Maximum of the absolute instantaneous error of all techniques after convergence of the algorithms.
1. Introduction
The increasing use of power electronic devices in power systems has been producing significant harmonic distortions, what can cause problems to computers and microprocessor based devices, thermal stresses to electric equipments, harmonic resonances, as well as aging and derating to electrical machines and power transformers [1–3]. The most important problems that have been reported in the literature concerns to the difficulty of the frequency control within the micro-grids and the increase of the total harmonic distortion. These two factors may negatively impact on the protection system, power quality analysis and intelligent electronic devices (IEDs), in which digital algorithms assume that the fundamental frequency is constant. Based on this fact, there has been an increasing interest in signal processing techniques for detecting and estimating harmonic components of time-varying frequencies. Their correct estimation has become an important issue in measurement equipment and compensating devices. Although many methods have been proposed in the literature, it still remains difficult to detect and estimate harmonics of time-varying frequencies [4, 5]. The harmonic components (voltage or current) can change its frequencies due to continuous changes in the system configuration and load conditions, to the rapid proliferation of distributed resources, and to possibilities of new operational scenarios (e.g., islanded microgrids). Also the need for massive monitoring of networks is unquestionable within the concept of
The concept of time-varying harmonics came recently to the vocabulary of power systems engineers, because more and more nonlinear loads, with dynamic behavior, are being connected to power systems and the fundamental frequency is experiencing a large range of variation. These factors have putting in check the traditional stationary spectral analysis methods, and many techniques for improving harmonics measurement have been proposed in recent years. Parametric and nonparametric methods that commonly have been used by the community of signal processing have been applied to power system harmonic estimation. These methods have in common that they need to estimate the fundamental frequency to adjust some internal parameters, like filter coefficients. The challenge is producing a harmonic estimator with high convergence ratio, high accuracy, low computational burden and immunity to the presence of interharmonic: conditions that are not ease to simultaneously deal with. The most used technique for harmonics estimation is based on the discrete Fourier transform (DFT) [8, 10]. The DFT algorithm is attractive because of its low computational complexity and its simple structure. However, DFT does not perform well if power system frequency varies around the nominal value. Several other techniques have been proposed in the literature for harmonic estimation. However, the DFT still appear to be the preferred algorithm mainly due to its simplicity.
2. Power quality and smart grid
The term “
One of the promises of the
An adequate power quality should guarantees electromagnetic compatibility between all equipment connected to the grid. Then, an important issue for the successful and efficient operation of smart grids is the introduction of advanced, flexible, robust, and cooperative set of signal processing and computational intelligent techniques for power quality analysis. With this set of techniques, an effective and extensive smart monitoring system can be devised and deployed. Such a monitoring system have to allow for the monitoring of such as voltage, current, bidirectional energy consumption at distribution transformers, substations transformers, smart meters, distribution feeders, distribution switching devices, and strategically installed power quality monitors in the power systems.
3. Harmonic estimation techniques: Before and after smart grid
Consider the monitored power line signal, after processed by the analog anti-aliasing filter, be expressed by
where
Assuming
The goal of harmonic estimation techniques is to provide estimates of the parameters
Basically, we can say that before
4. Methods for estimating steady-state harmonics
Methods for estimating steady-state harmonics are more simple than time-varying ones, and its algorithms do not use information of the fundamental frequency of the signal under estimation. In what follows, we describe four algorithms.
4.1. Discrete fourier transform
The most common and the most used technique for steady-state harmonic estimation is the discrete Fourier transform (DFT) [8-10]. The DFT method is simple and easy to be implemented in monitoring systems, but its application for time-varying harmonics is not recommended.
Given the discrete signal
and
respectively, where,
and
in which
The DFT algorithm is very simple and its implementation is easy for real-time application. However, if the fundamental frequency is not nominal and constant, then the estimates can carry significant errors.
4.2. Demodulation
The demodulation technique presented in [15] can be used to estimate the parameters of harmonics as point out in [16]. In similar way to the DFT technique the demodulation technique can give erroneous results if its filter is fixed.
The k-th harmonic parameters can be estimated by
and
in which
and
respectively, where
4.3. Goertzel
The Goertzel technique uses a second-order infinite impulse response filter to estimate the parameters of the
The amplitude and phase of the k-th harmonic is estimated, respectively, by
and
in which
and
where
4.4. Linear least squares
The linear least squares (LS) algorithm estimates several harmonics in one evaluation instead of a unique estimate [18]. Its advantage is the acquisition of several harmonics in only one evaluation. However the computational burden is high.
