Abstract

Heat transfer performance of refrigerant on the condensation process is very important in the designing of condensation equipment, especially in air conditioning and refrigeration systems. The outstanding advantages of microfin tubes are reducing the weight and size of condensers and also reducing the amount of refrigerant on the system. Reviewing the general concept of condensation and detailing the formation of flow pattern map that is also the procedure to determine heat transfer coefficient and pressure drop during condensation process of refrigerant inside the horizontal microfin tubes would be considered. Also, a typical example will be presented to illustrate a detailed procedure to calculate the value of heat transfer coefficient and pressure drop during the condensation process in horizontal microfin tubes. The data results show that microfin tube J60 with 60 number of fins inside 8.96 mm inner diameter, 0.2 mm height of fin, 40o of apex angle and 18o of helix angle, the condensation procedure of R1234ze at 35°C, heat flux of 8.62 kW/m2, and mass flux of 222 kg/m2s that could be estimated with heat transfer coefficient would be reduced from 8160.4 [W/m2 K] to 1413.8 [W/m2 K] follow with quality x changes from 0.99 to 0.01, and the maximum pressure drop of this process is 3173.8 [Pa/m].

Keywords

  • condensation
  • microfin tube
  • flow pattern
  • heat transfer coefficient
  • pressure drop

1. Introduction

The condensation procedure of refrigerant is an important issue in the refrigeration industry. It is strongly supported to the optimization of equipment by using the right refrigerant with the very good thermodynamics properties and friendly environment and also by applying the microfin tube to conceive, design, implement, and operate in order to improve the heat transfer performance of system and to reduce the size, weight of the system, and the amount of refrigerant used in the system. The best performances of microfin tubes are consequences of the increase of the heat transfer and the increase of the pressure drop. To understand this phenomenon, many researchers these days are demonstrating to analyze and create the new models for flow pattern map, heat transfer, and pressure drop.

The group research of Thome and Cavallini with their colleagues [1, 2, 3, 4, 5, 6, 7, 8] is concentrated in condensation phenomena from the past to now. They presented so much information from experiments to empirical correlation for these fields, condensation on tubes (smooth, microfin tubes, micro channel, etc.) to consider about the formation of flow regime and also the penalization terms for heat transfer and pressure drop. With the group of Muzzio, Colombo and Lucchini [9, 10, 11, 12], they have been considering about an experimental facility to determine the flow patterns map and heat transfer performance of condensation on the difference geometries of microfin tubes with vary of refrigerant from R22 to R134a, and now they keep working with new refrigerant R1234ze and R1234yf. Besides, the group research of Sunden and Wu [13, 14, 15] is also focused on two-phase phenomena on microfin tube with some difference geometries for the current refrigerants by using their experimental data as well as collected data results from the others group to make an overview for their purposes.

More specific, about the flow pattern maps, until now is no new update of the maps for microfin tubes. Those are still presented the flow pattern map of condensation procedure of refrigerant on smooth horizontal tube, with the maps for condensation in microfin tubes are come from experimental map, it is not represented to build for other conditions. So that, apply the map on smooth tubes to estimate and get the stepping stone of the behavior and the changing of two-phase flow in the tube in circumstances. The map of Breber [16] was introduced in 1980 after 2 years the map of Tandon [17] was published, and in 2003 the map of Hajal [1], the group research of Thome and Cavallini, was presented.

About the performance of heat transfer, it cannot be denied that the outstanding performance of heat transfer in microfin tubes for condensation is normative to compare with smooth tubes. A huge number of experimental researches have been done to contribute to a lot of databases for establishing the predictive and empirical models to determine the heat transfer coefficients and pressure drop. General correlations for heat transfer of condensation processes on microfin tubes are published and used to estimate data results with an acceptable value to design condensers in refrigeration systems. Those are Yu and Koyama [18] Kedzieski and Goncalves [19], Han and Lee [20], Cavallini et al. [4]. Also, for the pressure drop of two-phase flow, some correlations were built for both evaporation and condensation procedure of Choi et al. [21], Goto et al. [22], and the others used for separated purposes. Some particular pressure drop correlations could be mentioned for condensation procedure of Kedzieski and Goncalves [19], Haraguchi et al. [23], and Cavallini et al. [24].

