Open access peer-reviewed chapter

Contributing by Monitoring Energy Efficiency to the Development of Optimization Measures to Improve Energy Performance in an Industrial Platform

Written By

Laurentiu Constantin Lipan

Submitted: 12 July 2021 Reviewed: 28 November 2021 Published: 11 January 2022

DOI: 10.5772/intechopen.101801

From the Edited Volume

Alternative Energies and Efficiency Evaluation

Edited by Muhammad Wakil Shahzad, Muhammad Sultan, Laurent Dala, Ben Bin Xu and Yinzhu Jiang

Chapter metrics overview

336 Chapter Downloads

View Full Metrics

Abstract

Greenhouse gas emissions and climate change are currently major international problems. This makes it important to increase energy efficiency. The implementation of energy efficiency improvement measures has reduced energy demand for industrial platforms, so that energy plans designed before these measures are no longer appropriate for current tasks (extensions are not considered at this time). I intended to give a clear image and a better understanding of the factories’ power consumption (the industrial area in question is located near a city). A power plant-specific power system is quite disruptive, as can be seen from the monitored data at the power plant users and from the general power supply voltage bars (110 kV, 20 kV) as well as from the voltage bars of the adjacent users. Based on real-time measurements and monitoring devices, the following characteristic curves have been extracted for local energy systems. That is because data analysis is easy to be used for monitoring energy efficiency and elaborating optimization measures to improve power performance.

Keywords

  • greenhouse gas emissions
  • intelligent platforms
  • advanced metering infrastructure (AMI)
  • intelligent networks
  • U-THD
  • I-THD

1. Introduction

The experimental study of the energy action/behavior of an industrial user allows to highlight its energetic performance, practical ways to improve its energy use, as well as validating the theoretical hypotheses formulated in order to assess this user. Assessing the power quality supplied in the public system and observing the quality indicators for compliance with accepted standard limits plays an important role in order to establish the optimal functioning parameters for this industrial power user. In this paper, the results of the experimental study achieved at a large-scale/industrial power user are exposed, along with the problems that emerged from this research. Moreover, solutions for solving these kind of problems are indicated. The analysis of the power supply quality of the three-phase general power supply circuit of the analyzed user was performed on the 110 kV side in the measuring cells in the secondary measuring circuits of the T1 110/20 kV transformer, 16 MVA.

Advertisement

2. Analysis of the quality of the electrical power on the bars of 110 kV

“Analysis of the quality of the electrical power supply of the three-phase general power supply circuit of the user on 110kV” is based on “Study on the quality of power supply including load analysis, problems regarding voltage/current fluctuations, interruptions in the company’s power supply, flicker monitoring, asymmetries, harmonic levels on voltage and current, for the general supply on the 110kV side of the company in the Intelligent Electrical Connections Station, without personal workers, with Advanced Metering Infrastructure (AMI)”.

The electrical installations (Figure 1) of the analyzed industrial user consist of:

  • two 110/20 kV 16 MVA substations (one being in reserve) – Figure 2 and Table 1;

  • four 20/0.4 kV substations - PT1, PT2, PT3 and PT4;

  • electrical distribution boards (intelligent electrical networks platforms);

  • 0.4 kV power receivers (users).

Figure 1.

110 kV single-wire power supply diagrams of the analyzed company with transformers 1 and 2, 110/20 kV of 16 MVA [copyright © 2020 PLT – Adapted working scheme] .

Figure 2.

Real photo - transformer 1 (T1), 110/20 kV of 16 MVA.

TransformerSnΔP0ΔPscTensionFabrication year
UMTUMT
MVAkWkWkVV
TTUS-ONAN163830011020.52008
TTUS-ONAN163830011020.52008

Table 1.

Characteristics of the transformer in the transformer station.

The measuring point for the analyzed substation, in which the monitoring equipment was mounted, is represented by the entry point on the 110 kV (Table 1) side of the 110/20.5 kV, 16MVA transformer, or the exit point from the 110 kV electrical connection station of the conveyor (the common part with that of the distributor – the IT cells are actually located in the same premises). Table 2 presents some samples of measurements performed for the analyzed transformer in the electrical connections station.

Table 2.

