Open access peer-reviewed chapter

Dual Robust Control of Grid-Connected DFIGs-Based Wind- Turbine-Systems under Unbalanced Grid Voltage Conditions

Written By

Kamel Djamel Eddine Kerrouche, Lina Wang, Alex Van Den Bossche, Azzedine Draou, Abdelkader Mezouar and Larbi Boumediene

Submitted: 30 January 2018 Reviewed: 16 February 2018 Published: 10 October 2018

DOI: 10.5772/intechopen.75518

From the Edited Volume

Stability Control and Reliable Performance of Wind Turbines

Edited by Kenneth Eloghene Okedu

Chapter metrics overview

1,062 Chapter Downloads

View Full Metrics

Abstract

In this chapter, a comparative analysis is made for doubly-fed induction-generator (DFIG) low-voltage ride-through (LVRT) solutions. It is supposed to improve the LVRT capability of DFIG under unbalanced grid voltage conditions by hardware or software solutions. Therefore, this chapter proposes a low-cost software LVRT solution based on an efficient control scheme of DFIG driven by a wind turbine. The proposed control scheme is based on dual-sequence decomposition technique and Lyapunov-based robust control (RC) theory. Under an unbalanced grid voltage conditions, the proposed control strategy not only eliminates effectively the oscillations of the active and reactive powers exchanged between the generator and the grid but also achieves the symmetrical and sinusoidal grid currents injection. Simulation analysis under MATLAB®/Simulink® has been carried out on a 1.5 MW DFIG-based wind-turbine-systems, and the results are presented and discussed to demonstrate the feasibility and the efficiency of the control strategy for a grid-connected application under unbalanced voltage supply. The proposed dual control scheme is shown to be able to successfully mitigate torque, stator power and currents pulsations as compared with the conventional vector control based on the single control scheme.

Keywords

  • DFIG
  • LVRT
  • unbalanced grid voltage
  • robust control

1. Introduction

Variable wind turbines are known to be able to efficiently capture energy from a wide range of wind speed. Most of the variable speed wind turbines employ doubly-fed induction-generator (DFIG) due to their various advantages such as the decoupled control of the active and reactive powers, lower converter size and cost, and the feasibility of both stand-alone and grid connected operation [1, 2]. It consists of a wind turbine, gearbox, DFIG, Rotor Side Converter (RSC), Grid Side Converter (GSC) and electrical grid. In grid integration systems of DFIGs, several research studies assumed a balanced grid voltage with conventional control strategies [3]. However, in recent years, the control and operation of DFIG under disturbances and grid unbalanced have been widely studied [4]. The transient and steady-state responses of these generators during unbalanced grid voltage conditions have been presented in [5]. It has been specified from [6] that if the unbalanced grid voltage is not included in the synthesis of DFIG’s controllers, high oscillations will occur in the generator torque and the injected powers might be very harmful to wind turbine components and grid connection stability. Moreover, unbalanced stator and rotor currents and DC-link voltage oscillations may lead to the increase in generator losses, temperature increase and reduction of the lifetime of DC-link capacitor [7]. Under unbalanced grid voltage, direct power control (DPC) has been adopted to control the grid-connected wind turbine-driven DFIGs in [5] by using proportional-resonant (PR) controller [7] and sliding mode control (SMC) approach [8, 9]. Moreover, in [10, 11], conventional vector control (VC). Moreover, conventional vector control (VC) with an auxiliary PI current controller has also been adopted to help regulating the negative sequence current components. Otherwise, if no negative grid voltage sequence is considered in the control loop, the occurrence of unbalanced faults can deteriorate the performance of DFIGs. Nevertheless, the control loops considered in [7, 8] keep both active and reactive power constant with reduced power ripples and at the same time significant odd order current harmonics are generated, which is not allowed by the IEEE 519-1992 [12, 13]. Therefore, an additional cost is required by active filtering [3] may not be a practicable solution for grid-connected WECS. In [14], it has been shown that during balanced or symmetrical three-phase fault, an additional STATCOM system is reported as a promising device for applications of WECS based grid-connected.

