Development and Control of Generator-Converter Topology for Direct-Drive Wind Turbines

By Akanksha Singh

Submitted: September 21st 2018Reviewed: March 15th 2019Published: June 27th 2019

DOI: 10.5772/intechopen.85877

Downloaded: 162

Abstract

In this chapter, a new topology for Direct-Drive Wind Turbines (DDWTs) with a low-voltage generator design is presented in order to eliminate the required dc-bus capacitors or dc-link inductors. In the presented topology, the grid-side converter is replaced by a boost Current Source Inverter (CSI) therefore removing the need for the dc-bus electrolytic capacitors which results in increasing the system lifetime. In the developed topology, the synchronous inductance of the generator is utilized. This facilitates the elimination of the intrinsically required dc-link inductor in the CSI which further contributes to a reduction in the overall system weight and size. The boost CSI is capable of converting a low dc voltage to a higher line-to-line voltage. This results in the implementation of a low-voltage generator for DDWTs. The feasibility of the presented low-voltage generator is investigated through Finite Element (FE) computations. In this chapter, a modified 1.5 MW low-voltage generator for the proposed topology is compared with an existing 1.5 MW Permanent Magnet (PM) synchronous generator for DDWTs. The feasibility of the presented topology of generator-converter for DDWTs is verified through simulations and laboratory tests. Furthermore, the controls developed for the developed wind turbine topology is also presented in this chapter.

Keywords

  • boost CSI
  • direct-drive wind turbine
  • finite element analysis
  • permanent magnet synchronous generator
  • wind turbine topologies

1. Introduction

Wind power is one of the fastest growing energies and the global capacity has increased to 433 GW by the end of 2015 [1, 2]. The two most commonly used topologies for wind turbines are based on the Doubly Fed Induction Generator (DFIG) or Permanent Magnet Synchronous Generator (PMSG) [3]. In the DFIG configuration, the stator of the generator is directly connected to the grid while the rotor does not require to rotate at the fixed synchronous speed. The rotor is connected to the turbine shaft through a gearbox. In the PMSG-based wind turbines, the speed of the rotating magnetic field and the rotor is the same and therefore, it is connected to the grid through power converters. The PMSG-based wind turbines require a power electronics interface to be connected to the grid which provides the flexibility of using these turbines with or without gearbox between the turbine shaft and the generator shaft [3]. It has been shown that the gearboxes cause more downtime than any other component in a wind turbine [3, 4, 5]. It is worth noting that the gearboxes are responsible for 10% of the wind turbine failures which result in about 20% of the total wind turbine downtime [4, 5, 6]. Recent investigations reveal that gearboxes in wind turbines, which were supposed to last 20 years, might fail in 7–10 years [7, 8]. The Direct-Drive Wind Turbines (DDWTs) do not have a gearbox between the turbine rotor and the generator shaft. There is a definite trend toward DDWTs as is predicted in the research papers and trade articles but there are some major concerns that must be overcome in order to achieve higher market penetration [1, 9]. The power electronics interface in a DDWT is rated for full power transfer and it consists of an active rectifier and a grid-side converter, connected through a capacitor bank forming the dc-bus. The power electronics interface is one of the most vulnerable components in wind turbines [4, 5, 7]. A significant percentage of these failures have been attributed to the dc-bus electrolytic capacitors [10, 11]. Many methods which try to determine the remaining lifespan of electrolytic capacitors exist and are utilized for scheduled maintenance planning [5]. These methods do not serve to extend the life of the capacitors and contribute to an increase in the system downtime [7]. The other major concern which prevents the proliferation of DDWTs is the large size of PMSGs [12, 13]. The large size of the generator is a result of the generator shaft rotating at the same speed as the turbine rotor shaft. The low angular speed in PMSGs increases the required pole surface and the number of poles, which results in a high cost and volume of the generator.