Measurement sheet for the transformation station on the first day of the monitoring period 13/03/2021 at 18:00–22/03/2021 at 16:10.

Thus, an ION7600 Class A type analyzer was installed (Figure 3), approved and verified up to date (for monitoring the various electrical quantities that will be presented below), in order to make an energy analysis of the monitored electrical measures for the technological process in the general connections power station, at the supply point inside the company.

Figure 3.

Real photo – Measure cell for transformer 1 (T1), 110/20 kV of 16 MVA in Consumer’s Power Station [copyright © 2020 PLT – Working scheme & photo].

The analysis of the data registered in the period 26/06/2021 at 16:20–20/08/2021 at 19:00, for the power supply of the receivers within the company allows for the highlighting of the electrical characteristics of the power supply system.

Measurements performed on the HV bars (High Voltage) in the above mentioned period have been achieved in order to carry out the electric power study within the company. The measurements that were recorded are calculated as the average values of the electrical quantities, at an interval of 10 minutes, according to current quality standards IEC 61000–3-4 [1].

The voltage at the supply bars of the receivers shows variations (60.136…72.53) kV voltage per phase/(104.254 ÷ 126.17) kV voltage between phases, for TGD (Figure 4a and b), which must fit within the limits of 60 ± 10% / 110 ± 10% kV (54…66/100…120 kV). Rapid variations in voltage values caused by specific processes within the company (factory) lead to the recording of voltage fluctuations, accompanied by the flicker effect. The 3-phases are relatively symmetrically charged. It has been observed that the values of the supply voltage during the measurements did not exceed the normal (normed) limit values.

Figure 4.

Voltage curve at the supply bar for TGD: a - voltages between phases, b - voltages per phase.

The voltages at the supply bars have a shape close to a sinusoid, being characterized by a relatively low total THD distortion factor (Figure 5), which fits within the values allowed at the low voltage supply bars (THD admitted = 8%). The total voltage distortion factor - THD U (Figure 5) is relatively low (it fits between the values (1 ÷ 2.1%).

Figure 5.

Voltage distortion factor on supply phases a, b, c (THD U) - monitored values.

Figure 6 shows the variation of the unbalance factor during recording. It is observed that the values of the negative unbalance factor (ks = Vunb):

Figure 6.

Negative voltage unbalance factor at TGD supply bars (ks).

ks=UU+E1

where U is the negative sequence voltage (inverse) and U+ is the positive sequence voltage (direct), does not exceed the permissible values of the negative unbalance factor (<2%) at TGD (power supply point) in the monitored enclosure.

The analysis of the data in Figure 6 highlights an unbalance factor of about 5%, which indicates the existence of unbalanced and non-linear three-phase users connected in the low voltage network, unevenly, fact which causes different voltage drops on the three phases. It is important that the unbalance factor of the voltages between the phases has values within the accepted limits so that the three-phase motors connected in a triangle in the low voltage network are not affected by the unbalance of the supply voltages. Connecting star motors could lead to a reduction in their operating performance [2].

The variation of the measured values of the negative unbalance factor ks, determined as the ratio between the negative sequence component of the voltage curve U- and the positive sequence component of the voltage curve U+, is indicated in Figure 6 [3].

The analysis of the data in Figure 7 highlights the fact that, at the low voltage bars of the receiver supply system, the admitted levels of voltage fluctuations are exceeded in many cases, in the public network (Pst_admitted = 0.9, and Plt_admitted = 1.0) [3, 4, 5, 6]. The number of events that lead to values higher than those admitted in the public network is small and is due to specific processes. In addition, in the energy system of other users, the admitted values are different from those in the public network, established according to the effects of the process carried out. The data in Figure 7 indicate that higher voltage variations occur in phase c, accompanied by a higher level of flicker indicators. It is noted that the curves Pst and Plt in the general connections table (TGD) inside the studied company (factory), have almost the same shape (allure).

Figure 7.

Variation in the level of voltage fluctuations at the supply bars of the TGD.

Moreover, based on the measurements, it is observed that at the feed bars of the TGD, the flicker level (Pst, Plt) is within the normalized parameters (limit). The disturbances determined at the supply bar are due, first of all, to the variation, in wide limits, of the reactive power necessary for the operation of the furnace. In the case of AC voltage supply, the efficient operation of the oven requires the existence of a low power factor, which requires the adoption of measures to improve it.