In this chapter, a review of the recently published LVRT schemes is discussed. Then, a VC approach-based dual-sequence decomposition approach associated to the Lyapunov based robust control (RC) is proposed; in order to reduce the torque ripples, minimize the active and reactive powers pulsations by obtaining sinusoidal and symmetrical injected grid currents, when the voltage at the stator is unbalanced. The details of DFIG modeling, positive and negative components separation methods and RC technique are theoretically explained in this chapter. Moreover, comprehensive simulation tests and results of the WECS are carried out and included in this chapter.

Advertisement

2. Wind energy generator system

In recent years, several configurations are used for the dynamic model of DFIG systems, which can be shown in various reference frames such as stationary reference frame [9] or rotating reference frame [6, 11]. In this chapter, DFIG is modeled in a rotating reference frame under balanced and unbalanced operation conditions.

2.1. Balanced DFIG model

Using the assumption of linear magnetic circuits, the stator and rotor voltages expressions of the DFIG under balanced operating condition are written as follows [2, 15]:

Vs=vdsvqs=Rsids+dϕdsdtωsϕqsRsiqs+dϕqsdt+ωsϕds,Vr=vdrvqr=Rridr+dϕdrdtωsωϕqrRriqr+dϕqrdt+ωsωϕdrE1

where ids, iqs, idr and iqr are, respectively, the direct and quadrature stator and rotor currents. Rs and Rr are stator and rotor resistances. ωs, ω are stator and rotor electrical angular speed, with ω=pΩg, p is the pair pole number. The stator and rotor fluxes can be expressed as:

ϕs=ϕdsϕqs=Lsids+MidrLsiqs+Miqr,ϕr=ϕdrϕqr=Lridr+MidsLriqr+MiqsE2

where Ls, Lr and M are stator, rotor and mutual inductances. The active and reactive powers at the stator are defined as:

Ps=vdsids+vqsiqsQs=vqsidsvdsiqsE3

The principle of the conventional VC method consists of orientating the stator flux in such a way that the stator flux vector points into the d-axis direction. This approach is realized by setting the quadrature component of the stator flux to the null value:

ϕs=ϕdsϕqs=0E4

Using the condition that the per phase stator resistance is neglected, and that the grid system is in steady state that is having a single voltage Vs that leads to stator’s constant flux ϕs, the voltages can be easily deduced to be as:

vds=0vqs=ωsϕs=VsE5

The following equations are obtained when replacing the rotor flux Eq. (2) in Eq. (1) and using the above condition Eq. (5), the rotor voltages become:

vdr=σLrdidrdt+RridrσLrωriqr+MLsdϕdsdtvqr=σLrdiqrdt+Rriqr+σLrωridr+ωrMLsϕsE6

where Vs is the stator voltage magnitude is assumed constant, and ωr=ωsω=gωs is the slip frequency, and g is the slip range and σ=1M2LsLr is the leakage coefficient. Consequently, with regard to Eq. (4), the fluxes are simplified as indicated below:

ϕds=Lsids+Midr0=Lsiqs+MiqrE7

From Eq. (7), the stator currents can be deduced as:

ids=ϕdsMidrLsiqs=MLsiqrE8

By using Eqs. (3), (5) and (8), the stator active and reactive powers can then be expressed only versus these rotor currents as:

Ps=VsMLsiqrQs=VsMLsidrϕdsME9

2.2. Unbalanced DFIG model

As stated in [10, 11], during unbalanced grid voltage, the DFIG system can be separated into positive, negative and zero sequences. In this chapter, two methods are proposed for separate positive and negative sequences: delay inverse component canceling (DICC) method. And Notch filter method.

