a thermoelectric cooling device depends mainly on optimal positioning and layout of heat exchange & transfer surfaces.

The total heat transfer rate (Qc) of the fin heat exchanger on the cold side of the thermoelectric module (TEM) is given by [13]:

Qc=hcActrtc+mwHcE10

where hc is the coefficient of convective heat transfer (W/m2K), Ac is the heat transfer area (m2), tr is the room temperature (°C), tc is average temperature of cold fins (°C) and Hc is the latent heat of condensation (J/kg-K).

The dehumidifying rate (mw, kg/s) is calculated as [13]:

mw=maϕ1ϕ2TsecE11

where ma is the mass of the wet air inside the room (kg), Tsec is the dehumidifying period (sec), Φ1 and Φ2 are the relative humidity before and after dehumidification (%).

The convective heat transfer coefficient between adjacent fins and room air is given by [14]:

hc=0.517kairHRa0.25E12

where kair is the thermal conductivity of air (W/m-K), H is the height of fin (m) and Ra is the dimensionless Rayleigh number.

2.2. Exergy expressions

The specific exergy of fresh moist air into the duct is expressed as [15]:

exf,in=cpa+wf,incpvTf,inToTolnTf,inTo+RaTo[1+1.608wf,inln1+1.608wf,in1+1.608wo+1.608RaTowlnwf,inwo]E13

The reference temperature (To) and the humidity ratio (wo) is defined as the indoor air temperature and humidity ratio during hot and humid season. Ra is the thermal resistance of air. cpa is specific heat of moist air and cpv is specific heat inside the duct.

Thus from Eq. (13), total exergy of the fresh air flow into the duct is expressed as:

Exf,in=ρMaexf,inE14

where ρ is density of air and Ma is airflow rate m3/h.

The exergy of the heat transferred between the fresh air and TEM is expressed as:

ExQf=1ToTcQfE15

where Qf is heat transfer rate (W).

The system exergy efficiency is expressed as:

ηEx=ExeffExsup×100%=Exf,outExf,inExelec×100%E16

where Exeff is effective Exergy, Exsup is electrical exergy supplied.

3. Design considerations for thermoelectric cooling photovoltaic (TEC-PV) devices

  1. Building integration parameters: Thermoelectric cooling (TEC) devices can be fixed in a building on wall and ceiling as radiant cooling panels. Due consideration should be given for placing thermoelectric modules with or without heat sinks. Heat sinks can be placed towards building interior zone and towards exterior zone. The thermoelectric modules can be placed on a cut section of a wall, with provision of cooling the hot side heat sink. The thermoelectric cooling devices can also be fixed on a window or a skylight. Proper protection has to be ensured from air infiltration and direct solar radiation for TEC devices fixed on windows and skylights. The mode of operation for winter can be reversed by changing the direction of current of thermoelectric modules. TEC devices can also be fixed inside air supply ventilation ducts. Buildings requiring cooling and heating with dual duct ventilation system are good choice for using thermoelectric devices inside ducts.

  2. Thermoelectric module (TEM) system design: It depends on thermoelement length, number of thermocouple legs, cross sectional area, slenderness ratio. Both COP and cooling capacity of TEC devices are dependent on thermoelement length. Keeping cross sectional area constant, larger length of thermoelectric element achieves greater COP, while shorter length thermoelectric element achieves larger cooling capacity. Commercially available thermoelectric modules have thermoelement length in the range from 1 to 2.5 mm [11]. Cooling power capacity increases with decreasing the ratio of thermoelement length to cross sectional area.

  3. Thermoelectric cooling (TEC) system design: It depends on cooling system thermal design, heat sinks’ geometry, heat transfer area, heat transfer coefficients of hot and cold side heat sinks, thermal and electrical contact resistances, fins placement and design, heat sinks integrated with thermosyphon, heat transfer fluids, phase change materials [16]. Thermal contact resistance at the interface layer of thermocouple legs is critical for its cooling capacity and COP. Because of this reason, it is not essential that increase in ZT of thermoelectric material will increase ZT of a thermocouple leg because of the presence of interface layer. The performance and efficiency of heat sinks at hot and cold side effects the cooling COP. Air cooled heat sink (forced convection with fan, example thermal resistances of 0.54–0.66 K/W [11], water cooled heat sink (thermal resistance of 0.108 K/W [11], and heat sink integrated with heat pipe (thermal resistance 0.11 W/K are most commonly used techniques. It has been found that heat pipes are not preferred as they eventually have to release heat to either air or water eventually. Heat sinks with nanofluid have potential to achieve lower thermal resistance. Hot side heat sink performance is of greater importance due to higher heat flux density in comparison to heat flux at cold side heat sink. Allocation ratios of heat transfer area with heat transfer coefficients between hot and cold sides are important for achieving maximum COP. Typical allocation ratio is around 0.36–0.47 [11]. Maximum COP with optimum cooling capacity can be achieved at given hot and cold sides fluid temperatures.

