Wavelet–Neural–Network Control for Maximization of Energy Capture in Grid Connected Variable Speed Wind Driven Self- Excited Induction Generator System

By Fayez F. M. El-Sousy and Awad Kh. Al-Asmari

Submitted: April 16th 2012Reviewed: July 3rd 2012Published: February 6th 2013

DOI: 10.5772/51253

Downloaded: 1999

1. Introduction

Recently, the wind generation systems are attracting attention as a clean and safe renewable energy source. Induction machines have many advantageous characteristics such as high robustness, reliability and low cost. Therefore, induction machines are used in high-performance applications, which require independent torque and flux control. The induction machines may be used as a motor or a generator. Self-excited induction generators (SEIG) are good candidates for wind-power electricity generation especially in remote areas, because they do not need an external power supplies to produce the excitation magnetic fields in [1–3]. The excitation can be provided by a capacitor bank connected to the stator windings of the induction generator. Magnetizing inductance is the main factor for voltage build-up of the IG. The minimum and maximum values of capacitance required for self-excitation have been analyzed previously in [47].

The three phase current regulated pulse-width modulation (CRPWM) AC/DC/AC converters have been increasingly used for wind energy system applications. Their attractive features include: regulated DC-link voltage, low harmonic distortion of the induction generator currents and controllable power factor and efficiency in [89]. The current regulation of a SEIG in the synchronous frame has the advantages of fast dynamic current response, good accuracy, constant switching frequency and less sensitivity to parameter variations. In wind generation systems, a variable speed generation system is more attractive than a fixed speed one because of the improvement in the wind energy production. In a variable speed system, wind turbine can be operated to produce its maximum power at every wind speed by adjusting the shaft speed optimally. In order to achieve the maximum power point tracking (MPPT) control, some control schemes have been studied. For example, a search-based or perturbation-based strategy in [10–11], a fuzzy- logic based control in [12], a wind speed-estimation-based algorithm has been applied. Since the squirrel-cage IGs have robust construction, lower initial, run-time and maintenance cost, squirrel-cage IGs are suitable for grid-connected as well as isolated power sources in small hydroelectric and wind-energy applications. Therefore an IG system using radial basis function network (RBFN) was proposed to yield maximum power output through the DC-link power control in [13-14].

In the past several years, much research has been carried out in neural network control. It has proven that an artificial neural network can approximate a wide range of nonlinear functions to any desired degree of accuracy under certain conditions. In the conventional gradient descent method of weight adaptation, the sensitivity of the controlled system is required in the on-line training process. However, it is difficult to acquire sensitivity information for unknown or highly non-linear dynamics. Wavelets have been combined with the neural network to create wavelet–neural–networks (WNNs). It combine the capability of artificial neural networks for learning from process and the capability of wavelet decomposition for identification and control of dynamic systems. The training algorithms for WNN typically converge in a smaller number of iterations than the conventional neural networks. Unlike the sigmoid functions used in the conventional neural networks, the second layer of WNN is a wavelet form, in which the translation and dilation parameters are included. Thus, WNN has been proved to be better than the other neural networks in that the structure can provide more potential to enrich the mapping relationship between inputs and outputs in [15-23].

Particle swarm optimization (PSO), first introduced by Kennedy and Eberhart in [24], is one of the modern heuristic algorithm. It was developed through simulation of a simplified social system and has been found to be robust in solving continuous nonlinear optimization problem in [25-29]. The PSO technique can generate a high quality solution within shorter calculation time and stable convergence characteristics than other stochastic methods in [30-34]. Much research is still in progress for proving the potential of the PSO in solving complex dynamical systems.