In the first method, the components in the three-phase a,b,c system are transformed into two-phase α,β stationary reference frame. Then, the positive and negative components can be determined by the following expression:

vαs+vβs+vαsvβs=121001011010010110vαstvβstvαstT4vβstT4E10

The obtained positive and negative sequences from Eq. (10) in stationary reference frame are transformed into positive and negative sequences in rotating reference frame as follows:

vds+vqs+vdsvqs=cosθssinθs00sinθscosθs0000cosθssinθs00sinθscosθsvαs+vβs+vαsvβsE11

The associated Simulink scheme of the separate positive and negative sequences based on DICC method is depicted in Figure 1.

Figure 1.

Simulink block for DICC method.

In the second method, the component of the negative sequence seems as a second-order harmonic in the positive rotating reference frame d,q+ and the component of the positive sequence seems as a second-order harmonic in the negative rotating reference frame d,q. Then, the DC values are bypassed and the high-frequency oscillations are suppressed by the notch filter tuned at ω0=2ωs and ξ=0.707. The associated Simulink scheme of this method is shown in Figure 2.

Figure 2.

Simulink block for the notch filter method.

In Figure 3, the unsymmetrical voltage dip was applied between 1.5 and 1.6 s. Then, with two separation methods, the positive and negative sequences of the stator voltages in the rotating reference frame d,q are shown in Figure 4.

Figure 3.

Grid stator voltage.

Figure 4.

Unbalanced voltages in positive and negative dq rotating reference frame: (a) with DICC method and (b) with notch filter method.

It can be noticed from these figures that the method based on DICC is faster than the method based on the notch filter. Therefore, the DICC method is chosen in this chapter due to its fast and precise characteristics. Assuming that the zero-sequence in the grid is neglected, the unbalanced stator voltages can be written as follows:

Vs+=vds+vqs+=Rsids++dϕds+dtωsϕqs+Rsiqs++dϕqs+dt+ωsϕds+,Vs=vdsvqs=Rsids+dϕdsdt+ωsϕqsRsiqs+dϕqsdtωsϕdsE12

The voltages at the rotor side are:

Vr+=vdr+vqr+=Rridr++dϕdr+dtωsωϕqr+Rriqr++dϕqr+dt+ωsωϕdr+,Vr=vdrvqr=Rridr+dϕdrdtωs+ωϕqrRriqr+dϕqrdt+ωs+ωϕdrE13

The stator and rotor fluxes are:

ϕds+ϕqs+ϕdsϕqs=Lsids++Midr+Lsiqs++Miqr+Lsids+MidrLsids+Midr,ϕdr+ϕqr+ϕdrϕqr=Lridr++Mids+Lriqr++Miqs+Lridr+MidsLridr+MidsE14

Under unbalanced grid, the active and reactive powers expression in Eq. (3) is decomposed into different pulsating components, which can be rewritten as:

PsQsPssin2Pscos2=vds+vqs+vqs+vds+vdsvqsvqsvdsvqsvdsvdsvqsvqs+vds+vds+vqs+ids+iqs+idsiqsE15

In order to obtain a constant stator power, the oscillating terms of the active and reactive powers Pssin2,Qscos2 in (15) are neglected, therefore, only the average terms are controlled. By inverting (15), the stator currents can by calculated as follows:

ids+iqs+idsiqs=PsD1vds+vqs+vdsvqs+QsD2vqs+vds+vqsvdsE16

where D1=vds+2+vqs+2vds2+vqs2 and D2=vds+2+vqs+2+vds2+vqs2.

Figure 5 shows that the positive stator flux is aligned along with the d+-axis and rotates at the speed of ωs, whereas the d-axis rotates at an angular speed of ωs, with the phase angle to the α-axis being θs. Therefore, by using Eq. (12) with stator flux orientation under unbalanced grid, the stator currents are simplified as follows:

ids+iqs+idsiqs=1Lsϕds+0ϕds0MLsidr+iqr+idriqrE17

Figure 5.

