Open access peer-reviewed chapter

Advanced Control Strategies with Simulations for a Typical District Heating System to Approaching Energy Efficiency Buildings

Written By

Li Lian Zhong

Reviewed: 07 November 2017 Published: 20 December 2017

DOI: 10.5772/intechopen.72290

From the Edited Volume

Sustainable Buildings - Interaction Between a Holistic Conceptual Act and Materials Properties

Edited by Amjad Almusaed and Asaad Almssad

Chapter metrics overview

773 Chapter Downloads

View Full Metrics

Abstract

District heating systems (DHSs) are very common and important in cold areas in the world not only because of the huge energy consumption including kinds of fuel, electricity and water but also due to thermal comfort of all customers. To increase the energy efficiency and improve heating quality within the operational period, suitable and optimal control strategy should be applied for the DHSs. Thus, in this chapter, a typical DHS is designed. Based on the DHS information, a dynamic model is developed by using thermodynamic principles and corrected according to the measured operational data from real systems. The DHS properties are simulated by utilizing the open-loop tests (OLTs) of the developed actual dynamic model. System performance of operation, energy consumption and zone air temperature are addressed for several control strategies. Based on the energy consumed and indoor air temperature response, average water temperature set point corrected by equivalent outside air temperature (Case 4) and indoor air temperature control directly (Case 5) are considered, which are the best cases of optimal operation in the DHS.

Keywords

  • district heating system
  • dynamic modeling
  • control strategy
  • simulation
  • estimation
  • energy efficiency

1. General information of typical district heating systems

1.1. Introduction of DHSs

Indoor environment of living and work in cold areas in the world must satisfy certain conditions in cold period. For instance, in some Nordic countries, if people feel cold with in zone air temperature, they could run the heating system to maintain the air temperature warmer due to the DHS operated yearly. Another example is that, in China, following the heating guide, if average outside air temperature lowers than 5°C within 3 days continuously, heating systems should be run from that time (adjusted a few days actually). The space heating systems have been developed from decentralized heating to district heating, which are sometime called as central heating systems, usually with huge served heating floor area.

When the DHSs are operated from the beginning to the end, the systems have been expectedly running in an optimal way to improve their performance, increase their energy efficiency, reduce the pollutant emissions and maintain accepted indoor air temperature as well. Consequently, energy efficiency of buildings has been approached. DHS performance is related to operational data collection, status estimation, alarm, data analysis, control settings and control strategies. Energy efficiency should consider the heat transfer from the heat source to the end users, which could be separated by efficiency of heat source, pipe network and substation, respectively. Although zone air temperature is normally kept in constant, but the set points could be reasonably changed such as to increase the human body adaptability with a little bit zone air temperature fluctuation.

From energy-saving point of view, how to reduce energy consumption including fuel, electricity and water is always a hot topic, a question and a great challenge. These reasons behind are that currently DHSs integrated not only have been become larger and larger but also require strong and various technologies to assist the activity. For example, Beijing Heating Group has the biggest DHSs in the world, around 2.55 Mm2 in 2016–2017 heating period with powerful SCADA system to support the operation.

One way to increase system energy and served building efficiency is to investigate the system properties using collected operational data and apply the results to the real system operation. However, this is time-consuming and cannot test all kinds of situations, which are expected because of potential risks. Therefore, what the efficient way could be utilized has been considered by the researchers and HVAC engineers in this field. Currently, this methodology is entitled as dynamic simulation based on mathematical modeling, which basically could be used to obtain system characteristics, study control strategies and predict energy consumption and dynamic responses of system operation.

1.2. The advantages and disadvantages of dynamic modeling

System modeling has two types of methods: one is steady-state modeling, and the other is dynamic modeling [1, 2]. The thermal capacities of DHSs are not considered in steady-state modeling process, but those have been calculated in dynamic modeling. This is because thermal capacities have profound influence in actual system dynamic responses and process control. To investigate the system responses closely to the real world, the system modeling and simulations in this chapter always refer to the dynamics. The properties of modeling can be described as follows.

1.2.1. The advantages of modeling

  1. An ideal model of an overall DHS can be developed by the first law of thermodynamics and corrected by operational data, which has been changed to the actual model.

  2. Quick dynamic responses and characteristics could be gathered in the simulation with acceptable accuracy by simulating the actual model.