The variability specific to the technological process may require adequate compensation of the reactive power. The wide variation of the reactive power absorbed from the mains supply causes rapid voltage variations (voltage fluctuations) at the supply bars (usually within the accepted limits of slow voltage variations, +10%, in mains networks high voltage) accompanied by the phenomenon of flicker in users connected in the same area of use. The complexity of the phenomenon, as well as its propagation in the power supply network, requires experimental determinations to be based on the analysis of the level of disturbances in users in the area and, if necessary, to evaluate measures to reduce the level of disturbances.

The technical study carried out comprises a wide area of use in which it has been identified and analyzed, in particular, the electromagnetic disturbance in the form of voltage fluctuation which causes flicker phenomenon. The determinations in the area followed a large number of parameters and quality indicators, but the detailed analysis focused on the short-term and long-term flicker indicators Pst, measured according to the recommendations of IEC 61000.

Also, the electrical quantities determined in the representative points of the scheme in the area were analyzed, namely at the high voltage supply bar of the analyzed user, at the high voltage supply bar of other users in the area and at the low voltage bar, at which are powered by the affected receptors.

The determined values enable the comparison with the admitted values recommended or imposed by the international CEI standards and the RET&RED performance standard (RET = Electrical transmission networks; RED = Electrical distribution networks).

In order to ensure the quality of electricity, limit values are indicated in the standards and norms in force, technical energy norms for limiting voltage fluctuations, including the flicker effect, in electricity transmission and distribution networks - NTE 012/14/00 and standards international IEC 61000–4-30 ver. III, IEC 61000–3-7: 2008 and IEC 61000–2-2. The national standards NTE 012/14/00, Ord_12_2016_RET and international performance standard IEC 61000–4-30 ver.3, IEC 61000–3-7: 2008 and IEC 61000–2-2 indicate, for the low voltage level, the limits of compatibility in Table 3. For the range of medium, high and very high voltages, the planning values of the flicker indicators on short-time (Pst) and long-time (Plt) are indicated in Table 4.

Flicker indicatorCompatibility level
Pst1.0
Plt0.8

Table 3.

Compatibility limits for flicker indicators in low voltage networks.

Flicker indicatorLevel of planning*
(Medium Tension) MT(High Tension) IT
Pst0.90.8
Plt0.80.6

Table 4.

Indicative values of the planning level for flicker indicators, in medium, high and very high voltage networks.

The values of the flicker indicators were established considering that the transfer factor to the low voltage network is unitary. In real cases, this factor may vary and must be determined for different operating conditions. In this way, the values at the MT and IT levels may be appropriately higher. The values mentioned are for guidance only.


For the low voltage level, in any time interval of one week, the long-term flicker indicator must meet the Plt < 1 condition for 95% of the time. The same condition is imposed for the average voltage level [3, 4, 5, 6].

Due to the fact that low voltage users are affected by voltage fluctuations (flicker phenomenon) during the operation of the electric arc furnace, experimental determinations have been proposed, in particular, to verify the compliance of the level of disturbances within the accepted limits by international standards. Also, the curves regarding the voltage variation in significant points of the scheme and the curves for the variation of the reactive power on the user’s power supply line will be analyzed.

As electromagnetic compatibility analyzes are taken into account, in particular values with a probability of 95%, these values will be highlighted in the analysis, which must be compared with the admitted values. Also, as comparison, the values with a probability of 50% (average values) will be highlighted.

The electric currents on the three phases monitoring have quite close values indicating, however, an asymmetric phase charge. The variations of these currents are presented in Figure 8.

Figure 8.

Electric current curve on the feed bar for TGD. a. Arms [a] – Monitored. b. Arms [a] - instantaneous values.

The total distortion factor of electric current - THD I (Figure 9), according to the shape of the graph curves, indicates the sinusoidal shape of the current in the supply circuit. At a first comparison with the data on the level of distortion of the voltage on the bars, there is no direct influence, especially in the case of phase a, in which the harmonic distortion of the electric current is superior to the other two phases. The analysis of Figure 8a and b also shows a weak imbalance between the loads of the three phases.