In the most commonly used DDWT configuration the power electronics interface comprises of back-to-back Voltage Source Converters (VSCs) connected through electrolytic capacitors [14]. In this paper, the grid-side VSC is replaced by the boost Current Source Inverter (CSI). The proposed boost CSI topology of the converter results in the elimination of the dc-bus electrolytic capacitors, which are one of the frequently failing components in the existing topologies of direct-drive wind turbines without any supplementary component at the dc-bus [10, 11, 15]. The boost CSI converts the low dc voltage of the generator rectifier to the higher voltage level which facilitates the implementation of low voltage PMSG with lower weight and volume [16]. In addition to the introduction, this chapter has five more sections. In Section 2, the existing wind turbine topologies are reviewed, and the topology of the developed system is introduced. Section 3 presents the feasibility of a 1.5 MW low-voltage PMSG for the presented system. This section also presents a comparison between the generator for the developed system and an existing 1.5 MW PMSG for a DDWT using Finite Element (FE) computations. The controls developed for the new DDWT topology are presented in Section 4. The simulation results demonstrating the feasibility of the developed system are presented in Section 5. A laboratory scale setup is used to experimentally confirm the feasibility of the proposed topology in Section 6. Section 7 presents the conclusions of the chapter.

2. Wind turbine topologies

In this section, several wind turbine topologies are reviewed prior to introducing the inductorless current source generator-converter topology.

2.1 Indirect drive wind turbine topologies

In the majority of wind turbine topologies, the windmill rotor shaft is connected to the generator through a gearbox [14, 17]. The indirect drive wind turbines can be assembled using various types of generators and converters. Most commonly used indirect wind turbine utilizes the DFIG configuration of the drivetrain. In this configuration, the rotor is connected to the grid through a back-to-back converter while the stator windings are directly connected to the grid and. This back-to-back converter includes of two bidirectional converters connected at the dc-bus, which formed by a capacitor bank. In this configuration, the major part of the power injected into the grid is through the stator of the generator and the back-to-back converters transfer only a fraction of the power produced by the wind turbine into the grid. The PMSG with the same back-to-back converter topology is another common indirect drive wind turbine topology. Unlike in the DFIG configuration, the converter is rated for the full power.

2.2 Direct drive wind turbine (DDWT) topologies

The DDWT is a relatively new topology and has the turbine rotor shaft directly connected to the generator shaft without any gearbox. Figure 1 shows commonly used topologies for DDWTs using the PMSG. Figure 1(a) displays the power electronics interface which consists of a diode bridge rectifier, dc-dc boost converter, and grid-tied VSC [17, 18]. Figure 1(b) shows another DDWT topology with power electronics interface consisting of grid-tied back-to-back Current Source Converters (CSCs) connected through a dc-link inductor [19, 20]. Figure 1(c) demonstrates the most frequently used configuration of DDWTs, comprising of a PMSG connected to the grid through two VSCs [17, 21, 22]. The dc-bus between the VSCs is formed using electrolytic capacitors in order to regulate and stabilize the dc-bus voltage. In some cases, multilevel converters are used to form the power electronics interface in the drivetrain. The topology of the multilevel converters can be an H-bridge back-to-back converter or a neutral-point-clamped back-to-back converter [17, 22]. Most wind turbine topologies either have a dc-bus formed by electrolytic capacitors or a dc-link formed by inductors. The electrolytic capacitors are one of the most failure-prone components that adversely impact the system reliability [5]. The failure of these capacitors has a significant impact on the maintenance cost especially in the case of offshore wind turbines [13, 23]. The dc-link inductor is bulky and adds to the system loss reducing the system’s efficiency [19]. In some cases, the grid side converter is located away from the wind turbine and the transmission cable is used to realize the dc-link inductor [20]. Additionally, the lack of gearbox in the DDWT increases the size of the PMSG and the capital cost of the overall system [13, 23, 24, 25]. In the following, the proposed DDWT topology is described.

Figure 1.

Common DDWT topologies with (a) PMSG connected to diode-bridge, boost converter and VSI, (b) PMSG connected to back-to-back CSCs, and (c) PMSG connected to back-to-back VSCs.

2.3 Proposed DDWT topology

The proposed topology for the DDWT is presented in Figure 2. In this subsection, different parts of the proposed topology are explained. First, the power electronics interface topology is presented, and then, the PMSG design flexibility provided by implementing the boost CSI is described.

Figure 2.

The proposed wind turbine system topology with PMSG connected to a VSC and the boost inverter equipped by RB-IGBTs.