  3. The results could be obtained in simulation environment without any risks.

  4. The boundary conditions could be changed very efficiently by inputting different parameters and could be utilized while they are modified.

  5. Both greater efficiency and time-saving of R&D could be achieved by programming with friendly user interface.

  6. Almost all consideration and simulation could be fulfilled by using dynamic modeling to attain optimal results.

  7. The system responses such as the performance of system, energy efficiency and zone air temperature could be observed and analyzed.

  8. By using simulation method, the optimal parameters of system operation could be found and applied for real system to improve energy efficiency of buildings as well as overall DHSs.

1.2.2. The disadvantages of modeling

  1. It is relatively difficult to develop an overall dynamic model of a DHS with correction.

  2. Programming based on mathematics, control theory, optimization method and computer skills is required for various dynamic simulations.

  3. Simulations for fast dynamic system, water mass flow rate and pressure, for instance, could consume more time to get results.

  4. Very powerful computers could be required for more accurate simulation with bigger and more complex DHS system.

1.3. Methods of dynamic modeling and simulation

1.3.1. Dynamic modeling method

Any closed system must obey certain laws including energy, momentum and mass conservation [3, 4, 5]. According to the properties of DHSs, the dynamic responses mainly depend on slow response system (temperature dynamics) rather than fast response system (mass and pressure dynamics). To this end, the dynamics of fast response systems could be replaced by using steady-state method without affecting the major dynamic properties of DHSs. Energy and mass conversion are applied for the development of an overall DHS that is addressed in the following section below.

1.3.2. Dynamic simulation method

Recently, simulation methods of DHSs have played more important rule than ever followed by the progress of science and technology. The computer, algorithm, programming and software become very powerful as simulation tools. Many businesses or academic software such as BLAST, EnergyPlus, DeST, DOE-2, RNSYS, PKPM-CHEC, eQuest, VisualDOE, ESP-r, Ecotect, IES, etc. [6] can be easily obtained from various channels. However, if considering inside of the software, most of them were developed based on steady-state approach. In research area, dynamics is normally applied to equipment or partial system simulations. Few researchers are working in the dynamic simulation field for developing entire DHS modeling and try to utilize the models for system-level improvement [7, 8, 9, 10, 11, 12].

1.4. Major focus on this chapter

In this chapter, a typical hot water DHS is considered and designed. Then, a dynamic mathematical model is developed based on the physical model and thermal dynamic principles. An actual model is developed by correcting an ideal model of the DHS. Following that, the characteristics of the DHS could be collected by using open-loop test (OLT) method. Finally, five types of control strategies are simulated and compared with the analysis of dynamic response, energy consumption and zone air temperature responses.

Advertisement

2. Design of a typical DHS

2.1. A typical DHS diagram

Due to the heated floor area of DHSs which become very larger, indirect DHSs are commonly formed in practice for major district heating field with substations. A typical DHS diagram is shown in Figure 1, and the meaning of symbols in it is given in the nomenclature.

Figure 1.

A typical DHS diagram with control principle.

The hot water with high-level temperature (usually less than 150°C in design condition) is supplied from the boiler (sometimes from CHPs) in the heat source and transfers heat to the substations; then the heat is released to the secondary side in the substation, and the temperature of the return water in the primary side is decreased. The radiators at the end-users receive transferred heat from the substations and then are emitted to the indoor air for space heating. The supplied heat should be continuously gained to maintain suitable zone air temperature due to the heat balance between the indoor and the outdoor environments. The three-way control valves installed in the primary side of the substations are utilized to regulate the water mass flow into the heat exchangers and to balance the heat supplied to the secondary systems. Note that the makeup water systems in the secondary side are same as it is in the primary side (drawing ignored).

2.2. Subsystem of the DHS

From Figure 1, it is realized that the structure of the indirect DHS includes the following subsystem such as heat source, pipe network in the primary side, substation, pipe network in the secondary side, heat emit system from terminal, indoor air and outside environment.

Advertisement

3. Mathematical model development

3.1. Physical model

To obtain the mathematical model of the DHS, it is required to design the heating system illustrated in Figure 1. The design parameters are given in Table 1. The DHS is designed based on these parameters, which could be utilized to develop mathematical model and simulations.