Basically, the LS algorithm has as a result the vector given by
Thus, the amplitude and phase of the k-th harmonic (k ∈ [1, 2,...,
and
The vector
where
and
In this kind of technique, the number of harmonic has to be known a priori. Otherwise, the performance can be considered reduced, also, the computational complexity is higher due to the matrix operations.
5. Methods for estimating time-varying harmonics
Methods for estimating time-varying harmonics consider that not only the amplitudes and phases of harmonics change, but also the fundamental frequency, and consequently, the harmonics frequencies. Thus, the frequency estimation is generally required to improve the algorithms.
5.1. Discrete fourier transform with sampling frequency control
The main weakness of the DFT is to estimate the harmonics when the sampling frequency is not synchronous with the fundamental frequency. In order to guarantee this synchronism we can control the sampling frequency as shown in Fig. 1. This method reduces and can also eliminate the errors caused by the mismatch between the fundamental frequency and the sampling frequency, however, it requires a robust and controllable ADC converter and a frequency estimation algorithm. As a result, its use is not recommended.
5.2. Discrete fourier transform with signal resample
An alternative to the problem of synchronization of the sampling frequency when the sampling frequency is constant and not controllable is resampling the original signal before the harmonic estimation with the DFT. The drawback of this approach is the high computation complexity required by the resample process. Also, a frequency estimation technique is required to control the resampling process. Fig. 2 shows the block diagram of this strategy.
5.3. Discrete fourier with window
An interesting way of improving the DFT algorithm is using a window in each block of data before the evaluation of the DFT. The windowing of the data can deal with the spectral leakage of the DFT caused by the frequency deviation by adding some computational burden to the algorithm. Some windows generally used are the triangular and Hanning. The coefficients of a Hanning window are computed from the following equation:
The triangular window has its coefficient given by
for
for
5.4. Demodulation
An interesting method based on demodulation technique for estimating time-varying harmonics is presented in [16]. This technique can provide very accurate estimates with a reasonable computational complexity.
The block diagram of the demodulation technique is depicted in Fig. 3. The LP blocks implement identical low-pass filters and the blocks COS and SIN implement the demodulation signals expressed by
and
respectively. The term
where
The blocks AMP and PHAS implement, respectively, the expressions
and
respectively, where
In this technique, it is applied a approach to control the demodulation signals (blocks COS and SIN) and the frequency response of the low-pass filters (blocks LP) by the power frequency estimate, which is implemented by the block FREQ. The low pass filters are finite impulse response (FIR) filters which are controlled by a frequency estimator.
5.5. Non linear least squares
The nonlinear least squares (NLS) uses the same expressions of the linear least squares for evaluate the harmonics [18]. The advantage of this approach is the improving of the estimates related to the linear version, however, the additional searching of the optimal frequency introduces additional delay in the technique and computational burden.
The NLS algorithm test several values of
Thus, with the optimal
6. Performance analysis
In order to analyze the performance of the described techniques the following signal is considered:
where
Fig. 4 shows time estimations of the amplitude of the 3rd harmonic considering a 50% drop in the amplitude of signal when the fundamental frequency is equal to 60 Hz. Estimation delays of 2 cycles of the fundamental component are noted because the twocycles version of each technique was considered. However, when the fundamental frequency is set to 60.5 Hz such techniques exhibit significant errors in the estimates (time variations), as can be seen in Fig. 5. Otherwise, the time-varying techniques significantly improve the estimates. These results are depicted in Fig. 6. Table 1 shows the maximum of the absolute instantaneous error of all techniques after convergence of the algorithms (after the 50% drop in the amplitude of signal).
The best results are achieved with the demodulation and NLS techniques. Considering only these last two techniques, the errors were evaluated when the fundamental frequency varies between 59.5 Hz to 60.5 Hz for the 25th harmonic (See Fig. 7). Also, it is important to note that the improvement achieved by the DFT with hanning and triangular windows is significant compared with the standard DFT method as can be seen by Figs. 5 and 6. In order to better show this improvement, the errors, considering the DFT, DFT with triangular window and DFT with hanning window, were evaluated when the fundamental frequency varies between 59.5 Hz and 60.5 Hz for the 25th harmonic (Fig. 8).
|
|
DFT | 4.7655 |
Goertzel | 4.7655 |
LS | 4.7655 |
Demodulation (steady-state) | 4.7655 |
DFT with hanning window | 0.7479 |
DFT with triangular window | 0.2296 |
NLS | 0.0842 |
Demodulation (time-varying) | 0.0660 |
7. What is next and needed?
Most existing end-user equipment (computer, television, lamps, etc) emit almost exclusively at the lower odd integer harmonics, but there are indications that modern devices including certain types of distributed generators emit a broadband spectrum [11–14]. The measurement of these low levels of harmonics at higher frequencies will be more difficult than for the existing situation with higher levels and lower frequencies. This might require the development of new measurement techniques including a closer look at the frequency response of existing instrument transformers. Consequently, harmonic estimation of higher order harmonics will be very important and needed. In this case the sampling frequency should be increased to satisfy the Nyquist criterion and faster
Power electronic based photovoltaic solar and wind energy equipment may emit disturbances causing voltage fluctuations and unbalance. These types of electric sources will have large presence in the future grids very large. In order to deal with this new scenario, the harmonic estimation algorithms must be immune to higher voltage fluctuations and interharmonics.