This chapter is focused on the condensation procedure of refrigerants in horizontal microfin tubes. Summary, the phenomenon, the effectiveness of fluid dynamics on the formation of flow pattern map, heat transfer coefficient, and pressure drop during condensation process under the empirical correlations are the examples to calculate condensation parameters.

Advertisement

2. Flow pattern map

With the aim of understanding the trend of increasing and decreasing heat transfer coefficient and pressure drop during the changing phase of refrigerants during condensation processes, the formation and transient of flow regime during the changing phase of condensation should be considered.

In order to draw a map of flow mechanism, there needs to be a classification of different regimes of flow in microfin tube, which relies on flow patterns such as slug, fully stratified, stratified wavy, helix, annular, and some regimes which are the combination of two or three flow pattern simultaneously happened. Many parameters have to define as an input parameter such as geometries of tube, refrigerants (consider about thermophysical and thermodynamic of refrigerant) heat flux, and mass flux that could take microfin tube from Colombo et al. as an example as shown in Figure 1, and the geometrical of microfin tube consists of number of fins, fin height, apex angle, and helix angle besides the inner and outer diameters of tubes.

Figure 1.

A geometrical parameter of microfin tube J60 [9].

It is could be considered about an experimental result of flow pattern map in microfin tube from the group of Colombo et al. [10], and they classified the pattern into five regimes: slug flow, stratified wavy flow, intermittent (slug, stratified wavy, and helix), helix flow, and annular flow. They showed their map as an indifferent dot of data points and compared it with the map of Hajal et al. as presented in Figure 2.

Figure 2.

Flow pattern results observed from experiment of Colombo et al. [10] draw on the map of Hajal [9].

2.1 The flow pattern map of Breber et al.

Breber et al. [16] published their map in 1980, and the map could be used for smooth tube that divided into four quadrant zones based on two parameters: dimensionless gas velocity JG– and turbulent-turbulent Martinelli parameter Xtt (annular and mist-annular flow, wavy and stratified flow, slug and plug flow, and bubble flow) and some transition zones between each other.

Dimensionless gas velocity JG is given by:

JG=G.xg.d.ρGρLρGE1

Turbulent-turbulent Martinelli parameter Xtt is given by:

Xtt=1xx0.9ρvρl0.5μlμv0.1E2

Transition criteria for flow regimes on the map:

Zone 1Zone 2Zone 3Zone 4
Annular flowWavy and stratifiedSlug flowBubble (at high reduced pressure)
JG > 1.5
X < 1.0
JG < 0.5
X < 1.0
JG < 1.5
X > 1.5
JG > 1.5
X > 1.5

2.2 The flow pattern map of Tandon et al.

The map of Tandon et al. [17] is presented in five zones of patterns: spray, annular and semi-annular, wavy, slug, and plug. They used two dimensionless numbers to draw their map: gas velocity JG and (1 − α)/α with α is the void fraction.

Dimensionless gas velocity JG is given by:

JG=G.xg.d.ρGρLρGE3

Void fraction is defined from Smith’s equation (1970) is given as follows:

α=1+ρGρL1xx0.4+0.6ρLρG+0.41xx1+0.41xx1E4

Transition criteria for flow regimes on the map.

SprayAnnular and semi-annularWavySlugPlug
JG ≥ 6
(1-α)/α ≤ 0.5
1 ≤ JG ≤ 6
(1-α)/α ≤ 0.5
1 ≤ JG
(1-α)/α ≤ 0.5
0.01 ≤ JG ≤ 0.5
(1-α)/α ≥ 0.5
JG ≤ 0.01
(1-α)/α ≥ 0.5

2.3 The flow pattern map of Hajal et al.

The map of Hajal et al. [1] introduced the logarithmic mean void fraction instead of homogeneous void fraction to define the stratification of liquid and vapor and is based on the transient line between mass velocity and vapor quality to classify the regimes of patterns. The procedure to calculate step by step is shown as follows:

  • Step 1: Calculate logarithmic mean void fractions ε based on homogeneous and nonhomogeneous void fractions:

    Homogeneous: εh

    εh=1+1xxρVρL1E5

    Nonhomogeneous: εra

    εra=xρV1+0.121xxρV+1xρL+1.181xρLρV0.25GρL0.51E6

    Logarithmic mean void fractions: ε

    ε=εhεralnεhεraE7

  • Step 2: Determine the stratified angle θstrat and geometrical parameters for two-phase flow in a circular tube:

    + The stratified angle θstrat:

    θstrat=2π2{π1ε+3π21/3121ε+1ε13ε1312001εε121ε1+41ε2+ε2}E8

    + Geometrical parameters for two-phase flow in a circular tube:

    ALD=ALD2=A1εD2E9
    AVD=AVD2=D2E10
    hLD=0.51cos2πθstrat2E11
    PiD=sin2πθstrat2E12

  • Step 3: Use the value from step 1 and 2 to determine the transient lines:

    + Transient line of stratifine wavy: Gwavy:

    Gwavy=16AVD3gDρLρVx2π212hLD120.5π225hLD2WeFrL1.023+10.5+5075ex20.972/x1xE13

G_wavy_min occur at x_min.

then, for x > x_min → G_wavy = G_wavy_min.

+ Transient line of fully stratified: Gstrat:

Gstrat=226.33ALDAVD2ρVρLρVμLgx21xπ31/3+20xE14

+ Marttineli parameter: X_IA:

XIA=0.2914ρVρL1/1.75μLμV1/7+11E15

+ Transient line of mist flow: Gmist:

Gmist=7680AVD2gDρLρVx2π2ξFrWeL0.5E16
ξ=1.138+2logπ1.5ALD2E17

G_mist_min occur at x_min.

then, for x > x_min → G_mist = G_mist_min.

+ Transient line of bubbly flow: Gbubbly:

Gbubbly=256AVDALD2D1.25ρLρLρVg0.31641x1.75π2PiDμL0.251/1.75E18

  • Step 4: Draw the flow pattern map of condensation in 2D with the transient lines of mass velocity and vapor quality. The result of Hajal flow pattern map of condensation R134a in a smooth tube of 8 mm diameter at 40°C temperature with initial value of mass velocity 300 kg/m2s is shown in Figure 3.

Figure 3.

Flow pattern map of Hajal et al. [1].

Advertisement

3. Two-phase heat transfer coefficient in condensation

3.1 The correlation of Cavallini et al.

The correlation of Cavallini et al. [4] was published in 2009 which derived 558 data points, experimental results, and validated databases from other researches. The working range of microfin tubes: h/D < 0.04 (fin height/fin tip diameter) and helix angle is from 0° to 30°.

D: fin tip diameter; ng: fins number; h: fin height; β: spiral angle; γ: apex angle.

Heat transfer coefficient of two phases could be determined from two zones as follows:

α=αA3+αD30.333E19

Heat transfer coefficient for the ΔT independent zone αA is given as follows:

αA=αAS.A.CE20
αAS=αLO1+1.128x0.817ρLρG0.3685μLμG0.23631μGμL2.144PrL0.1E21
αLO=0.023λLDReLO0.8PrL0.4=0.023λLDGDμL0.8PrL0.4E22
A=1+1.119Fr0.3821Rx10.3586E23
Fr=G2gDρLρG2E24
Rx=2h.ng1sinγ/2πDcosγ/2+11cosβE25
C=1ifnopt/ng0.8E26
C=nopt/ng1.904ifnopt/ng<0.8E27
nopt=4064.4D+23.257E28

Heat transfer coefficient for the ΔT dependent zone αD is given as follows:

αD=C2.4x0.1206Rx11.466C10.6875+1αD,S+C1x0.087Rx.αLOE29
αD,S=0.7251+0.7411xx0.3321λL3.ρLρLρGg.hLGμL.D.T0.25E30
C1=1ifJGJGE31
C1=JG/JGifJG<JGE32
JG=xGgDρGρLρG0.5E33
JG=0.67.54.3Xtt1.111+13+2.530.3333E34
T=TsTwE35