No.NameUnitDataRemark
1Outside air temperature°C−20
2Supply water temperature in the primary system°C120
3Return water temperature in the primary system°C60
4Heat capacity in the heat sourceMW7
5Natural gas-fired boiler%92
6Water volume in the boiler bodyT3
7Supply water temperature in the secondary system°C75Radiator
8Return water temperature in the secondary system°C50Radiator
9Supply water temperature in the secondary system°C50Floor heating
10Return water temperature in the secondary system°C40Floor heating
11Indoor air temperature°C20Radiator terminal
12Indoor air temperature°C18Floor heating terminal
13Heated floor area in Substation #1m250,000
14Heating load index in Substation #1W/m255
15Water volume in the radiator of Substation #1T75
16Factor of the heat transfer coefficient test in Substation #10.35
17Heated floor area in Substation #2m235,000
18Heating load index in Substation #2W/m242
19Water volume in the radiator of Substation #2T38
20Factor of the heat transfer coefficient test in Substation #20.28
21Heated floor area in Substation #3m240,000
22Heating load index in Substation #3W/m235
23Water volume in the radiator of Substation #3T38
24Factor related to heat transfer coefficient simulation in Substation #30.04
25Heating load in Substation #1MW2.75
26Heating load in Substation #2MW1.47
27Heating load in Substation #3MW1.40

Table 1.

Design parameters of the DHS.

3.2. Assumption of model development

The designed DHSs are a very complex system from mathematic modeling point of view because of the multiple connections among the subsystems. To simplify the dynamic model development process, several assumptions are listed below without affecting major properties of the DHSs [13]:

  1. Some parameters such as comprehensive heat transfer coefficient of buildings and heated floor area of buildings are integrated.

  2. The water leakage from the pipe network is assumed taking place in the primary pipe network of the substation and in the end-user of the secondary side, and it is divided into half in supply and half in return pipes, respectively.

  3. Transportation delay of pipe network is not considered in the system dynamics.

  4. Fast response system is expressed as steady-state condition.

  5. The solar radiation is considered from south side windows in the outside wall only.

  6. The water mass flow rate remains constant in the secondary system in each substation.

3.3. Dynamic modeling

By applying for the first law of thermodynamics and mass conservation principle, each subsystem dynamic model is shown and described briefly below:

3.3.1. Boiler model

CbdTs1dt=ufGfdHVηbcwu11G11d+u12G12d+u13G13dTs1Tr1mE1

In Eq. (1), the net heat stored in the water of the boiler body is computed with the difference between the heat from the gas combustion and the heat transferred to the circulation water in the primary system. Note that the boiler efficiency is calculated according to measured operational data.

3.3.2. Substation model

Cex11dTr11dt=cwu11G11d0.5Gmk11Ts1B1Tr11fex1Uex1LMTD1E2
Cex12dTr12dt=cwu12G11d0.5Gmk12Ts1c1Tr12fex2Uex2LMTD2E3
Cex13dTr13dt=cwu13G13d0.5Gmk13Ts1DTr13fex3Uex3LMTD3E4

The return water temperatures from each substation in the primary system are given in Eqs. (2)(4). The net heat stored in the heat exchanger (primary side) is computed between the heat from the pipe network to the substation and the heat transferred in the substation:

Cex21dTs21dt=fex1Uex1LMTD1cwu21G21dTs21Tr21mE5
Cex22dTs22dt=fex2Uex2LMTD2cwu22G22dTs22Tr22mE6
Cex23dTs23dt=fex3Uex3LMTD3cwu23G23dTs23Tr23mE7

The supply water temperature from the substation in the secondary system is presented in Eqs. (5)(7). The net heat stored in the heat exchanger in the secondary side is related to the heat transferred in the substation and the heat taken from the substation to the secondary system. Note that the logarithmic mean temperature difference (LMTD) is calculated in Eq. (8). Note that it refers to each substation from #1 to 3. Letter i denotes to 1–3, which is the number of substation:

LMTDi=Ts1inTs2ziTr1iTr2imlnTs1inTs2ziTr1iTr2im1E8

3.3.3. Radiator model

Cht1dTr21dt=cwu21G21d0.5Gmk21Ts21zTr21fht1Uht10.5Ts21z+Tr21Tz11+k1E9
Cht2dTr22dt=cwu22G22d0.5Gmk22Ts22zTr22fht2Uht20.5Ts22z+Tr22Tz21+k2E10
CrfdTr23dt=cwu23G23d0.5Gmk23Ts23zTr23frfUrf0.5Ts23z+Tr23Tz31+k3E11

The return water temperature from the end-user (radiator and radiant floor heating) is addressed in Eqs. (9)(11). The net heat stored in the terminal equals to the heat difference between the heat gathered from the circulation water and emitted to the indoor air.