An important issue associated with smart grid in regarding to harmonic estimation is the real time estimation of several harmonics instantaneously, including higher-order harmonics. Higher-order harmonics will be more and more important to estimate due its influence in sensitive electronics devices. Also, the dynamic and diversity of smart grid will demand different set of techniques to analyze the behavior of the time-varying harmonics. For deal with these issues, the use of reconfigurable hardware that allow the exchange of features between existing monitoring devices is of ultimate importance.
8. Concluding remarks
Several methods and techniques were developed so far for estimating steady-state and timevarying harmonics. Although several techniques can deal with time-varying harmonics, the implementation of them is incipient. However, the needs and demands related to
Although
References
- 1.
New trends in active filters for power conditioning,H Akagi IIEEE Trans. Ind. Appl. ,32 6 1312 1322 November1996 - 2.
Harmonics in large systems, andN. R Watson J Arrigala Electric Power System Research ,66 15 29 2003 - 3.
Derating of Asymmetric Three- Phase Transformers Serving Unbalanced Nonlinear Loads, andM. A. S Masoum andP. S Moses A. S Masoum IEEE Trans. Power Delivery ,23 4 2033 2041 October2008 - 4.
Real-time frequency and harmonic evaluation using artificial neural networks, andL. L Lai andW. L Chan andC. T Tse A. T. P So IEEE Trans. on Power Delivery ,14 1 52 59 Jan.1999 - 5.
Time-Varying Waveform Distortions in Power Systems, Wiley-IEEE Press,P Ribeiro 2009 - 6.
Frequency tracking in power networks in the presence of harmonics,M. M Begovi c a. n. d P. M Djuri andc a. n. d S Dunlap A. G Phadke IEEE Trans. on Power Delivery ,8 2 480 486 Apr.1993 - 7.
Estimating and interpreting the instantaneous frequency of a signal. I. Fundamentals,B Boashash Proceedings of the IEEE ,80 4 520 538 Apr1992 - 8.
Harmonic power flow determination using the fast Fourier transform,T. A George IEEE Trans. on Power Delivery ,2 2 530 535 Apr.1991 - 9.
Real-time voltage phasor measurements for static-state estimation, andJ. S Thorp andA. G Phadke K. J Karimi IEEE Trans. Power App. Syst. ,PAS-104 11 3099 3106 Nov.1985 - 10.
Computer Relaying for Power Systems New York: John Wiley and Sons,1988 - 11.
Power Quality aspects of Smart Grids, International Conference on Renewable Energies and Power Quality, Granada (Spain), 23th to 25th March,M. H. J Bollen J Zhong F Zavoda J Meyer andA Mceachern F. C. L Opez 2010 - 12.
Limits for voltage distortion in the frequency range 2-9 kHz,M. H. J Bollen P. F Ribeiro andE. O. A Larsson C. M Lundmark IEEE Transactions on Power Delivery ,23 3 1481 1487 July2008 - 13.
An Investigation of the Harmonic Emissions of Wind Turbines, andS. T Tentzerakis S. A Papathanassiou IEEE Trans. Energy Convers. ,22 1 150 158 March2007 - 14.
Harmonic analysis in a power system with wind generation, andS. A Papathanassiou M. P Papadopoulos IEEE Trans. Power Delivery ,21 4 pgs. 2006-2016, October 2006. Instantaneous phase tracking in power networks by demodulation,IEEE Trans. On Instrumentation and Measurement , vol. 41, no. 6,963 967 December1992 - 15.
ki, Instantaneous phase tracking in power networks by demodulation, andP. M Djuric andM. M Begovic M Doroslova IEEE Trans. on Instrumentation and Measurement ,41 6 963 967 Dec.1992 - 16.
and E. A. B. da Silva, A Controlled Filtering Method for Estimating Harmonics of Off-Nominal Frequencies, andC. A. G Marques andM. V Ribeiro andC. A Duque P. F Ribeiro IEEE Trans. On Smart Grids ,3 1 38 49 March2012 - 17.
An algorithm for the evaluation of finite trigonometric series,G Goertzel The American Mathematical Monthly ,65 1 34 35 1958