2.3.1 The power electronics interface

The power electronics interface in the proposed topology is a back-to-back converter made up of a three-phase VSC and a boost CSI, as shown in Figure 2. The boost CSI is equipped by Reverse Blocking IGBTs (RB-IGBT), and no dc-bus capacitor or dc-link inductor exists in the proposed DDWT. As a result of avoiding the dc-bus capacitor, the system mean-time-between-failure can significantly be improved in comparison with the conventional VSC-based systems [26]. While any CSI requires an inductor at the dc-link, the proposed DDWT eliminates the dc-link inductor by utilizing the generator synchronous inductance, Ls[15]. In order to achieve a Total Harmonic Distortion (THD) of the current waveforms at the inverter output acceptable under the IEEE 1547–2018 interconnection standards, the operation of the boost CSI must always be in Continuous Conduction Mode (CCM). The minimum dc-link inductance, Ldcrequired to keep the inverter in CCM has been derived in [27]. However, the synchronous inductance, Ls, will be less than the Ldc, i.e.Ls=3/2Ldc. This is because Thevenin’s equivalent inductance of the generator-converter from the dc-bus is almost 3/2Lsand Irms2/3Idc. Also, a traditional CSI operated using space vector PWM switching provides a maximum boost ratio, VLLrms/Vdc, of about 1.2 [28]. However, the boost CSI is modulated using the Phasor Pulse Width Modulation (PPWM) switching technique, providing a boost ratio more than three [29, 30, 31]. As a result, a low voltage PMSG design will be possible for the proposed DDWT. The advantages gained by using a low voltage generator are discussed in the next subsection.

2.3.2 The permanent magnet generator

The low dc-side voltage required by the boost CSI enables a low output ac-voltage from the PMSG. In a traditional DDWT topology, the voltage at the generator and the grid should have almost the same rms value [32, 33]. However, if the developed topology is utilized, then, for example, 120VLLrmsfrom the PM generator is sufficient to generate an rms line-to-line voltage of 480 V at the converter output. As described in [15], consider the emf equation ENphpωmϕp, where, Eis the peak induced voltage per phase, Nphis the number of winding turns per phase, ωmis the mechanical angular velocity, pis the total number of poles, and ϕpis the maximum magnetic flux per pole, [33]. Here ωmis dependent on the wind speed, and the fundamental magnetic flux per pole is obtained from ϕp4/πBm2π/pD/2l=4DlBm/p, where Dis the mid-airgap diameter, Bmis the flux density, and lis the stack length. Accordingly, for a given angular velocity, permanent magnet material, and air-gap height, lgone can say ENphDl, which means that a generator with a lower output voltage requires a lower value of NphDl. On the other hand, the minimum synchronous inductance, required for the boost CSI to operate in CCM, restricts the maximum number of poles, since LsDl/lgNph/p2[33]. Hence, the desired values of the generator output voltage, E2ωsLsI21/2Eand synchronous inductance, Ls,are herein used as the PMSG design inputs for a given rated power.

3. Generator design and comparison

In this section, a 1.5 MW PMSG is designed for the proposed DDWT topology and then the design is compared with an existing 1.5 MW PMSG [34].

3.1 New generator design

The generator is designed using GenAC toolbox of MagneForce Finite Element (FE) software. The designed machine is a low-speed, concentrated overlapping tooth coil double layered winding, three-phase PMSG rated at 1.5 MW. The generator is designed to be radial flux, cylindrical rotor, rotor surface mounted pole machine so that it can be compared with the existing 1.5 MW PMSG [34]. For the sake of comparison, both the existing and new 1.5 MW systems have the rated speed of 19.65 rpm, and the same generator airgap of 0.6 mm. Also, the line-to-line voltage of the new generator is 450 V, while the existing generator line-to-line voltage is 770 V, see Table 1.

ParameterExisting generatorDesigned (new) generator
Power rating1.5 MW1.5 MW
Speed19.65 rpm19.65 rpm
Air gap length0.6 mm0.6 mm
Line-to-line voltage770 V450 V

Table 1.

The existing and new generator input parameters.