3.3.4. Indoor air model

Cz1dTz1dt=cwu21G21d0.5Gmk21Ts21zTr21+qsolsFs1+qintF1Uen1Tz1ToE12
Cz2dTz2dt=cwu22G22d0.5Gmk22Ts22zTr22+qsolsFs2+qintF2Uen2Tz2ToE13
Cz3+CcdTz3dt=cwu23G23d0.5Gmk23Ts23zTr23+qsolsFs3+qintF3Uen3Tz3ToE14

Zone air temperature dynamic responses can be represented in Eqs. (12)(14). The net heat stored is related to the heat obtained from the circulation water in the secondary system, the solar radiation from south side windows, the internal heat gains and the heat transferred to the outside environment. Note that the thermal capacity in the terminal of floor heating is considered by accumulating the influence of the concrete structure.

3.3.5. Pipe segment in the primary and secondary systems

CsegjdTsegoutjdt=cwGseginjTseginjcwGsegoutjTsegoutjQmksegjQhlsegjE15

The schematic diagram of a pipe segment is shown in Figure 2. The makeup water and the heat loss from the pipe insulation are considered to gather the water temperature left from the pipe segment. The supply water temperature from the pipe segment is related to the heat loss from the pipe segment, while the return water temperature has been considered in the heat losses from pipe insulation and makeup water. In Eq. (15), the net heat stored in the pipe segment equals to the heat received from the entrance minus the heat outlet from the exit and the heat losses from both makeup water leakage and pipe segment. Note that supply pipe segments do not consider the water leakage by the assumption. Letter j represents each pipe segment.

Figure 2.

Schematic diagram of a pipe segment.

In summary, 29 dynamic equations are used to address the overall DHS mathematical model. The developed model is utilized to obtain system properties, simulate various dynamic responses of control strategies and compare with system energy consumption.

Advertisement

4. Actual dynamic model corrected by using open-loop test

4.1. The purposes of OLT

The purposes of doing OLT based on the developed dynamic model are stated hereby. Firstly, the mathematical model should be checked out with ideal condition to ensure the accuracy. Then, by applying the experience and operational data, the ideal dynamic model could be corrected to seek the characteristics of the DHS and various simulations.

4.2. Ideal model of the DHS

The ideal conditions represent that outside and indoor air temperature and water mass flow rate in primary and secondary system are same as their design values. The affluent factors of both heat transfer area of each substation and terminal equal to 1. No solar radiation and internal heat gains exist in the ideal dynamic system. The heat losses from both water leakage and pipe network are ignored.

With these situations, the dynamic responses of the ideal model with the fuel control signal by 0.798 are shown in Figure 3. In addition to the zone air temperature in Substation #3, which is equal to 17.9°C due to the huge thermal capacity of the floor heating structure, the supply and return temperatures from the heat source and substations are identical to the design conditions. Steady-state time of the water temperatures and zone air temperatures except for the zone air temperature in Substation #3 (48 h) reaches 15 h similarly.

Figure 3.

Dynamic responses of ideal model (a) Time(h), (b) Time(h), (c) Time(h), (d) Time(h).

4.3. Actual model of the DHS

In practice, the affluent factors of both heat transfer area of each substation and terminal are greater than 1 because of the safety consideration from designers. The circulation water flow rate could be adjusted rather than design values. With these situations, the ideal dynamic model should be modified to simulate the real DHS, which is entitled as actual dynamic model. Regarding the experience and operational data of typical DHSs in China, the affluent factors of each heat transfer area and terminal in Substations #1–#3 are provided as [1.4, 1.4, 1.4, 1.5, 1.35, 1.4], respectively.

While outside and indoor air temperature and water mass flow rate in primary and secondary system are identical to their design values, no solar radiation and internal gains exist, the water leakage and heat losses from pipe segments are considered, the control signal of fuel equals to 0.854 and the dynamic responses of the temperatures from actual model are shown in Figure 4. In this figure, the steady-state values of the supply and return water temperatures from the heat source and Substations #1–#3 are 97.5, 33.2, 57.6, 31.6, 58.6, 33.6, 38.4 and 28.1°C, while the zone air temperatures equal to 20.8, 19.6 and 18.8°C, respectively. From the values, the supply water temperature from the heat source is not necessary to satisfy its design value (120°C), while outside air temperature is −16.9°C. Meanwhile, the zone air temperatures are not same as the design values. The reason behind is that the affluent factors of the heat transfer area affect the operation very much in the DHS. It is also hinted that the zone air temperature should be controlled separately because they cannot approach its design value simultaneously.