3.2 The correlation of Han et al.

Heat transfer coefficient correlation of Han et al. [20] was proposed in 2005, which was formed from a database of three various refrigerant R134A, R22, and R410A and four different inner diameter of microfin tubes di = 8.92, 6.46, 5.1, 4 mm. Some hypotheses were used to build this correlation as the uniform of liquid film thickness and turbulent flow in vapor core, neglect the radial temperature gradients and temperature in the vapor, and assume that the saturation temperature is constant at temperatures in the vapor core and at liquid-vapor interface.

Heat transfer coefficient of two-phase flow is given as follows:

h=ρcput0.904e+0.592Pr0.729+2.1335lnδ/eE36

Liquid film thickness is given as follows:

δ=1λDi4E37

Void fraction from Yashar λ is given as follows:

λ=1+1xxρgρl1+1.3Relo0.19ρlρg0.72x1x0.51E38

With Relo is Reynolds of liquid only, e+ is roughness Reynolds number and ut is turbulent friction (or shear velocity) and is given as follows

e+=eutvE39
ut=τρ0.5=Di4ρdPdzfr0.5E40

where e is the fin height, p = πDi/ntanβ is the axial fin pitch, Di is the inside tube diameter, n is the number of fins, and β is the spiral angle.

If liquid film thickness is less than fin height, the term of logarithm ln(δ/e) is neglected.

3.3 The correlation of Kedzieski and Goncalves

Kedzieski and Goncalves in 1999 [19] collected 1704 data points from their experimental database to regress correlation. Their experimental data recorded in various working conditions as from four different refrigerants R134a, R410A, R125, and R32 in one microfin tube that has 8.91 mm root diameter, 0.2 mm fin height, and 50°apex angle, and the model was derived as follows:

Nu=h2DhKl=2.256Reβ1Jaβ2Prβ3PrPcβ4log10PrPcβ5Svβ6E41

β1=0.303; β2=0.232xq; β3=0.393; β4=0.578xq2; β5=0.474xq2; β4=2.531xq2.

The authors also supplied the simpler form with larger uncertainty:

Nu=h2DhKl=4.94Reβ1Prβ3PrPcβ4log10PrPcβ5Svβ6E42

β1=0.235; β3=0.308; β4=1.16xq2; β5=0.887xq2; β4=2.708xq2

Ja=ifgCpr,lTsE43
Ts=TsTwE44
Sv=vvvlvE45
v=xqvv+1xqvlE46
Re=GDh/μr,lE47

where Dh is the hydraulic diameter.

3.4 The correlation of Yu and Koyama 1998

The correlation of Yu and Koyama [18] for microfin tubes was updated from the correlation of Haraguchi et al. for smooth tubes and was introduced in 1998. The procedure to determine heat transfer coefficient by Nusselt number is presented as follows:

The Nusselt number of two-phase flow is given by:

Nu=NuF2+NuB21/2E48
NuF=0.1520.3+0.1PrL1.1Φv/XttReL0.68E49
Φv=1.1+1.3GXttgdiρvρlρv0.35E50
NuB=0.725ηA14.HξGa.PrLPhL1/4E51
Hξ=ξ+Aξ1ξE52
A=101ξ0.18.0E53

where di is the mean inner diameter of tube, ηA is the enlargement ration of heat transfer area, and Ph_L is the phase change number.