The recent evolution of power-electronics technologies has aided the advancement of variable-speed wind-turbine generation systems in [3539]. In spite of the additional cost of power electronics and control circuits, the total energy captured in a variable-speed wind-turbine system is more than the conventional one. Thus, the variable-speed wind-turbine system has lower life-cycle cost. Moreover, the PWM converters not only can be used as a variable capacitor but also can supply the needed reactive power to load and to minimize the harmonic current and imbalance in the generator current. On the other hand, the variable speed wind turbine driven SEIG systems display highly resonant, nonlinear, and time-varying dynamics subject to wind turbulence and operating temperature of the SEIG. Furthermore, there is an appreciable amount of fluctuation in the magnitude and frequency of the generator terminal voltage owing to a varying rotor speed governed by the wind velocity and the pulsating input torque from the wind turbine. The phenomena of fluctuation are objectionable to some sensitive loads. Therefore, the employment of PWM converters with advanced control methodologies to control the wind turbine driven SEIG systems is necessary in [3638]. In addition, for the research of wind energy conversion systems, the developments of wind turbine emulators are also necessary in [43, 44]. However, the fuzzy logic controller, the sliding-mode controller, and the PI controller adopted in [4048] may not guarantee the robustness when parameter variations or external disturbance occurred in the control system in practical applications due to the lack of online learning ability.

This Chapter is organized as follows. Section 2 presents the variable speed wind generation system description. In this section the analysis of the wind turbine is carried out and the maximum power point tracking analysis is also introduced. In Section 3, the dynamic model of the self-excited induction generator is introduced to analyze all its characteristics. Section 4 provides the indirect field-orientation control (IFOC) dynamics for the IG (torque, slip angular frequency and voltage commands) which are derived from the dynamic model of SEIG. The d-q axes current control according to the IG rotor speed gives the maximum mechanical power from the wind turbine and the losses of the IG are minimized. In Section 5, the dynamic equations of the CRPWM converter in the synchronous reference frame are carried out based on the IFOC dynamics of the IG. The dynamic equations of the grid-side CRPWM voltage source inverter connected to the grid are given in Section 6. By using vector control technique, the currents of the CRPWM inverter are controlled with very high bandwidth. The vector control approach is used, with a reference frame oriented along the grid voltage vector position. This allows independent control of the active and reactive power. Section 7 considers the design procedures for the PID voltage controller of the IG-side CRPWM voltage source converter, the PID active power and reactive power controllers for the grid-side CRPWM inverter. In Section 8, an intelligent maximization hybrid control system based on the WNN with IPSO is proposed in order to control the DC-link voltage of the IG-side CRPWM voltage source converter, active power and reactive power of the grid-side CRPWM voltage source inverter effectively based on the MPPT from the wind driven SEIG system. Finally, to testify the design of the proposed hybrid control system and MPPT control scheme, the variable speed wind generation system is simulated in Section 9. The dynamic performance of the system has been studied under different wind velocities. The simulation results are provided to demonstrate the effectiveness of the proposed hybrid control for variable speed wind generation system.

2. Variable Speed Wind Generation System Description

The proposed wind generation system is shown in Figure 1. The wind turbine is coupled to the shaft of a SEIG. The output of the SEIG is connected to a double-sided CRPWM voltage source converter connected to a utility grid.

2.1. Double-Sided Converter System

The voltage-fed double-sided converter scheme used in the proposed wind energy conversion system is shown in Figure 1. The variable frequency variable voltage power genertated is rectified by a PWM converter. The PWM inverter topology is identical to that of the PWM converter and it supplies the generated power to the utility grid. The converter consists of six switches with their anti-parallel diodes that are switched using space vector pulse width modulation (SVPWM) pattern. The switching functions of the top and bottom devices are defined S a , S b and S c ; and S a ' , S b ' and S c ' respectively. The switching function has a value of one when the switch is turned on and it is zero when it is turned off. The voltage equations for the converter in the stationary reference frame can be expressed in terms of the switching functions as given by (1-3).

Va=13Vdc[2SaSbSc]E1
Vb=13Vdc[Sa+2SbSc]E2
Vc=13Vdc[SaSb+2Sc]E3

2.2. Analysis of Wind Turbine

The wind turbine driven SEIG system has the following parameters. The Wind turbine parameters are P m =1.5 kW at V ω =16m/s, turbine radius R T =0.7m and λ opt =6.5 while the IG parameters are P e =1.5 kW, V=380 V, I s =4 A, number of poles P=4, f=50 Hz, R s =6.29Ω, R r = 3.59Ω, L s =L r =480 mH, L m =464 mH and the total moment of inertia of the wind turbine and the IG J=2 kg. m2.