Figure 4.

Dynamic responses of actual model (a) Time(h), (b) Time(h), (c) Time(h), (d) Time(h).

Advertisement

5. Advanced control strategies and simulations

5.1. System disturbance

Usually, the disturbances taking place in DHSs include outdoor air temperature, solar radiation and internal heat gains, while outdoor air temperature plays the biggest rule in system operation. On the other hand, when the comprehensive heat transfer coefficient (Uen value) of the buildings is getting smaller and smaller, the additional heat gains (solar radiation and internal gains) should be considered in the simulation and in real system operation. In this chapter, outdoor air temperature, solar radiation and internal heat gains are drawn into actual model with the range from 8.2 to 13.1°C, from 0 to 45 W/m2 and from 0.9 to 6.8 W/m2, respectively, for all simulations of the cases.

5.2. Control signals

In many circumstances, DHSs are operated with experience; likely, the supply water temperature from the heat source has been controlled depending on the experience of operators. Nevertheless, the disturbances described above change based on time. It means that the heating supply from the heat source and the heat consumption (heating load) should be tracked and balanced. Thus, the DHS must be regulated accordingly. Otherwise, the zone air temperature could fluctuate in larger range, which influences thermal comfort of end-user. By simulating the dynamic responses of actual model with different conditions (change outdoor air temperature, indoor air temperature as similar as design value, design water mass flow rate in the pipe network, constant water leakage rate, considered pipe insulation heat loss, no solar radiation and internal gains), the simulated stable results from OLTs are listed in Table 2 as set points for related parameters used in control strategies.

To, °C151050−5−10−16.9−20
Ts1, °C37.549.154.270.681.191.4104.2111.8
Tw2arg1, °C24.528.529.235.338.441.344.546.9
Tw2arg2, °C25.129.330.236.639.843.046.549.0
Tw2arg3, °C20.422.721.826.528.329.931.633.2

Table 2.

Set points used in control strategies.

5.3. Control strategies

Five cases are selected for dynamic simulations (given in Table 3) to study the system responses, the energy consumption (heat consumed in the cases) and the thermal comfort of the end-user [14, 15, 16, 17]. Note that typical PI algorithm is used to all controllers to gather output signals [18].

CaseControl strategyDescriptionUsed controller
1Experienced Ts1 controlSupply water temperature from the heat source controlled based on experienceCf
2Tuned Ts1 controlSupply water temperature from the heat source controlled based on tuned set pointsCf
3Tuned Ts1 and Tw2arg controlSupply water temperature from the heat source and average water temperature in the secondary system of each substation controlled based on tuned set pointsCf, C1, C2, C3
4Tuned Ts1 controlled based on
To and Tw2arg controlled based on Toe
Supply water temperature from the heat source controlled based on To and average water temperature in the secondary system of each substation controlled based on equivalent To (Toe)Cf, C1, C2, C3
5Tuned Ts1 controlled based on To and zone air temperature controlled based on TzSupply water temperature from the heat source controlled based on To and zone air temperature in each substation controlled based on TzCf, C1, C2, C3

Table 3.

Control strategies used in the cases.

5.4. Case study based on dynamic simulation

5.4.1. Case 1

Many operators run DHSs according to their experience if they cannot realize the set points of supply water temperature from the boiler. In this case with 5 days consciously, the dynamic responses of the DHS are presented in Figure 5. From this figure, the supply water temperature from the boiler changes depending on the outside air temperature (Figure 5(a)). The average water temperature responses of the secondary side in Substations #1 and #2 are almost similar and higher than that in Substation #3 due to the difference between the radiator and the floor heating terminals (Figure 5(b)). The difference of indoor air temperature dynamic responses shown in Figure 5(c) is mainly resulted from the structure of terminals. By considering the responses of the last 2 days rather than the influences of the initial parameter settings, the average and the range of the zone air temperatures in Substations #1–#3 are 20.2, 17.4–24.1, 20.9, 18.1–25.2, 21.1 and 20.7–22.2°C, respectively. The control signal of fuel in the heat source is changed based on the heating load (Figure 5(d)). The water mass flow rate in the pipe network is set to be the design values.