Stator flux orientation under unbalanced grid.

Combining Eq. (17) with Eq. (16), the rotor currents are written as follows:

idr+iqr+idriqr=LsMPsD1vds+vqs+vdsvqsLsMQsD2vqs+vds+vqsvds+Mϕds+0ϕds0E18
Advertisement

3. Controllers design

The details of the conventional Lyapunov-based robust control have been presented in [16, 17, 18], so, this control strategy with unbalanced DFIG model is considered in this chapter.

3.1. Tracking error

In this chapter, J. J. Slotine [16] proposed the used tracking error:

Sx=t+λxn1exE19

where ex is the error vector (e(x) = x* −x), λx is a positive coefficient, n is the system order. To bring the state variable to the tracking errors, the following two conditions have to be satisfied:

Sx=0,ddtSx=0E20

For n = 1 in Eq. (19), the errors of direct and quadrate rotor currents are chosen as:

Sx=S1idr+=idr+idr+S2iqr+=iqr+iqr+S3idr=idridrS4iqr=iqriqrE21

3.2. Control law

In this chapter, the Lyapunov-based robust control is used to generate voltage references as an input to PWM. The control law satisfies the previous conditions is presented in the following form:

Vr==Vr,eq+Vr,nE22

where Vr is the control vector, Vr,eq is the equivalent control vector, Vr,n is the switching part of the control law.

The derivative of the tracking error (20) is rewritten as follows:

ddtSx=F+DVrE23

From Eq. (20), when the trajectories of rotor currents converge toward their references, the derivative of the tracking error is:

ddtSx=F+DVr=0E24

The following equation is obtained by replacing the rotor flux Eq. (14) in Eqs. (12) and (13) and combining with Eq. (24):

F=F1F2F3F4=i̇dr++RrσLridr+ωriqr++MσLrLsvds+RrσLriqr++i̇qr++ωridr++MσLrLsvqs+MσLrLsϕsd+ωsωri̇dr+RrσLridrωriqr+MσLrLsvdsRrσLriqr+i̇qr+ωridr+MσLrLsvqsMσLrLsϕsdωs+ωrE25

where

D=1σLr1000010000100001E26

The following control law is obtained:

Vr=D1F1+K1satS1F2+K2satS2F3+K3satS3F4+K4satS4E27

and

satSi=1,Si>λiSi/λiSiλi1,Si<λiE28

where λi is the width boundary layer and i indicates 1, 2, 3 or 4 and K1, K2, K3 and K4 are positive control gains of the switching control part.

3.3. Lyapunov stability proof

The stability and robustness of the system are thoroughly investigated and subsequent results are presented in [16, 17, 18]. In this chapter, the stability theory of Lyapunov is used to check the convergence of the tracking errors toward the zero by satisfying the following condition:

V̇=STxṠx0E29

Then, the Lyapunov function is obtained as:

V̇=STxF+DVr0E30

By using Eq. (27), Lyapunov function Eq. (30) is rewritten as:

V̇=STxF+DD1F1+K1satS1F2+K2satS2F3+K3satS3F4+K4satS40E31

Or

V̇=STxK1satS1K2satS2K3satS3K4satS40E32

From Eq. (32), the Lyapunov function is definitely negative so that the control law becomes stable.

3.4. Lyapunov robustness proof

In practice, the tracking error S will be influenced by the parameter variations and measurement uncertainties. Thus, Eq. (23) is rewritten as:

ddtSx=F+DVr+HE33

where H = [H1 H2 H3 H4]T represents system disturbances. Thus, Eq. (35) can be rewritten as:

V̇=STxH1H2H3H4K1satS1K2satS2K3satS3K4satS40E34

It is worth mentioning that if the positive control gains satisfy the following condition, specifically, K> |H1|, K> |H2|, K> |H3| and K> |H4| the time derivative of Lyapunov function V̇ is still definitely negative. Consequently, the control law features are robust. Figure 6 shows the block diagram of the VC scheme for DFIG using Lyapunov-based robust control (RC). In this block diagram, the Phase-Locked-Loop (PLL) estimates the frequency, the grid voltage magnitude and the stator angle. The block of separate positive and negative sequences of the current and the voltage shown in Figure 1 is used in this schema for the dual current controller and the calculation of the current references.