The wind turbine is characterized by the non-dimensional curve of coefficient of performance as a function of tip-speed ratio λ. The mechanical input power P m of a fixed-pitch wind turbine as a function of the effective wind velocity V ω through the blades, the air density, ρ, the blades radius R T and the power coefficient C P is given in [9, 12]:

PmT=12ρπRT2Vω3CP(λ)E4

Considering the rotational speed of the wind turbine ω t and the torque coefficient C T (λ), the wind turbine mechanical torque is given by:

TmT=12ρπRT3Vω2CT(λ)E5
CP(λ)=λCT(λ)E6

where C P (λ) is the turbine power coefficient, C T (λ) is the turbine torque coefficient, V ω is the wind velocity (in m/s), ρ is the air density (typically 1.25 kg/m3), R T is the blades radius (in m) and λ is tip-speed ratio and is defined as:

λ=ωTRT/VωE7

where ω T is the wind turbine rotational speed (rad/s).

Figure 1.

Intelligent maximization control of a variable speed wind driven self-excited induction generator system connected to a utility grid.

The turbine power coefficient C P (λ) and the turbine torque coefficient C T (λ) are functions of the tip-speed ratio of the blades if the pitch angle of the blade is constant. The turbine power coefficient is represented by various approximation expressions. In this Chapter, C P ) and C T (λ) are approximated by a fifth-order polynomial curve fit given by (8-9) and are shown in Figures (2 and 3). The power and torque versus speed curves of wind turbine can be calculated by (4)-(7) at various wind velocities. The optimum point corresponds to the condition where the power coefficient C P (λ) becomes the maximum. The maximum C P is 0.37 when λ=6.7.

CP(λ)=0.0084948+0.05186λ0.022818λ2+0.01191λ30.0017641λ4+7.484x105λ5E8
CT(λ)=0.00066294+0.0091889λ0.0026952λ2+0.001688λ30.00028374λ4+1.3269x105λ5E9

2.3. Maximum Power Point Tracking Analysis

When the tip speed ratio is controlled by the optimum value regardless of the wind speed, the maximum mechanical power is obtained from the wind turbine. The optimum speed of the IG for maximum power of the wind turbine is given by (10) and the maximum mechanical power and the optimal torque are given by (11) and (12).

ωopt=KωoptVωE10
PTmmax=KpmaxVVω3E11
TTmopt=KToptVVω2E12
KpmaxV=12ρπRT2Cp,maxE13
KToptV=12ρπRT3Cp,max/λoptE14
Kωopt=λopt/RTE15
Kpmaxω=KpmaxV/(Kωopt)3E16
KToptω=KToptV/(Kωopt)2E17
PTmmax=Kpmaxωωopt3E18
TTmopt=KToptωωopt2E19

When the IG speed is always controlled at the optimum speed given in (10), the tip-speed ratio remains the optimum value and the maximum power point can be achieved. At any wind speed, we can calculate the optimum rotational speed of the IG from (10), and then the maximum mechanical power is calculated from (11). The maximum power is used as the reference power to the CRPWM converter in order to get the maximum load current.

From (10)-(17), the maximum power and optimal torque as function of the optimum rotational IG speed are calculated and given by (18)-(19). From Figure 4, it is clear that the maximum power can be achieved when the IG torque is controlled on the optimal torque curve according to the IG rotor speed.

TIGopt=KToptωIGωr2E20
KToptωIG=KToptV/G.(Kωopt)2E21

3. Dynamic Model of the Self-Excited Induction Generator

The dynamic model of the IG is helpful to analyze all its characteristics. The d-q model in the arbitrary reference frame provides the complete solution for dynamic analysis and control in [2-4]. The dynamic model is given by (22-24, 25).