Figure 5.

Dynamic responses in case 1 (a) Time(h), (b) Time(h), (c) Time(h), (d) Time(h).

5.4.2. Case 2

From the simulation by using experience of the supply water temperature from the heat source, the average zone air temperatures excess their design values with bigger fluctuation. This situation should be improved by utilizing tuned supply water temperature set points (Ts1sp). With Ts1sp given in Table 2, the simulation results are shown in Figure 6. With the tuned setting value, the average zone air temperatures in Substations #1–#3 are given as 19.7, 20.2 and 20.1°C, meaning that average zone air temperatures are reduced comparing with those in Case 1.

Figure 6.

Dynamic responses in case 2 (a) Time(h), (b) Time(h), (c) Time(h), (d) Time(h).

5.4.3. Case 3

From Cases 1 and 2, the average and the fluctuation of zone air temperatures are still larger than the expected results. Because the heat properties of the substations are different, indoor air temperatures should be controlled separately to balance their heat supply and requirement. In this situation, the simulation is made and shown in Figure 7 for zone air temperature responses only, and considering the time-consuming simulation, the time span is decreased to 2 days continuously. The results illustrate that the fluctuation of zone air temperatures is reduced significantly, but average zone air temperatures are still high compared with their design values.

Figure 7.

Dynamic responses in case 3.

5.4.4. Case 4

The meaning behind average zone air temperatures excessed the deign values is that the disturbances are never considered in the control algorithm. Consequently, a concept of an equivalent outside air temperature is introduced to reset the original average water temperature set points and improve the stability and decrease zone air temperature swing. The equivalent outside air temperature is calculated in Eq. (16). This case is simulated and addressed in Figure 8. Compared with Figure 7, the purpose of decreasing zone air temperature fluctuation is realized perfectly:

Toei=To+qsolsFsi+qintFiUeni1E16

Figure 8.

Dynamic responses in case 4.

5.4.5. Case 5

As known that, average water temperature in a terminal is related to the zone air temperature indirectly, and the return water temperature from the terminal is delayed due to the thermal capacity of the terminal. If the zone air temperature is measured and applied for the control strategy, it would be better to elevate the thermal comfort of indoor environment. To this end, the simulation is made and shown in Figure 9. The dynamic responses of zone air temperatures in Substations #1–#2 are improved very much. Because of the huge thermal capacity of the radiant floor heating structure, the zone air temperature in Substation #3 although approaches 18°C still needs more advanced control strategy such as predictive control or two-temperature control to improve the dynamic response of zone air temperature.

Figure 9.

Dynamic responses in case 5.

5.5. Comparison with energy consumption

Due to relevant smaller parts of electricity and water consumption in DHSs, the heat consuming is considered only for energy comparison. The simulated results in the fuel control signal responses are presented in Figure 10. From this figure, the fuel consumption in Case 2 has the lowest value but with larger zone air temperature fluctuation. By observation with all cases, Case 5 is the best control strategy based on both dynamic responses of zone air temperature and the fuel consumption. Without measuring zone air temperature for compensation, Case 4 is the best one for optimal operation of the DHS.

Figure 10.

Comparison with fuel consumption.

Advertisement

6. Conclusions

  1. 6.1 The first law of thermodynamics and mass conservation principle can be utilized to develop dynamic mathematical models of DHSs.

  2. 6.2 The developed ideal dynamic model must be corrected to obtain actual model, which can be applied for various simulations, analysis and compression.

  3. 6.3 DHSs must be controlled due to the disturbances from outside air temperature, solar radiation and internal heat gains to reduce the influence of zone air temperature.

  4. 6.4 By dealing with the disturbances in Cases 4 and 5, the thermal comfort level has been improved significantly because of the compensation of disturbances.

  5. 6.5 Instead of the limitation of measuring zone air temperature in buildings, the equivalent outside air temperature method could be utilized to compensate the disturbances.

  6. 6.6 The best thermal comfort can be approached with the lowest energy consumption (Case 5) by utilizing zone air temperature control strategy directly to regulate average water temperature in the secondary system.