Figure 9.

Electric current distortion factor on supply phases a, b, c (THD-I or Athd) - monitored values.

It should be noted that the jumps in the variation curves of the harmonic spectrum are due to sudden variations in electric current at the start of various electrical equipment - motors (in-rush current). These values are not specific for the analysis of harmonic distortion of electric current.

The variation of the unbalance factor of electric current, during the recording time, is indicated in Figure 10. The negative unbalance factor was determined based on the relation:

Figure 10.

Variation of the negative current unbalance factor of TGD (ks = Aunb).

ks=II+E2

where I is the negative (reverse) sequence component of the electric currents, and I+ is the positive (direct) sequence component.

The data in Figure 10 shows that, during the recording, the unbalance factor of the electric current did not exceed the normal values in operation, these being determined especially by the voltage unbalance at the supply bars.

Special attention was paid to monitoring the values of electric currents in the supply circuits to determine both their loads and the level of losses in the user’s electrical circuits.

Figures 11 and 12 show the variation P (active powers) and, respectively, Q (reactive powers) on the IT/MT (at 110 kV) bars, and Figure 13 shows the variation of the apparent powers transited on the circuit (S), respectively, in Figure 14 the variation of the three-phase powers comparative. The phase shift between the voltages and the electric currents monitored at the supply bar of the analyzed electrical equipment, in instantaneous values, is presented in Figure 15.

Figure 11.

P [kW] variation on the IT bars at 110 kV.

Figure 12.

Q [kVAr] variation on the IT bars at 110 kV.

Figure 13.

Apparent single-phase powers transited through at 110 kV - S [kVA].

Figure 14.

Three-phase powers transited at 110 kV. SumP [kW], SumQ [kVAr], SumS [kVA].

Figure 15.

The phase shift between voltages and electric currents at the supply bar at 110 kV.

The curves in Figure 12 indicate that the user absorbs capacitive reactive power over a significant period of time. In comparison with the data in Figure 14, it is highlighted that the values of the capacitive power factor are within the limits accepted by the regulations in force. In order to ensure the control of the reactive power in the capacitive zone, and the limitation of some undesired increases of voltage in this interval, concrete solutions for the limitation of the capacitive regime were analyzed.

The PF power factor was determined based on the recorded energy values over a specified time interval:

PF=WtrifazatPWtrifazatSE3

The PF value, although widely used in practical applications, provides correct information on the energy behavior of the consumer only in the case of a constant consumption during the time interval in which the power factor is evaluated.

The variation of the power factor during the recording, and in the time intervals in which the equipment was in operation, is indicated in Figure 16 for each phase. As it can be seen from the graph of the variation of the power factor (Figure 16), it is highlighted the fact that an important circulation of the reactive power appears in the supply circuit. The recorded values of the harmonic spectrum are affected by the specific operating mode, with frequent starts and stops of motors, as well as other electrical equipment (lighting, etc.). The real values of the harmonic spectrum can only be taken into account for stationary time intervals.

Figure 16.

PF variation (power factor) at 110 kV.

Figure 17 shows the minimum, average and maximum loads of the transformer during the monitoring period. The average load of the transformer station is about 13%, and the maximum load is 18%. Due to the low level of consumption in most operating cases, the transformer station operates poorly charged, which is an important source of energy loss. There are also times when the load is 6%.

Figure 17.

Transformation station loading (load T1).

Obs. In the power balance made for the transformer station of consumer, it is found that the transformer load does not exceed 18% of the nominal value (during 13/03/2021 at 18:00–22/03/2021 at 16:10).

Figure 18 shows the values of the voltage harmonics on the three phases (a, b and c) at 110 kV. Figure 19 shows the values of the current harmonics on the three phases (a, b and c) at 110 kV (in Cell Measure with Ion7600 Class A).

Figure 18.

Voltage harmonics level on phases a, b and c at the supply bars - monitored values at 110 kV. a. Harmonic level [%] phase 1 (voltages). b. Harmonic level [%] phase 2 (voltages). c. Harmonic level [%] phase 3 (voltages).

Figure 19.