Figure 3 shows the cross-sectional view of the new generator, including the stator slot and tooth dimensions in details. Moreover, the insulation thickness in each slot is 3.5 mm. The overall slot-fill is about 62%. Also, the rotor shaft bore diameter is 700 mm. The stator bore diameter is 3500 mm, the stator length is 600 mm, and the airgap length, lg, is 0.6 mm. The PM material is sintered Neodymium Iron Boron (NdFeB) with the maximum residual flux density of Br=1.2 T, and maximum coercive force of 24kOersted(i.e. Hc=1910 kA/m). The permanent magnet pole dimension is as 260×100mm2with a pole arc to pole pitch ratio of 0.8. Figure 4 demonstrates the electromagnetic flux and the flux density distribution over the PMSG at 1 p.u.load. As can be seen in Figure 4, the generator is not saturated at rated load. The maximum flux density is observed at the stator tooth, and the maximum airgap flux density measured using FE computations is about 1.15 T. Using circuit simulation for the new design, ~20 mH is needed to keep the dc-link current in CCM for different load levels.

Figure 3.

Cross sectional view of the new design 1.5 MW PMSG.

Figure 4.

Flux and flux density distribution (T) over the cross-section of the designed PMSG at full load.

3.2 Generator parameter comparison

In this subsection, the designed PMSG is compared with an existing 1.5 MW PM generator for DDWT [34]. Table 2 shows the differences between the new and existing design parameters. In order to compare the two generators, the existing generator design is duplicated using the FE software. The design parameters for the existing generator are obtained from [34]. The comparison of the generator no-load line-to-line voltage, and the flux linkage with respect to rotor electrical position is presented in Figure 5. The no-load line-to-line voltage waveforms are shown in Figure 5(a). The flux linkage of phase-A of the generator versus the rotor electrical position is presented in Figure 5(b). As can be seen in Figure 5(b) that there is minimal distortion in the flux linkage, and it is sinusoidal for the generator designed. Furthermore, Figure 5(b) shows that the flux linkage is higher for the new design than the existing generator, as the new design has higher per phase inductance than that of the existing generator. It should be noted that even though the flux is higher in the new generator design, the maximum flux density is less than that permissible for the core, i.e. 1.2 T. As shown in Table 2, the number of poles in the existing generator is 78 which has been reduced to less than half in the new design to 32 poles. Also, each pole volume is 600 × 260 × 100 mm3 in the new design, whereas, in the existing PMSG, each pole volume is 500 × 142 × 100 mm3. Thus, the total permanent magnet material is reduced by 9.8% in the new design. The reduction in the permanent magnet material reduces the dependency on the imported and highly unstable market of NdFeB materials.

ParameterExisting generatorDesigned (new) generator
No. of poles, p7832
Airgap flux density, Bmax1.01 T1.15 T
Winding current density, J4 A/mm26 A/mm2
Linear current density31.08 kA/m36.60 kA/m
Stator winding factor, kw0.9420.951
Stator q-axis inductance, Lq12.20 mH20.16 mH
Stator d-axis inductance, Ld12.19 mH20.11 mH
Stator inner diameter4462 mm3500 mm
Stack length500 mm600 mm
Number of slots23496
Winding turns per phase5630
Copper weight384.4 kg401.3 kg
Core weight (stator)21,552 kg19,429 kg
Rotor weight40,990 kg35,870 kg

Table 2.

Comparison of the designed vs. existing generator.

Figure 5.

Generator (a) line-to-line voltage, and (b) phase flux linkage vs. rotor electrical position obtained through FE computations for the existing and new design of the generators.

The FE measured linear current density for the new design is 36.6 kA/m at the pole surface, as shown in Table 2, while the NdFeB coercive force is 1910 kA/m. In Table 3, the demagnetization of PM poles is computed for different output power factors and the results are presented. The computation of demagnetization is done using the MagneForce FE software. The software calculates the total flux with virgin (non-demagnetized) magnets. It then runs the simulation and keeps track of the worst demagnetization that each element within the rotor pole experiences throughout a complete ac cycle. The FE software uses the demagnetized elements to re-construct the magnet, and then, calculates the total flux from this demagnetized magnet. Finally, the software calculates the percentage drop in total flux from the virgin magnets to the demagnetized magnets and reports the difference as the amount of demagnetization. It should be noted that the demagnetization analysis is based on loading of the generators and total flux drop, and it does not take into account the thermal models for the generators.

pf=0.950.850.75
Demagnetization (%)
Existing design0.0800.0750.078
New design0.0840.0800.081

Table 3.