Advertisement

Nomenclature

cspecific heat (J/kg°C)
Cthermal capacity (J/°C) or controller
ffactor
Fheated floor area (m2)
Gwater mass flow rate (kg/s)
HVheating valve of fuel (J/kg)
LMTDlogarithmic mean temperature difference (°C)
qheating load per m2 (W/m2)
Qheating load (W)
ttime (s)
Ttemperature (°C)
ucontrol signal
Uheat transfer rate (W/°C)
1, 2number of substation or primary/secondary system
3number of substation
argaverage
bboiler
ddesign
enenclosure of building
exheat exchanger
ffuel
hlheat loss from pipe segment
htheater-radiator
i1–3
ininlet
intinternal
jrefer to pipe segment j
kfactor related to heater transfer coefficient test
mmix
mkmakeup water
ooutside air
oeequivalent outside air
outoutlet
rreturn
rfradiant floor
ssupply
segsegment of pipe network
solsolar radiation
spset point
wwater
zzone air
Alphabet
ηefficiency

References

  1. 1. Zaheeruddin M, Monastiriakos P. Hydronic heating systems: Transient modeling, validation and load matching control. International Journal of Energy Research. 1998
  2. 2. Lianzhong L, Zaheeruddin M, Cho SH, Jung SH. Steady state and dynamic modelling of an indirect district heating system. International Journal of Air-Conditioning and Refrigeration. 2010;18(1):61-75
  3. 3. Riederer P, Marchio D, Visier JC, Husaunndee A, Lahrech R. Room thermal modelling adapted to the test of HVAC control systems. Building and Environment. 2002;37(8-9):777-790
  4. 4. Itzhak M, Reddy TA. Literature review of artificial intelligence and knowledge-based expert systems in building and HVAC system design. ASHRAE Transactions. 2003;109:12-26
  5. 5. McQuiston FC, Parker JD. Heating, Ventilating, and Air Conditioning Analysis and Design. 6th ed. Hoboken, New Jersey, US: John Wiley & Sons Inc.; 2005
  6. 6. BLAST. Blast 3.0: Building Loads Analysis and System Thermodynamics Program. User Manual. Urbara-Champaign: Support Office, Department of Mechanical and Industrial Engineering, University of Illinois; 1979
  7. 7. Astrom KJ, Wittenmark B. Advanced Control. Boston, Massachusetts, US: Addison-Wesley Publication Company; 1989
  8. 8. Kanarachos A, Geramanis K. Multivariable control of single zone hydronic heating systems with neural networks. Energy Conversion and Management. 1998;39(13):1317-1336
  9. 9. Singh G, Zaheeruddin M, Patel RV. Adaptive control of multivariate thermal processes in HVAC systems. Energy Conversion & Management. 2000;41(15):1671-1685
  10. 10. Zoltan M, Robert P. Energy saving of district heated flats from the recommendation of the heating system in Hungary. ASHRAE Transactions. 2002;108(2):575-588
  11. 11. Nielsen HA, Madsen H. Modeling the heat consumption in district heating systems using a grey-box approach. Energy and Buildings. 2006;38(1):63-71
  12. 12. Lianzhong L, Zaheeruddin M, Cho S-H, Hong S-K. Simulated performance of a combined radiant floor heating and domestic hot water supply system under different control strategies. International Journal of Air-Conditioning and Refrigeration. 2013;21(2)
  13. 13. Lianzhong L, Zaheeruddin M. A control strategy for energy optimal operation of a direct district heating system. International Journal of Energy Research. 2004;28:597-612
  14. 14. Kitamori T. A design method for control system based upon partial knowledge about controlled processes. Transactions of the Society of Instrument and Control Engineers. 1979;15(4):549-555
  15. 15. Jacimovic B, Zivkovic B, Genie S, Zekonja P. Supply water temperature regulation problems in district heating network with both direct and indirect connection. Energy and Buildings. 1998;28(3):317-322
  16. 16. Kamimura K, Hashimoto Y, Yamazaki T, Kurosu S. A comparison of controller tuning methods from a design viewpoint of the potential for energy savings. ASHRAE Transactions. 2002;108(2):155-165
  17. 17. Liao Z, Dexter AL. An inferential control scheme for optimizing the operation of boilers in multi-zone heating systems. Building Services Engineering Research & Technology. 2003;24(4):245-256
  18. 18. Kasahara M, Matsuba T, Kuzuu Y, Yamazaki T. Design and tuning of robust PID controller for HVAC systems. ASHRAE Transactions. 1999;105-116

Written By

Li Lian Zhong

Reviewed: 07 November 2017 Published: 20 December 2017