[0000]=[(Rs+Lsσddt)ωLsσLmLrddtLmLrωωLsσ(Rs+Lsσddt)ωLmLrLmLrddtLmLrRr0(Rr/Lr+ddt)(ωωr)0LmLrRr(ωωr)(Rr/Lr+ddt)][iqsidsλqrλdr]+[VqsVdsVqrVdr]E22
Vqs=1Ciqsdt+Vcq|t=0E23
Vds=1Cidsdt+Vcd|t=0E24
Te=32P2LmLr(λdriqsλqrids)E25

where, V qs , V ds , i qs , and i ds are the stator voltages and currents, respectively. v qr and v dr are the rotor voltages. λ qr and λ dr are the rotor fluxes. R s , L s , R r and L r are the resistance and the self inductance of the stator and the rotor, respectively. L m is the mutual inductance.

Figure 2.

Power coefficient versus tip speed ratio.

Figure 3.

Torque coefficient versus tip speed ratio.

The relation between the wind turbine output torque and the electromagnetic torque of the IG is given by (26).

TTm=Jddtωm+βωm+TeE26

From (22-26), the state equations of the SEIG and wind turbine can be accomplished as in (27) and (28).

ddtωm=1JTTmβJωm1JTeE27

Figure 4.

Characteristics of wind turbine at various wind speeds.

ddt[iqsidsλqrλdr]=1σLsLr[(RsLr+RrLm2/Lr)ωσLsLr(Lm/Lr)RrωrLmωσLsLr(RsLr+RrLm2/Lr)ωrLm(Lm /Lr)RrσLsLrLmRr/Lr0σLsLrR/rLr σLsLr(ωωr)0σLsLrLmRr/LrσLsLr(ωωr)σLsLrRr/Lr][iqsidsλqrλdr]+1σLsLr[LmvqrLrvqsLmvdrLrvds   σLsLrvqr   σLsLrvdr]E28

where ω m , J and β are the mechanical angular speeds of the wind turbine, the effective inertia of the wind turbine, the induction generator and the friction coefficient, respectively.

In order to model the induction machine when used for motoring application, it is important to determine the magnetizing inductance at rated voltage. In the SEIG, the variation of magnetizing inductance L m is the main factor in the dynamics of voltage buildup and stabilization. In this investigation, the magnetizing inductance is calculated by driving the induction machine at synchronous speed and taking measurements when the applied voltage was varied from zero to 100% of the rated voltage. The magnetizing inductance used in this experimental setup is given as shown in Figure 5. The test results are based on the rated frequency (50 Hz) of the IG while the dots are experimental results and the curve is a fifth-order curve fit given by

Lm=1.023×10-11Vph5+6.162×10-9Vph41.25×10-6Vph3+8.267×10-5Vph23.843×105Vph+0.1985

where V ph is the phase voltage.

Figure 5.

Magnetic curve of the SEIG.

4. Optimal IFOC of the Induction Generator

The IFOC dynamics for the IG can be derived from (22-25), respectively at λ qr =0, qr /dt=0, dr /dt=0, and ω=ω e . The torque and slip angular frequency for rotor field orientation are given in (26-27) while the voltage commands of the IFOC are given by (29-31) in [11, 12].

Te=Kt.idse*iqse*=KToptωIGωr2E29
ωsl=1τr.iqse*idse*E30
[Vqse*Vdse*]=[eqseedse][Rs+σLsddt           ωeσLsωeσLs         Rs+σLsddt][iqseidse]E31

where K t =(3/2)(P/2)(L m )2/L r is the torque constant, e e qs and e e ds are the back EMFs of the IG. T e , τ r , ω sl , and ω e are the electromagnetic torque, the rotor time constant, the slip angular frequency, and the angular frequency of the synchronous reference frame, respectively.