ξ=1+ρvρl1xx0.4+0.6ρvρl+0.41xx1+0.41xx1E54
ReL=G1xdiμLE55
Ga=gρL3di3μL2E56
PhL=CpLTsatTwihvlE57
Advertisement

4. Pressure drop

4.1 The correlation of Han et al.

Han et al. [20] not only presented the correlation for heat transfer coefficient as aforementioned but also introduced a new correlation to define pressure drop. It is could be considered as follows:

Friction pressure gradient of two phases is given as follows:

dPdzfr=Φl2flG1x22DiρlE58
fl=0.193G1xDiμl0.024pe0.539E59
Φl2=2.684Xtt1.946E60
Xtt=1xx0.9ρvρl0.5μlμv0.1E61

4.2 The correlation of Kedzieski and Goncalves

In 1999, Kedzieski and Goncalves [19] modified the correlation of Pierre 1964 with confirmation by their own experimental data from four refrigerants such as R134a, R410A, R125, and R32 in their microfin tube that has 8.91 mm root diameter, 0.2 mm fin height, and 50°apex angle, and presented the correlation as follows:

pL=pfL+pmL=G2fvtp,out+vtp,indh+vtp,outvtp,inLE62
dh=4Accosβ/n.SpE63
f=0.002275+0.00933expe/0.003dfrReh,LO1/4.16+532e/dfrKf0.211E64
Reh,LO=Gdh/μlE65
Kf=x.hlvgLE66

where dh is the hydraulic diameter, dfr is the fin root diameter, and e is the fin height.

4.3 The correlation of Harraguchi

Harraguchi et al. [23] presented their correlation for two-phase friction pressure drop from their experimental results with R134a, R123, and R22 in a horizontal smooth tube and a horizontal microfin tube in 1993.

Two-phase friction pressure drop is given as follows:

dPdzf=Φv2dPdzv=Φv22fe,vGx2/ρvdeE67
de=4AcπE68
fe,v=0.046Ree,v0.2E69
Φv=1.1+1.3XttG/gdeρvρlρv0.50.35E70
Ree,v=Gxde/μvE71
Xtt=1xx0.9ρvρl0.5μlμv0.1E72
Advertisement

5. Example

The condensation of refrigerant R1234ze inside horizontal microfin tube at 35°C, heat flux of 8.62 kW/m2, and mass flux of 222 kg/m2s using the microfin tube J60 with the geometrical parameters: 60 number of fins, 8.96 mm inner surface diameter, 0.2 mm fin height, 18o of helix angle, and 40o of apex angle is considered. Heat transfer coefficient and pressure drop during condensation process are determined. Saturation to wall temperature difference is kept constant (5°C).

Solve:

Thermal properties of refrigerant R1234ze at saturation temperature tsat = 35°C is listed in Table 1.

Refrigerant: R1234ze, molar mass: M = 114 g/mol, pcritical = 3.64 MPa

Reduce pressure: pr = psat/pcritical = 0.66756/3.64 = 0.1834

Heat flux: q = 15.3 kW/m2

Mass flux: G = 220 kg/m2 s

Microfin tube: N = 60 number of fins, dr = 8.96 mm, h = 0.2 mm, β = 18o; γ = 40o

5.1 Heat transfer coefficients

Quality x = 0.5 could be taken as an example to present the procedure to calculate heat transfer coefficient and pressure drop of boiling refrigerant inside horizontal microfin tube, with the data point of quality x from 0 to 1 that can be determined with the same method.

Applied the correlation of Cavallini et al. to calculate heat transfer coefficient as below:

  • Heat transfer coefficient of two phases could be determined from two zones as follows:

    α=αA3+αD30.333

  • Heat transfer coefficient for the ΔT independent zone αA is give as follows:

    αA=αAS.A.C

+ Calculate αAS:

αLO=0.023λLDGDμL0.8PrL0.4=0.0237.098.1028.96.103220.8.96.1031.772.1040.83.5480.4
αLO=521.87
αAS=αLO1+1.128x0.817ρLρG0.3685μLμG0.23631μGμL2.144PrL0.1
αAS=521.87[1+1.1280.50.817112935.320.36851.772.1041.269.1050.2363(11.269.1051.772.104)2.1443.5480.1]
αAS=2199.82

+ Calculate A:

Fr=G2gDρLρG2=22029.81.8.96.103112935.322=0.46035
Rx=2h.ng1sinγ/2πDcosγ/2+11cosβ
Rx=2.2.104.60.1sin40/2π.8.96.103.cos40/2+11cos18=1.79
A=1+1.119Fr0.3821Rx10.3586
A=1+1.1190.460350.3821.1.7910.3586=2.383