  4. Photovoltaic (PV) power system design: The most conventional way is to install PV panels on rooftop and façade of a building with thermoelectric cooling (TEC) devices. In this way, excess power can also be stored in a battery system. In case of non-availability of solar PV power, power can be fed directly from the battery backup. Active façade ventilation can be integrated with TEM and PV devices [17, 18, 19]. For heating requirements during winter season, these active façade elements can supplement with heating from TEM and façade integrated PV ventilated devices [20, 21, 22].

  5. Performance & operational parameters optimization: It depends on electric current input, coolants, cooling methods of hot side heat sink, mass flow rate, ventilation requirements. Performance indicators are COP and energy efficiency of devices and systems.

4. System design of thermoelectric cooling-photovoltaic (TEC-PV) device

4.1. Importance of outdoor air ventilation

Indoor air quality improvement is achieved by bringing in outdoor air into the building environment. Introduction of outdoor air increases energy consumption of the conventional air conditioning system. In the conventional air conditioning system, limited energy conservation is achieved through heat recovery ventilators, such as fixed-plate, run-round coil and rotary wheel. In these heat recovery ventilators, passive means are employed through temperature and humidity difference between fresh outdoor air and return air, which are dependent on outdoor weather conditions. However in a thermoelectric cooling-photovoltaic (TEC-PV) device, dedicated outdoor air is cooled and dehumidified by active means through input of solar power. The design is assessed by estimating the cooling capacity for selection of a TEC module according to the temperature difference between the hot and cold side. The current required to operate the TEC module can be obtained from trials and also checked from manufacturer data curve to meet the actual cooling capacity. Energy efficiency of a thermoelectric cooling (TEC) device is defined as the ratio of the cooling capacity to the electrical energy consumed. Exergy analysis is based on quality of energy, used for evaluating energy process with respect to ideal thermodynamic equality. Exergy analysis is used for identifying exergy losses, which is used for understanding of irreversible losses of energy conversion in its system design.

The system design consists of: (i) outdoor fresh air ventilation; (ii) thermoelectric cooling (TEC); (iii) building integration; (iv) photovoltaic power generation; and (v) exhaust air ventilation.

4.2. Operation

The outdoor fresh air is cooled down and dehumidified as it flows over a heat sink/exchanger attached to thermoelectric cooling (TEC) module. The cool air enters the indoor environment which is to be maintained at 23°C and 55% RH. The stale air is taken out through ducted exhaust air ventilation system. The exhaust air also cools down the heat sink/exchanger attached to hot side of thermoelectric module (TEM). The outdoor fresh air is introduced into the single zone building air volume at varying rates as mentioned in Table 2. Four DC fans are used to provide power for forced airflow. Two of them are installed on supply fresh air side and other two are installed on exhaust air side. The input power for each fan is 1.5 W with airflow rate at 60 m3 h−1. The maximum fresh air supply in the room is 120 m3 h−1 at full capacity. The outside fresh air is at 33°C and 75% RH. Eight solar PV modules of 300 W each are used to power thirty TEC modules of 60 W each and four DC fans of 1.5 W each. Four solar PV modules are placed on south façade while other four are fixed on roof top. The maximum sensible cooling load in the building zone is 1 kW while maximum latent load varies up to 0.48 kW.

Principle:

Two-stage Dehumidification (Condensation): Depending on dew point of the air, cooling dehumidification and iso-thermal dehumidification can take place on fins inside cooling duct and on wall with TEC modules.

Heat transfer process: A steady state is reached when temperature of air remains constant with heat transfer from the cold side fins. Cold side fins are placed both on supply duct and inside room. Hot side fins are placed on exhaust duct and exterior of room wall surface. The height of heat transfer surface inside the duct is 0.5 m and height of heat transfer surface inside the room is 2.5 m. The condensation phenomenon at initial dehumidification will result in rapid temperature drop of cold side fins. The dehumidification will continue further at steady temperature of cold side fins. In order to improve the performance of fins for dehumidification, rapid elimination of condensed water is necessary. This is achieved by specially treated heat transfer surfaces (fins) with superhydrophilic or super water repellant surfaces [13].