[eqseedse]=[ωeλdreLmLr       0]E32

In the previous analysis, the IG torque is given by (29) as a function of the rotor speed. Therefore, the d-axes current becomes a function only of the rotor speed. The optimal d-q axes currents i ds and i qs can be derived from (22) and (29) and are plotted as given in Figure 6. These plots show the relation of the optimal currents as function of the IG rotor speed and can be approximated by a third-order polynomials given by (34, 35).

idse(ωr)iqse(ωr)=(KToptω/Kt)ωr2E33
idseopt(ωr)=Kd3ωr3+Kd2ωr2+Kd1ωr+Kd0E34
iqseopt(ωr)=Kq3ωr3+Kq2ωr2+Kq1ωr+Kq0E35

By controlling the d-q axes currents utilizing (34)-(35) according to the IG rotor speed, the maximum mechanical power is obtained from the wind turbine and the losses of the IG are minimized. Also, from (29), it is clear that the IG torque is proportional to the q-axis current when the d-axis current is kept constant and thus he IG power is almost proportional to q-axis current. Therefore, the control of generated power becomes possible by adjusting the q-axis current according to the required generated power, where the d-axis current is given by (34).

5. Dynamic Model of the IG-Side CRPWM Voltage Source Converter

The block diagram of the CRPWM voltage source converter control system based on the IFOC-SEIG is shown in Figure 8. It is well known that the IFOC of induction machines allows for the independent control of two input variables, stator q-axis current i e qs and stator d-axis current i e ds . This suggests that it is possible to control the output voltage and power factor and/or efficiency by controlling the two components of the stator currents. The dynamic equations of the CRPWM converter are based on the IFOC dynamics of the IG in [12-14] and are given by (36, 37).

eqseVqsec=Rsiqsec+σLsddtiqsec+ ωeσLsidsec E36
edseVdsec=Rsidsec+σLsddtidsec ωeσLsiqsec E37

By considering the converter as an ideal current regulated source, the energy is transferred between the IG and the DC-link. As a consequence, the instantaneous power of both the converter’s AC-side and DC-side is the same.

Vdcidc=32(Vqseiqse+Vdseidse)E38

From (38), the relation between the DC-link current i dc and the d-q axis currents i e qs and i e ds is as follows.

idc=32(VqseVdciqse+VdseVdcidse)E39

At FOC V e ds 0, therefore, there is a direct relation between the DC-link current and the q-axis current of the IG.

iqse=23VdcVqseidcE40

The dynamics of the DC-link is given by (41-43).

CdcddtVdc+iL=idcE41
CdcddtVdc+1RLVdc=idcE42
idc=32VqseVdciqseE43

where, C dc is the DC-link capacitor, i L is the load current and i dc is the DC-link current. The state equations of the CRPWM converter and DC-link are derived from (36-43) and are given in (44-45).

ddtVdc=[1Cdc      1RLCdc][idcVdc]E44
ddt[iqsecidsecVdc]=1σLs[Rs            ωeσLs      0ωeσLs         Rs         0σLsKdcq      σLsKdcd     0][iqsecidsecVdc]                 +1σLs[σLs      0           00        σLs         00           0      σLs][eqseVqsecedseVdsec      iL]E45

Figure 6.

Optimal d-q axes currents as a function of IG rotor speed.

From (45), the current in q-axis iqsecan be estimated as:

iqse=An1[V˙dcBniLCEnqdse]E46

where, An=[Kdcq+Kdcd/τr.ωsl], Bn=[1/Cdc], Cn=[1/Cdc]and Eqdse=[eqse*Vqse*   edse*Vdse*].

At the steady state, the load current i L is approximately equals to the DC-link current i dc . Therefore, the optimal load current can be approximated by (47). Figure 7 shows the optimal load current corresponding to the maximum mechanical power obtained from the wind turbine.

iLopt(ωr)=KL3ωr3+KL2ωr2+KL1ωr+KL0E47

Figure 7.

Optimal load current as a function of IG rotor speed.