+ Calculate C:

nopt=4064.4D+23.257=4064.48.96.103+23.257=59.7
C=1ifnopt/ng0.8
C=nopt/ng1.904ifnopt/ng<0.8

In this case:

noptng=59.760=0.9950.8

  • C = 1

    Heat transfer coefficient for the ΔT independent zone αA is given as follows:

    αA=αAS.A.C=2199.82.2.383.1=5242.213

  • Heat transfer coefficient for the ΔT dependent zone αD is given as follows:

+ Calculate C1:

JG=xGgDρGρLρG0.5=0.5.2209.81.8.96.103.35.32.112935.320.5
JG=1.8878

Martinelli number is given as follows:

Xtt=1xx0.9ρGρL0.5μLμG0.1=10.50.50.935.3211290.51.772.1041.269.1050.1=0.2302
JG=0.67.54.3Xtt1.111+13+2.530.3333
JG=0.67.54.30.23021.111+13+2.530.3333=1.3994
C1=1ifJGJG
C1=JG/JGifJG<JG

In this case: JG = 1.8878 > J*G = 1.3994 = > C1 = 1

+ Calculate αD,S:

T=TsTw=5
αD,S=0.7251+0.7411xx0.3321λL3.ρLρLρGg.hLGμL.D.T0.25
αD,S=0.7251+0.74110.50.50.33217.098.1023.1129.112935.32.9.81.159.861.772.104.8.96.103.50.25
αD,S=226.31

= > Heat transfer coefficient for the ΔT dependent zone αD is given as follows:

αD=C2.4x0.1206Rx11.466C10.6875+1αD,S+C1x0.087Rx.αLO
αD=1.2.40.50.1206.1.7911.46610.6875+1.226.31+1.10.50.087.1.79.521.87
αD=634.51

Heat transfer coefficient of condensation at x = 0.5 is given as follows:

α=αA3+αD30.333
α=5242.2133+634.5130.333=5200.58W/m2K

5.2 Pressure drop

5.2.1 The correlation of Harraguchi

Harraguchi et al. [23] presented their correlation for two-phase friction pressure drop from their experimental results with R134a, R123, and R22 in a horizontal smooth tube and a horizontal microfin tube in 1993.

Two-phase friction pressure drop is given as follows:

Xtt=1xx0.9ρGρL0.5μLμG0.1=10.50.50.935.3211290.51.772.1041.269.1050.1=0.2302
de=4AcπD=8.96.103mm
Ree,v=G.x.deμv=220x0.5x0.008961.269.105=77667.45
fe,v=0.046Ree,v0.2=0.046.77667.450.2=0.004838
Φv=1.1+1.3XttG/gdeρvρlρv0.50.35
Φv=1.1+1.30.2302.220/9.81.0.00896.35.32.112935.320.50.35
Φv=2.3378
dPdzf=Φv2dPdzv=Φv22fe,vGx2ρvde=
dPdzf=Φv2dPdzv=Φv22fe,v,GoGx2ρvde=2.33782.2.0.004838220.0.5235.32).(0.00896=2022.105Pam

Condensation process of R1234ze at 35°C inside horizontal microfin tube J60 with quality change from x = 0.99 to x = 0.01 could be estimated with heat transfer performance which are performed in heat transfer and pressure drop in Table 2.

PropertyUnitValuePropertyUnitValue
Tsat[°C]35Psat[MPa]0.66756
ρL[kg/m3]1129λL[W/m-K]7.098E−02
ρV[kg/m3]35.32λV[W/m-K]1.452E−02
νL[m3/kg]8.857E−04μL[Pa-s]1.772E−04
νv[m3/kg]2.831E−02μV[Pa-s]1.269E−05
hLV[kJ/kg]159.86PrL[−]3.548
CpL[kJ/kg-K]1.421PrV[−]0.904
CpV[kJ/kg-K]1.034σ[N/m]7.578E−03

Table 1.