Figure 6.

Block diagram of the proposed Lyapunov-based robust control scheme.

Advertisement

4. Simulation results

The generator is tested under single line to ground fault condition on phase ‘a’; at 1.5 s an unbalanced voltage drop of 20% is created for a time of 0.1 s as shown in Figure 3. In this section, all the physical quantities are in per unit values, and the quantities of the rotor are referred to the stator side. Figure 7 shows the Simulink block diagram of the DFIG wind turbine model. The switching frequency of converter is set to 1 kHz; the nominal DC converter is set to 2000 V. Wind speed varies from 10 to 11 m/s. To examine the validity of the proposed dual Lyapunov based robust control scheme (RCS), these results are compared with the conventional single Lyapunov-based RCS published in [15].

Figure 7.

Simulink block diagram of the DFIG wind turbine model.

Figures 8(a) and (b), 9(a) and (b), 10(a) and (b) and 11(a) and (b), show that, during grid voltage unbalance, if conventional control is applied, the active and reactive powers contain important oscillations due to the nature of the second harmonic at twice the grid frequency (100 Hz) with magnitude of 0.78 pu. The conventional control does not provide adequate control of the negative sequence current during the occurrence or removal of voltage unbalance. Whereas, by using the proposed control method, these oscillations are dramatically reduced because of the negative sequence current compensation, during grid fault, by the dual current control loops which can indirectly control these powers.

Figure 8.

Stator active power (pu): (a) conventional single RCS, (b) proposed dual RCS.

Figure 9.

Harmonic spectra of the stator active power (pu): (a) conventional single RCS, (b) proposed dual RCS.

Figure 10.

Stator reactive power (pu): (a) conventional single RCS, (b) proposed dual RCS.

Figure 11.

Harmonic spectra of the stator reactive power (pu): (a) conventional single RCS, (b) proposed dual RCS.

Figures 12(a) and (b) and 13(a) and (b) show that the ripples of the electromagnetic torque are also mitigated with the proposed control. On the contrary, when we use the conventional control method, the electromagnetic torque has oscillations with magnitude of 0.74 pu and frequency of 100 Hz, which might be harmful to the mechanical parts.

Figure 12.

Electromagnetic torque (pu): (a) conventional single RCS, (b) proposed dual RCS.

Figure 13.

Harmonic spectra of the electromagnetic torque (pu): (a) conventional single RCS, (b) proposed dual RCS.

Figures 14(a) and (b) and 15(a) and (b) show that the stator currents have important harmonics with conventional control, which are injected into grid, but these currents are quite sinusoidal and symmetrical with the proposed control.

Figure 14.

Stator currents (pu): (a) conventional single RCS, (b) proposed dual RCS.

Figure 15.

Harmonic spectra of the stator currents (pu): (a) conventional single RCS, (b) proposed dual RCS.

Figures 16(a) and (b) and 17(a) and (b) show that the currents at the rotor side are also unbalanced with conventional control, but these oscillations are attenuated by using the proposed control method. This is due to the fact that the conventional control cannot control the negative component introduced by the unbalanced voltage in the stator flux and current vectors to zero. In that situation, interaction of these components in the generator develops motoring and generating behavior resulting in excessive oscillations. The stator flux amplitude is constant at the steady-state and rotates synchronously with the grid voltage. Instantly after the occurrence of the unbalanced voltage dip (see Figure 3), two voltages cause a positive and negative flux in the stator. Unlike the case of balanced voltage dip, where two components will be induced in the stator flux: the forced component is rotating with the grid frequency; afterward, the natural flux is static with the stator.