Percent demagnetization of pm poles for varying output power factor and s = 1 p.u. using FE computations.

A normalized comparison of the copper and core losses, rotor and stator weights, and the volume of the two generators is presented in Figure 6. In Table 4, the efficiency, as well as core and copper losses, are provided for different power factors and a constant apparent power, i.e. S=1 p.u. The base values for the per-unit (p.u.) calculations are Sbase=1.5 MVA, and Vbase=690 V. As can be observed, the copper loss in the new generator increases. This is due to the higher current level in the low-voltage generator. Although the new design has lower number of turns in the generator winding – lower overall stator resistance – the line current is higher, which results in higher copper loss in the new low voltage generator. Nevertheless, the core loss for the designed low voltage generator decreases by about 9.5%. This reduction in the core loss in the new designed generator is due to the reduction in the number of poles in the new designed generator, which results in a substantial decrease in the generator output voltage and frequency, see Table 2. It can be observed that the generator efficiency is not compromised with full load efficiency of the new and existing generator being 94.4 and 93.8%, respectively, while the stator and rotor dimensions are significantly decreased. The no-load core-losses for the existing and new generator designs are computed to be 0.040 p.u. and 0.0351 p.u., respectively. The change in core losses from no-load to full load can be attributed to the armature reaction, see Table 4. It should be noted that the losses and efficiency data presented in in Table 4, and Figure 6 are obtained using the FE models of the PMSGs. A comparison of the rotor and stator weights, respectively, for the two generators is presented in Figure 6. The rotor weight is the cumulative weight of the NdFeB PM poles and the rotor core. Similarly, the stator weight presented in the combined weight of the armature windings and the stator core. The stator and rotor weight reductions for the new generator are ~9.4 and 12.5%, respectively. Additionally, the overall volume of the new generator is reduced by ~2.79% than the existing design. It can be observed that the decrease in the stator diameter (which is about 10%) does not render to a comparable reduction in the overall volume of the new generator. This is due to the higher stack length of the new generator. The designed generator has a stack length to diameter l/Dratio of 0.13 as compared to the existing generator design with l/Dratio of 0.11. The decrease in the generator volume and weight along with the elimination the failure prone dc-bus capacitor and circumventing the dc-link inductor needed in CSIs will further render into decreased capital cost of the overall system. The simulation and experimental results evaluating and validating the performance of the proposed topology of the DDWT are presented in the following sections.

Figure 6.

Comparison of normalized (a) copper loss, (b) core loss, (c) stator diameter, (d) rotor weight, (e) stator weight, and (f) volume of the existing and designed PM generator for DDWT using FE computation.

pf=0.950.850.75
Copper Loss (p.u.)Existing0.02450.02450.0250
New0.02680.02690.0278
Core Loss (p.u.)Existing0.04050.04050.0405
New0.03530.03540.0354
Efficiency (%)Existing93.5093.4993.45
New93.7993.7793.68

Table 4.

Core loss, copper loss, and efficiency for varying output power factor and S = 1 p.u. using FE computations.

4. System controls

In this section, first, the control technique implemented for the developed topology is briefly explained. The developed system is controlled with generator side VSC being modulated for power transfer to the grid and the boost inverter modulated to stabilize the input dc-voltage.

The power electronics interface proposed for the DDWT drivetrain is controlled to regulate the power injected to the grid and to maintain the average dc-side voltage. The generator side VSC is modulated to inject desired power to the dc-side. Figure 7 shows the block diagram of the controller for VSC. The generator line-to-line voltages and dc-side voltage and current are the measured feedback received by this controller. The ac side signals are then converted to the dqoreference frame. The desired active power on the grid side, Pis compared to the measured power on the dc side. The error is then mitigated by using a Proportional-Integral (PI) controller which then generates the desired q-axis converter voltage, VqVSC. The generated q- axis voltage and the measured d-axis voltages serve as base to generate the switching signal for the VSC. The controller is equipped with one of the existing MPPT techniques, e.g. P=KoptωR3, [36, 37].

Figure 7.

Block diagram of controller for the VSC [26].