Properties of R1234ze.

xαdP/dz
[−][W/m2K][Pa/m]
0.998160.42448.5
0.957930.42968.4
0.907641.13151.4
0.857349.03173.8
0.807053.83112.0
0.756755.32996.4
0.706453.02843.2
0.656146.92662.9
0.605836.42462.4
0.555521.12247.4
0.505200.62022.1
0.454874.11790.4
0.404541.01555.5
0.354200.21320.5
0.303850.11088.6
0.253489.1862.8
0.203114.7646.6
0.152722.8444.1
0.102306.4260.7
0.051849.2104.9
0.011413.813.1

Table 2.

Heat transfer performance of condensation.

Advertisement

6. Conclusions

An overview of the condensation procedure of refrigerant inside microfin tubes has been done with the flow pattern maps and heat transfer performance. The list of some correlations to determine heat transfer and pressure drop during the condensation process has been presented. Besides, an example has been introduced step by step to define heat transfer coefficient and pressure drop of condensation process with refrigerant R1234ze inside horizontal microfin tube J60. Until now, this field is still not getting too much data to get the general correlation for all types of microfin tubes and all kinds of refrigerants. Therefore, these fields are strongly attracted by scientists around the world.

Advertisement

Acknowledgments

We acknowledge the support of time and facilities from Ho Chi Minh City University of Technology (HCMUT), VNU-HCM for this study.