6. Dynamic Model of the Grid-Side CRPWM Voltage Source Inverter

The grid-side CRPWM voltage source inverter is connected to the grid through three single-phase coils (control windings). With this configuration it is possible to operate using boost mode and have attractive features as constant DC–link voltage, low harmonic distortion of grid current, bidirectional power flow and adjustable power factor. The aim of the control of the grid-side CRPWM voltage source converter is to impose a current to the control winding and to control independently the active and reactive power to be injected to the grid. By using vector control technique, the currents of the CRPWM inverter are controlled with very high bandwidth. The vector control approach is used, with a reference frame oriented along the grid voltage vector position, such that V qg =V mg and V dg =0. This allows independent control of the active and reactive power through currents i qg and i dg respectively. Usually, the reactive power component current is set to zero for unity power factor operation. The primary aim of this control scheme is to modulate the inverter to regulate the magnitude and the phase angle of the grid supply current, so that the active and reactive power entering the network can be controlled. The procedure for modeling the CRPWM inverter is based on the virtual-flux orientation control (VFOC) technique. The grid-side converter control, shown in Figure 9, is based on the d–q voltage equations of the grid-reactance-converter system according to following equations:

[Vqeg*Vdeg*]=[eqegedeg]+[Rg+Lgp        ωegLgωegLg         Rg+Lgp][iqegideg]E48
[PQ]=32.[Vqeg      VdegVdeg    Vqeg][iqeg  ideg  ]E49

The vector control of the grid-side CRPWM inverter is represented in the block diagram illustrated in Figure 9. The control of the reactive power is realized by acting over the control winding current, i ds . The reference current is obtained by a PI current controller that adjusts the reactive power to a desired amount. Similarly, the control of the active power is realized by acting over the control winding current i qs and the reference current is given by a PI current controller. The possible situation for defining the current references is to track the maximum turbine power for each wind speed.

At VFOC, V dg =0. Therefore, there are a direct relations between the active power, P and q–axis current and the reactive power, Q and d–axis current of the control windings. This allows independent control of the active and reactive power through currents i qg and i dg respectively according to following equations:

[PQ]=32.[+Vqeg       00        Vqeg][iqeg  ideg  ]E50

The d-q current commands of the inverter are expressed as:

[iqeg*ideg*]=23[ +P*Vqeg*Q*Vqeg*]E51

where, P * and Q * denote the required maximum active and reactive power. To achieve the unity power factor operation, Q * must be zero. From (50), it is obvious that the current command of the d–axis must be zero for unity power factor operation and the current command of the q–axis can be evaluated from the required active power. It is seen from (47) that coupling terms exist in the d-q current control loops. The d–q voltage decouplers are designed to decouple the current control loops. Suitable feed-forward control components of grid voltages are also added to speed up current responses. The d-q current control loops of the CRPWM inverter in the proposed control system are shown in Figure 9.

7. Design of the PID Controllers for Double-Sided CRPWM AC/DC/AC Voltage Source Converters

This section considers the design procedures for the PID voltage controller of the IG-Side CRPWM voltage source converter, the PID active power and reactive power controllers for the grid-side CRPWM inverter. The design procedures are based on the integral time absolute error (ITAE) performance index response method to obtain the desired control performance in the nominal condition of command tracking.

7.1. PID Voltage Controller Design for IG-Side CRPWM Voltage Source Converter

A systematic design procedure for the PI current controllers capable of satisfying the desired specifications is given in [12]. The gains of the PI d-q axis current controllers have been determined using the ITAE performance index response method and are given by (51-52). From the block diagram shown in Figure 8, a back EMF estimator is adopted to q-axis current loop for voltage feed-forward control. The q-axis stator current of the IG is selected as the variable to be changed to regulate the DC-link voltage. The voltage control is carried out through a voltage control loop using a PID voltage controller and is designed to stabilize the voltage control loop. The gains of the PID controller have been determined using the ITAE performance index response method. By exercising the decoupling control, the dynamic model including the CRPWM converter and the IG can be simplified and the closed loop transfer function is given by (53) from Figure 7.