The level of electric harmonics on phases a, b and c at the supply bars - monitored values at 110 kV. a. Harmonic electric currents phase1 [%]. b. Harmonic electric currents phase 2 [%]. c. Harmonic electric currents phase3 [%].

The main observations that emerge from the analysis of the electrical measurements performed are:

  • there is an imbalance of the charge of the three phases of the analyzed electrical circuit;

  • the power level factor varies slightly, from negative calories to positive values;

  • the flicker level varies strongly, but is maintained between optimal values;

  • the level of electric harmonics is relatively high (note that electric harmonics 5 and 7 have very high values).

Under these conditions, the optimization of the power balance aims at the balanced charging of the three phases, the improvement of the power factor compensation, the improvement of the flicker level and the operation with an improved harmonic regime (harmonics of electric current).

There is a good classification of the voltage level on phases and between phases in the normed parameters (framing in the normed limits).

Advertisement

3. Events recorded during the monitored period

This chapter presents a series of events recorded during the monitoring period (Dips&Swells) [5, 6]. These events led to production interruptions that caused significant damage to the user through recalibration, cleaning, disposal of inferior products of poor quality, the realization of additional waste and implicitly additional specific costs.

  • Events noted in the first half of the 110 kV monitoring period in the Electrical Station at the consumer – Figure 20.

  • Events noted in the last half of the 110 kV monitoring period in the Electrical Station at the consumer – Figure 21.

Figure 20.

Events noted in the first half of the 110 kV monitoring period in Electrical Station.

Figure 21.

Events noted in the last half of the 110 kV monitoring period in Electrical Station.

Advertisement

4. Technical analysis

According to the technical activity report, by downloading the monitored data by other industrial devices (such as SEPAMs), leads to the following technical statements assumed by the user [7]: “Event parity: approx. 5% of the total monitored events belong to the USER, and in approx. 95% of cases of origin of the Zonal Electricity Distributor and assumed by the Electricity Transporter.

That is, for month 1 there were 31 memorized events due to Zonal Electricity Distributor, at 2 ... 3 events of own influence - percentage, and for the 2nd month, there were 28 memorized events due to Zonal Electricity Distributor, at 2...3 events of own influence [7].

Obs. A series of additional information was analyzed that is not presented in detail in this chapter, but which competes or influences the proper functioning of the analyzed user, such as:

  1. Cables, switches (with related power bars)

  2. Specific operation of electrical equipment

  3. Field findings

  4. Protection information - provided by company representatives

  5. Information specific to electrical networks

  6. overall water demand, energy consumption and emission of conventional desalination processes - information such as size, emission [8] etc.

  7. etc.

Thus, for the various events and power quality, the following recommendations were taken into account, presented in the Table 5:

No.Proposed operationsEquipmentImplementation ModObs.
1Internal - mandatoryPTs and transformers+usersAfter performing a STUDY REGARDING THE DISTRIBUTION OF USERS BY STANDARD, PRIORITY CATEGORIES, CRITICISM IN SOCIETY (distribution by PTs and transformers)
2CheckingCablesWith mobile technical cable testing laboratory
BreakersWith mobile technical testing laboratory - thorough verification inside
Contact resistors between IT&MT bars and related cablesInternal - with the company’s electricians
Thorough grounding checkCheck the sockets by removing the connection plates, cleaning, thoroughly checking for improvement and if necessary.
TransformersWith mobile technical testing laboratory - thorough verification of sensors, with cleaning of dust terminals, insulating cleaning, moisture, oxidation or oil.
3Purchase of equipmentCompensation of capacitive/inductive operating modesWith specialized equipment made by established manufacturers
Proposal of a Rotary Compensator
Proposal of a PSS (Power System Stabilizer)
Proposal of an SVC (Static Var Compensator)
Proposal for a STATCOM (advanced FACTS device such as Back-to-back)
4Extensive inspections of the distributor’s installation - Zonal Electricity DistributorChecks for switching times and tripping and tripping times - various switching and protection equipmentWith specialists or with the knowledge of the Zonal Electricity Distributorexternal
Protection settingsWith specialists or with the knowledge of the Zonal Electricity Distributorexternal
Checking the operation of various switching equipment (switches, their automation etc.)With specialists or with the knowledge of the Zonal Electricity Distributorexternal
Study and implementation of the increase of the short circuit power of the ZONAL ELECTRICITY DISTRIBUTOR power station from which the enterprise is suppliedWith specialists or with the knowledge of the Zonal Electricity Distributorexternal
Checks of intervention modes in the 110 kV mains network of ZONAL ELECTRICITY DISTRIBUTOR (on the part of Medium Voltage and High Voltage) to the large users in the vicinity of Consumer who are connected to the same 110 kV network; verification of intervention times, interruptions, switching, respectively trigger times, triggering - various switching and protection equipment, plus other complaints that existed in the area (on IT and MT) during this monitoring period (but also before).With specialists or with the knowledge of the Zonal Electricity Distributorexternal