References

  1. 1. el Hajal J, Thome JR, Cavallini A. Condensation in horizontal tubes, part 1: Two-phase flow pattern map. International Journal of Heat and Mass Transfer. 2003;46(18):3349-3363. DOI: 10.1016/S0017-9310(03)00139-X
  2. 2. Cavallini A, del Col D, Matkovic M, Rossetto L. Frictional pressure drop during vapour-liquid flow in minichannels: Modelling and experimental evaluation. International Journal of Heat and Fluid Flow. 2009;30(1):131-139. DOI: 10.1016/j.ijheatfluidflow.2008.09.003
  3. 3. Thome JR, el Hajal J, Cavallini A. Condensation in horizontal tubes, part 2: New heat transfer model based on flow regimes. International Journal of Heat and Mass Transfer. 2003;46(18):3365-3387. DOI: 10.1016/S0017-9310(03)00140-6
  4. 4. Cavallini A, del Col D, Mancin S, Rossetto L. Condensation of pure and near-azeotropic refrigerants in microfin tubes: A new computational procedure. International Journal of Refrigeration. 2009;32(1):162-174. DOI: 10.1016/j.ijrefrig.2008.08.004
  5. 5. Cavallini A et al. Condensation in horizontal smooth tubes: A new heat transfer model for heat exchanger design. Heat Transfer Engineering. 2006;27(8):31-38. DOI: 10.1080/01457630600793970
  6. 6. Cavallini A, Bortolin S, del Col D, Matkovic M, Rossetto L. Condensation and Vaporization of Halogenated Refrigerants Inside a Circular Minichannel. International Refrigeration and Air Conditioning Conference. 2008. p. 886. Available online: http://docs.lib.purdue.edu/iracc/886
  7. 7. Cavallini A, Censi G, del Col D, Doretti L, Longo GA, Rossetto L. Condensation of halogenated refrigerants inside smooth tubes. HVAC and R Research. 2002;8(4):429-451. DOI: 10.1080/10789669.2002.10391299
  8. 8. Cavallini A, Brown JS, del Col D, Zilio C. In-tube condensation performance of refrigerants considering penalization terms (exergy losses) for heat transfer and pressure drop. International Journal of Heat and Mass Transfer. 2010;53(13–14):2885-2896. DOI: 10.1016/j.ijheatmasstransfer.2010.02.007
  9. 9. Colombo LPM, Lucchini A, Molinaroli L, Niro A, Phan TN, Pittoni PG. Flow patterns during flow boiling and convective condensation of R1234ze (E) inside a microfin tube. In: 5-6th Thermal and Fluids Engineering Conference (TFEC), ASTFE Digital Library. 2021. pp. 109-119. DOI: 10.1615/TFEC2021.boi.032115
  10. 10. Muzzio A, Niro A, Garavaglia M. Flow patterns and heat transfer coefficients in flow-boiling and convective condensation of R22 inside a microfin tube of new design. Heat Transfer Conference. 1998;2:291-296
  11. 11. Muzzio A, Niro A, Arosio S. Heat transfer and pressure drop during evaporation and condensation of R22 inside 9.52-mm O.D. microfin tubes of different geometries. Journal of Enhanced Heat Transfer. 1998;5:39-52. DOI: 10.1615/JEnhHeatTransf.v5.i1.40
  12. 12. Colombo LPM, Lucchini A, Muzzio A. Flow patterns, heat transfer and pressure drop for evaporation and condensation of R134A in microfin tubes. International Journal of Refrigeration. 2012;35(8):2150-2165. DOI: 10.1016/j.ijrefrig.2012.08.019
  13. 13. Wu Z, Sundén B, Wadekar V, Li W. Heat transfer correlations for single-phase flow, condensation, and boiling in Microfin tubes. Heat Transfer Engineering. 2015;36(6):582-595. DOI: 10.1080/01457632.2014.939531
  14. 14. Wu Z, Sundén B. Frictional pressure drop correlations for single-phase flow, condensation, and evaporation in microfin tubes. Journal of Heat Transfer. 2015;138(2):022901. DOI: 10.1115/1.4031268
  15. 15. Guo SP et al. Condensation and evaporation heat transfer characteristics in horizontal smooth, herringbone and enhanced surface EHT tubes. International Journal of Heat and Mass Transfer. 2015;85:281-291. DOI: 10.1016/j.ijheatmasstransfer.2015.01.115
  16. 16. Breber G, Palen JW, Taborek J. Prediction of horizontal tubeside condensation of pure components using flow regime criteria. Journal of Heat Transfer. 1980;102(August):471. DOI: 10.1115/1.3244325
  17. 17. Tandon TN, Varma HK. A new flow regimes l a p for condensation inside horizontal tubes. Journal of Heat Transfer. 1982;104(November):763
  18. 18. Yu J, Koyama S. Condensation Heat Transfer of Pure Refrigerants in Microfin Tubes. International Refrigeration and Air Conditioning Conference. 1998. p. 431. Available online: http://docs.lib.purdue.edu/iracc/431
  19. 19. Kedzierski MA, Goncalves JM. Horizontal convective condensation of alternative refrigerants within a micro-fin tube. Journal of Enhanced Heat Transfer. 1999;6(2):161-178. DOI: 10.1615/JEnhHeatTransf.v6.i2-4.90
  20. 20. Han D, Lee KJ. Experimental study on condensation heat transfer enhancement and pressure drop penalty factors in four microfin tubes. International Journal of Heat and Mass Transfer. 2005;48(18):3804-3816. DOI: 10.1016/j.ijheatmasstransfer.2005.02.041
  21. 21. Choi J, Kedzierski M, Domanski P. Generalized pressure drop correlation for evaporation and condensation in smooth and micro-fin tubes. Proceedings of the International Institute of Refrigeration (IIR). Thermophysical Properties and Transfer Processes of New Refrigerants, Paderborn, 1, GE. 2001;1:986. Available online: https://tsapps.nist.gov/publication/get_pdf.cfm?pub_id=860849
  22. 22. Goto NIM, Inoue N. Condensation and evaporation heat transfer of R410A inside internally grooved horizontal tubes. International Journal of Refrigeration. 2001;24(1):528-538. DOI: 10.1016/j.ijrefrig.2009.09.008
  23. 23. Haraguchi TFH, Koyama S. Condensation heat transfer of refrigerants HFC134a, HCFC123 and HCFC22 in a horizontal smooth tube and a horizontal microfin tube. In: Proc. 30th National Heat Transfer Symp. of Japan; Yokohama. 1993. pp. 343-345
  24. 24. Cavallini A, Del Col D, Doretti L, Longo GA, Rossetto L. Heat transfer and pressure drop during condensation of refrigerants inside horizontal enhanced tubes. International Journal of Refrigeration. 2000;23(1):4-25. DOI: 10.1016/S0140-7007(99)00032-8