Figure 16.

Rotor currents (pu): (a) conventional single RCS, (b) proposed RCS.

Figure 17.

Harmonic spectra of the rotor currents (pu): (a) conventional single RCS, (b) proposed dual RCS.

Figure 18(a) and (b) shows the trajectory of the stator flux. Before the voltage unbalance, the stator flux traces a circle with radius equal to 1 pu. The flux of the stator with the proposed dual RCS is very well centered compared with that obtained with the conventional single RCS. When the voltage unbalance starts, the ellipse trajectory drawn by the flux is due to the presence of positive and negative flux in the stator rotating in opposite directions, which is a common characteristic in unbalanced voltage sags. Whereas, the natural flux brings the ellipse to be off-center. After the clearance of the voltage unbalance, the natural component of the stator flux is attenuated and the trajectory of the stator flux turns into the center again. However, it is noticed from these figures that compared with the proposed dual RCS, the stator flux trajectory of the conventional single RCS is not well centered with an important transient with a slow decay.

Figure 18.

Stator flux (pu): (a) conventional single RCS, (b) proposed dual RCS.

For clear illustrations, Figures 19 and 20 are included to show the comparative results of ripples pulsating at twice the grid frequency (100 Hz) in the stator active/reactive powers and electromagnetic torque among these different control strategies during network unbalance. As presented, the proposed dual RCS aims at mitigating the torque pulsations and the power ripples compared with the conventional method. In addition, the proposed dual RCS is able to reduce the harmonics of the rotor and stator currents. It can be concluded from these strategies that the proposed control method can effectively reduce the torque oscillations which incidentally may lead to a decrease of the fatigues on the turbine shaft.

Figure 19.

Comparison of ripples in electromagnetic torque, stator active and reactive power between the two control strategies.

Figure 20.

Comparison of harmonics in stator and rotor currents between the two control strategies.

Advertisement

5. Conclusions

In this chapter, an improved control strategy for doubly fed induction generator (DFIG)-based wind turbine under unbalanced grid voltage is presented. The dynamic behavior of DFIG by the proposed control algorithm proved to be suitable by a set of simulation tests using the MATLAB®/Simulink® environment. The results obtained imply that with the conventional single robust control scheme (RCS), the magnitude of the second harmonic oscillations can become high, intolerable and may lead to electrical and mechanical failure in function. After removing the voltage unbalance, in the conventional control method, small oscillations appear in the powers and currents waveforms. On the contrary, when the proposed dual RCS is used, these power oscillations are effectively damped to a reasonable level. Furthermore, the proposed control strategy shows good performances and robustness by eliminating the pulsations in the torque which maybe preferred by wind farm operators since it will mitigate the fatigue of the turbine shaft as well as the gearbox. Moreover, symmetrical and sinusoidal stator and rotor currents are also obtained, in turn minimizing the copper losses in the rotor circuit, when the grid voltage is unbalanced. All computer simulations have been designed with a fixed-step size of 0.5 ms in order to consider digital implementation in future works.

Advertisement

A. Appendix

In this part, simulations are investigated with a 1.5 MW generator connected to a 690 V/50 Hz grid [15].

The generator’s parameters are presented below:

Three pole pairs, = 0.012 Ω, = 0.021 Ω, = 0.0135 H, = +2.00372 e−4 H, = +1.7507 e−4 H,

Turbine’s parameters: three blades, diameter = 70.5 m, gearbox ratio = 90: inertia (turbine + DFIG) = 1000 kg m2 and viscous coefficient (turbine + DFIG) = 0.0024 kg m/s.