Table 5.

Legend: Red = with maximum priority; Yellow = priority.

The principle of operation/assembly/effects/etc. is similar to the one previously presented on specialized technical literature in the field.

The difference is given by:

  1. The materials from which the insulation of various equipment will be made (cables, windings, etc.), which are much more expensive and specialized (unusual);

  2. The electrical equipment/devices which is more expensive, being connected at 110 kV, compared to those connected at 20 kV, (also because of other reasons, related not only to insulation, see electromagnetic fields, etc.).

  3. In the case of connection of these SVC type devices to the 20 kV bar, it is known that the reduction of the flicker level by a maximum of 2 times, is corroborated with an additional reduction by a few percent of the flicker level, by passing through the transformer of 110/20 kV that supplies the electric arc furnace; in case of mounting these SVC devices on the 110 kV side, it is to be taken into account only the design data of the SVC system (this additional attenuation is almost null at 110 kV).

  4. However, in this case, compared to the compensation of the flicker level on the 20 kV side, we can also consider a slightly lower level of short-term and long-term flicker indicators on the 110 kV bar, compared to their level on the 20 kV, which may or may not influence the final price (depending on the manufacturer/equipment used).

  5. Although the solution using SVC ensures the limitation of the flicker level to the users in the area, in the current configuration of the Electric Station at Zonal Electricity Distributor and Electric Station at Electricity Transporter with Electric Station at Consumer, the open coupling at 110 kV bus bar does not provide the necessary conditions for using a backup transformer for the user (a transformer will be dedicated to the analyzed user).

Thus, using FACTS devices (SVC or STATCOM) implies [9, 10, 11]:

  • Flicker

It is a random variation caused by rapid fluctuations of the reactive power in the common power supply point of the steel enterprise. The human eye perceives voltage fluctuation as the change in brightness of light sources.

  • Voltage stabilization

The operation of the electric arc can lead to a strong unbalance, especially in the initial stage of starting the melting process. The three-phase asynchronous motors are affected by voltage unbalance. The unbalance of the voltage causes the reduction of the installation’s yield, overheating, loud noises, vibrations and variations of motors’ speed. That is why the use of SVC in control mode on each phase of the steel company’s power supply system ensures the voltage symmetry and stabilization.

  • Reactive power compensation (Q)

The transport of reactive power leads to significant voltage drops and the increase of electric currents in the supply network, decreasing the transport capacity of the active power (P). Public network operators maximize the transport capacity, encouraging users to use local reactive power compensation. SVC maintains the required reactive power (Q) within the limits imposed by the operator, thus avoiding penalties, as well as increasing the efficiency of user activities.

  • Harmonic currents reduction

Users with non-linear characteristics such as electric arc furnaces generate harmonic electric currents. Harmonic currents charge the network and lead to voltage distortion. Distorted voltages can cause IT equipment (computers, etc.), control equipment, and other sensitive equipment to malfunction. SVC filter circuits are designed to absorb harmonic load-generated currents such as thyristor-controlled coils (TCRs). THD (Distortion Factor) and the individual level of harmonic currents are limited below the specified (normed) values.

  • Energy saving

Reactive power compensation (Q) and increased electricity quality lead to increased active power transmission capacity (P) and reduced active energy losses. Thus, overloading of the power supply network can be avoided. This fact brings benefits for both the company and the environment by a more efficient use of electricity, and a reduction of the need for electricity. It is known that, for every 1 kWh saved, produced in a thermal power plant, the amount of pollutants released into the atmosphere is smaller with about 1 kg of CO2.