The schematic of a building zone with two stage cooling through TEC modules by means of supply duct and wall mounted TEC modules with solar PV façade exhaust duct is illustrated in Figure 2. The performance characteristics with voltage variation of analyzed TEC1-12710 modules in TEC calculator is provided in Figure 3. The variation in theoretical values of COP (cooling) and temperature (cold) for ZTm = 1 is provided in Figure 4. The variation in theoretical values of cooling capacity with temperature difference is provided in Figure 5. The variation of theoretical heat transfer coefficient with height of heat transfer surface (fins) is provided in Figure 6. The theoretical variation of cooling capacity load served inside room with height of heat transfer surface (fins) is provided in Figure 7. The variation of theoretical exergy of air cooled inside the room with cold side temperature and Tout at 306 K is illustrated in Figure 8. All the results are based on theoretical values irrespective of actual performance values of the prototype TEC-PV device.

Figure 2.

Schematic of a building room zone with TEC modules and PV ventilated façade.

Figure 3.

Performance characteristics of TEC1-12710 module with voltage variation analyzed in TEC calculator.

Figure 4.

Variation in theoretical values of COP (cooling) and temperature (cold) for ZTm = 1.

Figure 5.

Variation in theoretical values of cooling capacity with temperature difference.

Figure 6.

Variation of heat transfer coefficient with height of heat transfer surface (fins).

Figure 7.

Variation of cooling capacity load served inside room with height of heat transfer surface (fins).

Figure 8.

Variation of theoretical exergy of air inside room with cold side temperature and Tout = 306 K.

5. Conclusion

Thermoelectric cooling (TEC) is one of the specialized areas in “Thermoelectrics.” This chapter has presented the summary of energy balance model parameters representing various performance characteristics of building-integrated thermoelectric cooling-photovoltaic (TEC-PV) devices. The cooling performance of thermoelectric modules for air-conditioning applications is a sustainable technology though not competitive with conventional vapor compression technology. There is significant growing interest level in thermoelectric cooling (TEC) because of their useful control aspects. This is because TEC modules are readily operated at partial load by changing the electric current. Moreover, there is increase in cooling COP with reduction of cooling power. Modular capability is the key merit of thermoelectric cooling (TEC) devices. These devices do not generate noise, thus are of considerable interest in many building applications in which noise is a significant factor. Furthermore, key advantage is the operation of thermoelectric cooling (TEC) devices without requirement of polluting refrigerants.

Air-conditioning of fresh outdoor air for direct indoor use through proper system design of supply air ventilation system and exhaust air ventilation system is another key benefit of thermoelectric cooling (TEC). In addition, photovoltaic (PV) roof-top power generation and photovoltaic (PV) ventilated façade are integrated into the system design, thus making it further sustainably sound in terms of input electricity requirements through green power and active ventilation system for supply and exhaust air. Finally, thermoelectric modules (TEM) offer air-conditioning solutions with flexible electrical loads in contemporary context of smart energy systems for buildings. Thermoelectric modules (TEM) have best advantage of their reversible operation as heating and cooling devices obtained by changing the direction of electric current. The future work comprises of advanced modeling and simulation of the presented prototype through thermoelectric modules (TEMs) operation as heating and cooling devices powered by photovoltaic modules.

Nomenclature

© 2018 The Author(s). Licensee IntechOpen. This chapter is distributed under the terms of the Creative Commons Attribution 3.0 License, which permits unrestricted use, distribution, and reproduction in any medium, provided the original work is properly cited.

How to cite and reference

Link to this chapter Copy to clipboard

Cite this chapter Copy to clipboard

Himanshu Dehra (July 11th 2018). Building-Integrated Thermoelectric Cooling-Photovoltaic (TEC-PV) Devices, Bringing Thermoelectricity into Reality, Patricia Aranguren, IntechOpen, DOI: 10.5772/intechopen.75472. Available from:

chapter statistics

365total chapter downloads

1Crossref citations

More statistics for editors and authors

Login to your personal dashboard for more detailed statistics on your publications.

Access personal reporting

Related Content

This Book

Next chapter

Feasibility and Numerical Analysis of Hybrid Photovoltaic (PV) Panels with Thermoelectric Cooling (TEC) Systems

By Arturo Monedero Khouri and Miguel Angel Olivares Robles

Related Book

First chapter

The Theory of Random Transformation of Dispersed Matter

By Marek Solecki

We are IntechOpen, the world's leading publisher of Open Access books. Built by scientists, for scientists. Our readership spans scientists, professors, researchers, librarians, and students, as well as business professionals. We share our knowledge and peer-reveiwed research papers with libraries, scientific and engineering societies, and also work with corporate R&D departments and government entities.