Figure 8 shows the block diagram of the controller for the boost CSI. The controls for this converter help regulate the dc-side voltage and to modulate the reactive power injected into the grid. Thus, the controller for the VSC helps modulate the active power injected into the grid and the controller for the boost CSI modulates the reactive power into the grid. The inputs to the boost CSI controller are the measured grid-side line-to-line voltages, line currents and dc-side. The three-phase signals are converted to the dqoreference frame. The dqoquantities are used to compute the reactive power injected to the grid, which is compared to the reference reactive power. The error is then mitigated using a PI controller which generates the reference angle, θfor the boost inverter. Similarly, the dc-side voltage, Vdcwhere,Vdc=vdcis compared to the desired dc-side voltage, Vdcand a PI controller is used to generate the modulation index, Dfor the implementing the PPWM switching technique [26]. The details on the PPWM technique has been provided in [29, 30, 31].

Figure 8.

Block diagram of controller for the single-stage boost inverter [26].

5. Simulation results

This section presents the simulation results for the evaluation of the feasibility and performance of the developed topology of the DDWT. The software platform used for these evaluations is MATLAB/Simulink environment using SimPowerSystems toolbox. The simulated system uses the FE design of the generator as presented in Section 3. The switching frequency of 6 kHz is used for both the VSC and the boost CSI. The switching methodology for the VSC is the Sine PWM (SPWM) technique while the boost CSI employs the PPWM switching technique [29, 30]. As described in the previous section, the VSC controller modulates the active power transfer injected into the grid and the boost CSI controller regulates the dc-side voltage and controls the reactive power injected into the grid. A detailed discussion on these controllers and their performance is presented in [26]. The output filter parameters for the boost CSI are Cf=20μFand Lf=5mH.

The quality of the output waveforms of the proposed system is demonstrated in Figures 9 and 10. Figure 10 presents the steady-state waveforms of generator line-to-line voltage and line current when the generator speed is 18.75 rpm. The power converters were modulated to inject 1 MW (0.67 p.u.) P into the grid at unity power factor (UPF). The boost CSI controller was regulating the dc-side voltage at 500V. Figure 10(a) and (b) show that the THD of the generator output line current is ~1.2%, which further ensures less harmonics transferred to the generator side and eliminates the low-frequency torque ripple on the generator shaft. Figure 9 presents the waveforms of the boost CSI output line-to-line voltage at the point of common coupling, and line current injected into the grid. The grid line current THD is computed to be ~3.3%, which is complaint of the IEEE 1547–2018 interconnection standards [38].

Figure 9.

Simulated results of inverter output (a) line current waveform, (b) line current FFT analysis, (c) line-to-line voltage waveform, and (d) line-to-line voltage FFT analysis for grid-tied system the generator speed is 18.75 rpm and the system is injecting 0.67p.u. Active power into the grid [35].

Figure 10.

Simulated results of generator output (a) line current waveform, (b) line current FFT analysis, (c) line-to-line voltage waveform, and (c) line-to-line voltage FFT analysis, for grid-tied system when the generator speed is 18.75 rpm and it is supplying [35].

Figure 11 presents the dynamic behavior of the proposed DDWT system. The generator speed, three-phase line-to-line voltage waveforms at the point of common coupling (PCC), three-phase generator line current waveforms, and the dc-side current are shown in Figure 11. The first event occurs at t=1s, when the generator speed changes gradually from 7.5 rpm to 19.65 rpm. The sudden speed changes shown in Figure 11 are not realistic and is just used as a case to evaluate the robustness of the system controls. Figure 11(c) and (d) show that the system easily tracks the maximum available wind power. The fault ride-through capability of the system is also evaluated. This is done by simulating a three-phase low-voltage fault on the inverter terminals at t=2s, where the grid voltage decreases by 35% and the fault is cleared after 0.5s[39]. The developed system rides-through this low-voltage seamlessly and starts normal operation again in ~0.38safter the clearing of the fault.

Figure 11.

Plot of (a)PMSG speed, (b) three-phase line-to-line voltage at the PCC, (c) three-phase generator line current, and (d) dc-side current showing system behavior for varying wind speed and three-phase low-voltage fault at the grid [35].