  • Productivity increase

The SVC system can ensure a practically constant voltage level at the company’s power supply bars. This way, it decreases the duration of the melting process and increases productivity. A SVC system limits production interruptions and restarts that require long durations. The electric arc furnaces stabilized by SVC have an important effect on reducing electrode consumption, heat loss and the life of the furnace liner. By increasing the quality of electricity, the demand for equipment is reduced, the lifespan is increased and the costs of maintenance and replacement of some components are reduced.

Advertisement

5. Conclusions

Conclusions resulting from the analysis of the monitored data on the 110 kV – T1 side (power station) as well as the main observations that emerge from the analysis of the electrical measurements performed are:

  • there is an unbalance of charge in the three phases of the analyzed electrical circuit;

  • the power factor level shows variations outside the range 0.90 ... 1.00; these values are not considered optimal (correctly compensated); there are penalties to the Electricity Invoice for not falling between the mentioned values, according to ANRE (National Energy Regulatory Authority) order only if those from PCC (Common Connection Point – CCP) to the electric meter;

  • the flicker level varies strongly, but is maintained between optimal values in 90% from 90% of the monitoring time (Obs. The values in the CCP matter the most);

  • the level of electric harmonics is relatively high; it is noticed that the harmonics of electric current 5, 7 have high values, with significant variations.

Under these conditions, the aim is: balanced charging of the three phases, improved power factor compensation, improved flicker level and operation with an improved harmonic regime (electric harmonics).

There is a good classification of the voltage level on phases and between phases, in the normed parameters (framing in the normed limits).

The two proposed performance solutions (in this case):

A. The connection of a STATCOM to the 110 kV bus bars of the user (Figure 22) leads to a factor of reduction of the flicker level between 3 and 6 (they multiply). The control block BC receives the information regarding the voltage level at the 110 kV bus bars and determines its maintenance by injection of real-time capacitive reactive power from capacitor C via the appropriate controlled inverter.

Figure 22.

Scheme of a STATCOM (for analyze) [3, 4, 5, 6, 7, 12]. a. Scheme of a STATCOM for voltage control at 110 kV bus bars. b. Functioning scheme/diagram of a STATCOM equipment.

Connecting SVC or STATCOM to the user’s 110 kV bus bars, along with using a dedicated 400/110 kV transformer, enables a reduction of practically 1.5…2 times (in case of using SVC), and 3…6 times (in the case of using STATCOM), of the disturbance level at the 110 kV bars of the Electrical Station [3, 4, 5, 6, 7, 12]. In this way, the problems related to the disturbance of the users in the area are completely solved as well [13].

In CIGRE study [12, 14] regarding a STATCOM type FACTS device to improve the flicker level in the case of an ELECTRIC ARC OVEN, it is said that the reduction of the flicker level in a single installation was reduced from an initial factor of Pst95% = 3,75 without STATCOM, to Pst95% = 0.76 with STATCOM in operation, for a short-term probability of 95% [3, 4, 5, 6, 7, 12]. This fact indicates that the flicker level has improved about five times with the introduction of the compensator.

B. “Back-to-Back System” - By using this type of system/equipment, the level of flicker indicators on the bar on which it is mounted is eliminated, in the sense that it can be fully controlled [3, 4, 5, 6, 7, 12]. This is due to the well-known fact that any type of disturbance is eliminated from the arc furnace to the Power Station by passing through a DC voltage level (Figure 23) [15, 16]. Obs. Back-to-back equipment has high-power thyristor electronic devices, which can themselves produce/generate system disturbances, if they are not correctly chosen and calculated with great accuracy.

Figure 23.

The functioning diagram of a back-to-back FACTS system [15, 16].