References

  1. 1. Kerrouche K, Mezouar A, Belgacem K. Decoupled control of doubly fed induction generator by vector control for wind energy conversion system. Energy Procedia. 2013;584:239-248
  2. 2. Gayen PK, Chatterjee D, Goswami SK. A low-voltage ride-through capability enhancement scheme of doubly fed induction generator based wind plant considering grid faults. Journal of Renewable and Sustainable Energy. 2016;8:025301
  3. 3. Kerrouche KDE, Mezouar A, Boumediene L, Kh B. Modeling and optimum power control based DFIG wind energy conversion system. IREE. 2014;9:174
  4. 4. Brekken TKA, Mohan N. Control of a doubly fed induction wind generator under unbalanced grid voltage conditions. IEEE Transactions on Energy Conversion. 2007;22:129
  5. 5. Mwasilu F, Justo JJ, Ro K-S, Jung J-W. Improvement of dynamic performance of doubly fed induction generator-based wind turbine power system under an unbalanced grid voltage condition. IET Renewable Power Generation. 2012;6:424
  6. 6. Abad G, Rodriguez MA, Iwanski G, Poza J. Direct power control of doubly fed induction generator based wind turbines under unbalanced grid voltage. IEEE Transactions on Power Electronics. 2010;25:442
  7. 7. Shehata EG. Active and reactive power control of doubly fed induction generators for wind energy generation under unbalanced grid voltage conditions. Electric Power Components and Systems. 2013;41:619
  8. 8. Hu J, Nian H, Hu B, He Y, Zhu ZQ. Direct active and reactive power regulation of DFIG using sliding mode control approach. IEEE Transactions on Energy Conversion. 2010;25:1028
  9. 9. Shang L, Hu J. Sliding-mode based direct power control of grid-connected wind-turbine-driven doubly fed induction generators under unbalanced grid voltage conditions. IEEE Transactions on Energy Conversion. 2012;27:362
  10. 10. Xu L, Wang Y. Dynamic modeling and control of DFIG-based wind turbines under unbalanced network conditions. IEEE Transactions on Power Systems. 2007;22:314
  11. 11. Lee S-B, Lee K-B, Lee D-C, Kim J-M. An improved control method for a DFIG in a wind turbine under an unbalanced grid voltage condition. Journal of Electrical Engineering & Technology. 2010;5:614
  12. 12. Norm's IEEE STD 519-1992: IEEE recommended practices and requirements for harmonic control in electrical power systems. April 12, 1993. pp. 15-99
  13. 13. Tedjini H, Meslem Y, Rahli M, Berbaoui B. Shunt active filter in damping harmonics propagation. Advances in Electrical and Computer Engineering. 2010;10:108-113
  14. 14. Abdou AF, Abu-Siada A, Pota HR. Improving the low voltage ride through of doubly fed induction generator during intermittent voltage source converter faults. Journal of Renewable and Sustainable Energy. 2013;5:043110
  15. 15. Kerrouche KDE, Mezouar A, Boumediene L, Van Den Bossche A. A comprehensive review of LVRT capability and sliding mode control of grid-connected wind-turbine-driven doubly fed induction generator. Automatika—Journal for Control, Measurement, Electronics Computing and Communications. 2016;60:922-935
  16. 16. Dash PK, Patnaik RK. Adaptive second order sliding mode control of doubly fed induction generator in wind energy conversion system. Journal of Renewable and Sustainable Energy. 2014;6:053143
  17. 17. Kerrouche K, Mezouar A, Boumediene L. A simple and efficient maximized power control of DFIG variable speed wind turbine. In: Proceedings 3rd International Conference on Systems and Control (ICSC) IEEE, Algiers, Algeria. 2013. p. 894
  18. 18. Kerrouche KDE, Mezouar A, Boumediene L, Van Den Bossche A. Modeling and Lyapunov-designed based on adaptive gain sliding mode control for wind turbines. Journal of Power Technologies. 2016;96:124

Written By

Kamel Djamel Eddine Kerrouche, Lina Wang, Alex Van Den Bossche, Azzedine Draou, Abdelkader Mezouar and Larbi Boumediene

Submitted: 30 January 2018 Reviewed: 16 February 2018 Published: 10 October 2018