6. Experimental evaluation results

The feasibility of the developed DDWT topology is evaluated using experimental results from 1.5 kW, 240VLL laboratory scale prototype, in this section (see Figure 12). In this setup, a motor-drive system is used as the wind turbine emulator that runs a commercially available PMSG, which feeds a three-phase 50Ωresistive load through the proposed back-to-back converter and a CL filter. The filter values are Cf= 20 μF and Lf= 5 mH, when fs= 6 kHz for the boost CSI. For the first test case to evaluate if the generator synchronous inductance can be utilized in place of the dc-link inductor, a diode bridge rectifier is used as the generator side. The waveforms of the generator line current, generator line-to-line voltage, load line current, and load line-to-line voltage are shown in Figure 13. The PMSG produces rms line-to-line voltage of 45 V at 30 Hz. This is boosted to an output load line-to-line voltage of 208 V at 60 Hz by the boost CSI. The generator current and load current THDs are measured to be 33.1 and 3.0%, respectively. For the next test case, the generator side converter employed is a VSC. Figure 14 shows the waveforms of the same quantities for this test case. The switching frequency for the VSC is fs= 25 kHz. The average dc side voltage was maintained at 70 V. The generator current and load current THDs are measured to be 2.9 and 2.8%, respectively The evaluation results presented in Figures 13 and 14 demonstrate the capability of the developed systems to utilize the generator synchronous inductance, while still maintain the quality of the system output.

Figure 12.

Laboratory scale 1.5 kW, setup for the proposed DDWT topology [35].

Figure 13.

Experimentally obtained waveforms of the (a) generator line current, (b) generator line-to-line voltage, (c) load line current, and (d) load line-to-line voltage when the generator is rotating at 450 rpm (30 Hz), the output is regulated at 208 V, and the generator side converter is a diode bridge rectifier [35].

Figure 14.

Experimentally obtained waveforms of the (a) generator line current, (b) generator line-to-line voltage, (c) load line current, and (d) load line-to-line voltage when the generator is rotating at 450 rpm (30 Hz) and the output is regulated at 208 V with the generator side converter as VSC [35].

7. Conclusion

In this chapter, an inductorless generator-converter topology has been presented for DDWTs. This paper also presents a new topology of power electronics interface for the DDWTs. The grid side VSC used in a conventional DDWT has been replaced by a boost CSI. The dc-link inductor inherently required in a CSI topology has been eliminated by using the synchronous inductance of the PMSG. This topology has further facilitated the elimination of vulnerable dc-bus electrolytic capacitors, thereby increasing the overall system reliability. Furthermore, less frequent failures of the capacitors will lead to increase in system availability, resulting in substantial decrease in the maintenance costs. In this chapter, FE analysis is used to design and evaluated a 1.5 MW generator for the proposed system. The FE analysis is also used to compare the designed and an actual generator. The advantages of using the proposed topology have been demonstrated through reduction in generator weight, volume, and amount of PM material. The controls for the proposed system have also been discussed in this chapter. The feasibility and performance of the proposed DDWT system has been validated through simulation results and experimental results from a laboratory scale prototype, in this chapter.

How to cite and reference

Link to this chapter Copy to clipboard

Cite this chapter Copy to clipboard

Akanksha Singh (June 27th 2019). Development and Control of Generator-Converter Topology for Direct-Drive Wind Turbines, Rotating Machinery, Getu Hailu, IntechOpen, DOI: 10.5772/intechopen.85877. Available from:

chapter statistics

162total chapter downloads

More statistics for editors and authors

Login to your personal dashboard for more detailed statistics on your publications.

Access personal reporting

Related Content

This Book

Next chapter

Methodology for Abrasive Wear Evaluation in Elevator Stage Centrifugal Pump Impellers

By Rodrigo O.P. Serrano, José G. do V. Moreira, Ana L.P. de Castro, Maria A. Pinto, Edna M. de F. Viana and Carlos B. Martinez

Related Book

First chapter

Introductory Chapter: Path to Net Zero Energy Buildings

By Getu Hailu

We are IntechOpen, the world's leading publisher of Open Access books. Built by scientists, for scientists. Our readership spans scientists, professors, researchers, librarians, and students, as well as business professionals. We share our knowledge and peer-reveiwed research papers with libraries, scientific and engineering societies, and also work with corporate R&D departments and government entities.