References

  1. 1. IEC. Electromagnetic Compatibility (EMC) - Part 3–7: Limits-Assessment of Emission Limits for the Connection of Fluctuating Installations to MV, HV and EHV Power Systems. IEC 61000–3-7, second edition of CAN/CSA-C61000-3-7/2008, 2008
  2. 2. IEC. Electromagnetic compatibility (EMC) - Part 2–2: Environment-Compatibility levels for low-frequency conducted disturbances and signalling in public low-voltage power supply systems. IEC 61000–2-2, IEC 61000-2-2:2002+AMD1:2017+AMD2:2018 CSV, Consolidated version, 2018
  3. 3. IEC. Electromagnetic compatibility (EMC), Part 4–30: Testing and measurement techniques- Power quality measurement methods. IEC 61000–4-30 ver. III, IEC 61000-4-30:2015/AMD1:2021, Amendment 1, TC 77/SC 77A Additional information, ISBN 978-2-8322-2324-6, 2021
  4. 4. SR EN 50160, Voltage characteristics of electricity supplied by public distribution systems. Standard EN 50160:1999, rev.2009; Romania, 2009
  5. 5. IEC. Electromagnetic compatibility (EMC) - Part 3–13: Limits-Assessment of emission for the connection of unbalanced installationa to MV, HV and EHV power systems. 61000-3-13, (Adopted IEC/TR 61000-3-13:2008, first edition, 2008-02), CAN/CSA-C61000-3-13-09 (R2017), 2017
  6. 6. IEC. Electromagnetic compatibility (EMC) - Part 3–6: Limits-Assessment of emission limits for the connection of distorting installations to MV, HV and EHV power systems. Standard IEC/TR 13, 61000–3-6, IEC TR 61000-3-6:2008. EU: IEC - International Electrotechnical Commission; 2008
  7. 7. Golovanov N, Postolache P, Iordănescu I, Lipan L, Porumb R. Instalaţii Electroenergetice si elemente de audit industrial. Bucuresti: Editura N’Ergo; 2008
  8. 8. Shahzad MW, Burhan M, Ang L, Ng KC. Energy-water-environment nexus underpinning future desalination sustainability. Desalination. 2017;413:52-64. DOI: 10.1016/j.desal.2017.03.009
  9. 9. Singh P, Senroy N. Steady-State models of STATCOM and UPFC using flexible holomorphic embedding. Electric Power Systems Research. 2021;199:107390, 2021. DOI: 10.1016/j.epsr.2021.107390
  10. 10. Ufa R, Gusev A, Zaki AA, Diab AS, Ruban N, Andreev M, et al. Analysis of application of back-to-back HVDC system in Tomsk electric power system. Research paper. Energy Reports. 2020;6:438-444. DOI: 10.1016/j.egyr.2020.01.017
  11. 11. Zellagui M, Lasmari A, Settoul S, El-Sehiemy RA, El-Bayeh CZ, Chenni R. Simultaneous allocation of photovoltaic DG and DSTATCOM for techno-economic and environmental benefits in electrical distribution systems at different loading conditions using novel hybrid optimization algorithms. International Transactions on Electrical Energy Systems. 22 August 2021;31(8):e12992. DOI: 10.1002/2050-7038.12992
  12. 12. CIGRE study. “Static synchronous compensator (statcom) for arc furnace and flicker compensation. Prepared by Working Group B4.19/Edited by I. Paris, EU: Arslan Erinmez; 2003
  13. 13. Čerňan M, Müller Z, Tlustý J, Valouch V. An improved SVC control for electric arc furnace voltage flicker mitigation. International Journal of Electrical Power & Energy Systems. 2021;129:106831. DOI: 10.1016/j.ijepes.2021.106831
  14. 14. Geetha Devi CE, Devanathan R. Computer simulation of linearized Statcom model. Materials Today; Proceedings. 2020;33(7):4243-4249. DOI: 10.1016/j.matpr.2020.07.349
  15. 15. Fathy A, Yousri D, Abdelaziz AY, Ramadan HS. Robust approach based chimp optimization algorithm for minimizing power loss of electrical distribution networks via allocating distributed generators. Sustainable Energy Technologies and Assessments. 2021;47:101359. DOI: 10.1016/j.seta.2021.101359
  16. 16. Sangeeta Sarali D, Selvi Agnes Idhaya V, Pandiyan Karuppasamy. Modeling of the three-phase converter using a predictive controller based on the dynamic voltage restorer model for improving power quality. Materials Today: Proceedings. Elsevier BV; 2021. DOI: 10.1016/j.matpr.2021.01.744

Written By

Laurentiu Constantin Lipan

Submitted: 12 July 2021 Reviewed: 28 November 2021 Published: 11 January 2022