Kicq=ωn2σLsKpcq=(1.4ωnσLsRsTq)E52
Kicd=ωn2σLsKpcd=(1.4ωnσLsRsTd)E53
Vdc(s)Vdc*(s)|iL=0=a3s3+a2s2+a1s+a0s4+b3s3+b2s2+b1s+b0                   ωn4s4+2.1ωns3+3.4ωn2s2+2.7ωn3s+ωn4E54

The PID voltage controller parameters are given by (54-56).

KPv=1Kdc.σLsKicq(2.7ωn3KpcqKicq.ωn4)E55
Kiv=1Kdc.σLsKicq.ωn4E56
Kdv=1Kdc.σLsKicq.(ωn4.KpcqKicq2.7ωn3.KpcqKicq+3.4ωn2KicqσLs)E57

7.2. PID Active Power Controller Design for Grid-Side CRPWM Voltage Source Inverter

A systematic design procedure for the PI current controllers is given in [12]. These controllers are designed based on the control windings dynamic model at VFOC. The gains of the PI d-q axis current controllers have been determined and are given by (57-58). The q-axis current of the control winding is selected as the variable to be changed to regulate the active power, P. The active power control is carried out through a power control loop using a PID controller and is designed to stabilize the active power control loop. The gains of the PID controller have been determined using the ITAE method. The block diagram of the active power control loop is shown in Figure 9. The closed loop transfer function of the active power control loop is given by (59).

Kigq=ωn2LgKpgq=(1.4ωnLgRg)E58
Kigd=ωn2LgKpgd=(1.4ωnLgRg)E59
Pqeg(s)PmaxT*(s)|VFOC=c3Ps3+c2Ps2+c1Ps+c0Ps3+d2Ps2+d1Ps+d0P ωn3s3+1.75ωns2+2.15ωn2s+ωn3E60

The PID controller parameters are given by (60-62).

KdP=(1.75ωnLgKiqgRgKiqg2.15ωn2LgKpqg)(KqPKi2qg+2.15ωn2KqPKp2qg1.75ωnKqPKpqg)E61
KpP=(2.15ωn2LgKqPKiqg)1KqP+(2.15ωn2KpqgKiqg).KdPE62
KiP=(ωn3LgKqPKiqg)+(KpqgKiqg).KdPE63

7.3. PID Reactive Power Controller Design for Grid-Side CRPWM Voltage Source Inverter

Similarly, the PID reactive power controller is designed and analyzed. The d-axis current of the control winding is selected as the variable to be used to regulate the reactive power, Q. The block diagram of the reactive power control loop is shown in Figure 9. The closed loop transfer function of the reactive power control loop is given by:

Qdeg(s)QmaxT*(s)|VOC=c3Qs3+c2Qs2+c1Qs+c0Qs3+d2Qs2+d1Qs+d0Q ωn3s3+1.75ωns2+2.15ωn2s+ωn3E64

The PID controller parameters are given by (64-66).

KdQ=(1.75ωnLgKidgRgKidg2.15ωn2LgKpqg)(KqQKi2dg+2.15ωn2KqQKp2dg1.75ωnKqQKpdg)E65
KpQ=(2.15ωn2LgKqQKidg)1KqQ+(2.15ωn2KpdgKidg).KdQE66
KiQ=(ωn3LgKqQKidg)+(KpdgKidg).KdQE67

8. Intelligent Maximization Control for Double-Sided CRPWM AC/DC/AC Voltage Source Converters

8.1. Configuration of the Proposed Intelligent Maximization Control System

In order to control the DC-link voltage of the IG-side CRPWM voltage source converter, active power and reactive power of the grid-side CRPWM voltage source inverter effectively, an intelligent maximization hybrid control system is proposed. The configuration of the proposed hybrid control system, which combines an on-line trained wavelet-neural-network controller (WNNC) with IPSO and a PID compensator, for wind turbine generation system is illustrated in Figures (8 and 9). It basically consists of an PI current controllers in the d-q axis, a three PID controllers and three on-line trained WNNCs with IPSO in parallel with the three PID controllers for voltage control of the DC-link side of the CRPWM converter, active power and reactive power of the grid connected CRPWM inverter. Although the desired tracking and regulation characteristics for DC-link voltage, active power and reactive power can be obtained using the PID controllers with nominal parameters, the performance of the system is still sensitive to parameter variations. To solve this problem, a hybrid controller combining the PID controller and the WNNC with IPSO is proposed for the DC-link voltage, active power and reactive power for the double-sided CRPWM AC/DC/AC converters. The control law and error signals are designed as:

Uqs*=Uqs*WNNC+Uqs*PIDE68
iqse*=δiqse*WNNC+iqse*PIDE69
idse*=δidse*WNNC+idse*PIDE70
ev=(Vdc*Vdc)V˙dc=kvdVdc/dtE71
eP=(P*P)P˙=kPdP/dtE72
eQ=(Q*Q)Q˙=kQdQ/dtE73

where iqse*PIDis the q-axis current command generated from the PID controller and δiqse*WNNCis produced by the proposed WNNC with IPSO to automatically compensate for performance degradation.

iqse*PID=iqseg*PIDfor CRPWM inverter, iqse*PID=iqse*PIDfor CRPWM converter, idse*PID=idseg*PIDfor CRPWM inverter,δiqse*WNNC=δiqseg*WNNCfor CRPWM inverter, δiqse*WNNC=δiqse*WNNCfor CRPWM converter, idse*WNNC=idseg*WNNCfor CRPWM inverter, P*=PmaxT*for CRPWM inverter, Q*=QmaxT*for CRPWM inverter.

8.2. Wavelet–Neural–Network Controller with IPSO

Since the squirrel-cage IGs have robust construction and lower initial, run time and maintenance cost squirrel-cage IGs are suitable for grid-connected in wind-energy applications. Therefore, a WNNC with IPSO is proposed to control a SEIG system for grid-connected wind-energy power application. The on-line trained WNNC with IPSO combines the capability of artificial neural-network for learning ability and the capability of wavelet decomposition for identification ability. Three on-line trained WNNCs with IPSO are introduced as the regulating controllers for both the DC-link voltage of the CRPWM AC/DC converter, active and reactive power of the CRPWM DC/AC grid-connected inverter. In addition, the on-line training algorithm based on the backpropagation is derived to train the connective weights, translations and dilations in the WNNs on-line. Furthermore, an IPSO is adopted to optimize the learning rates to further improve the on-line learning capability of the WNN and hence the improvement of the control performance can be obtained.

8.3. Wavelet–Neural–Network Structure

The architecture of the proposed four-layers WNN in [15-23] is shown in Figure 10, which comprises an input layer (the i layer), a mother wavelet layer (the j layer), a wavelet layer (the k layer) and an output layer (the o layer), is adopted to implement the WNNC. The signal propagation and the basic function in each layer are introduced as follows.

  1. Layer 1: Input Layer

The nodes in layer 1 transmit the input signals to the next layer. The input variables are the error signal, e(t), and the rate of change of the DC-link voltage, active power and reactive power. For every node i in the input layer, the input and the output of the WNN can be represented as:

neti1=xi1,yi1=fi1(neti1) =neti1  i=1,2E74
x11=e(t)andx21=ψ(t)E75

where e(t)=ev(t)=(Vdc*Vdc)for the CRPWM converter, e(t)=eP(t)=(P*P), e(t)=eQ(t)=(Q*Q), ψ(t)=V˙dc, ψ(t)=P˙, for the CRPWM inverter.

  1. Layer 2: Mother Wavelet Layer

A family of wavelets is constructed by translations and dilations performed on the mother wavelet. In the mother wavelet layer each node performs a wavelet ϕ j that is derived from its mother wavelet. There are many kind of wavelets that can be used in WNN. In this Chapter, the first derivative of the Gaussian wavelet function φ(x)=xexp(x2/2), is adopted as a mother wavelet. For the jth node

netj2=(xi2μij)/σij,yj2=fj2(netj2) =φj(netj2)j=1,...,nE76

where μ ij and σ ij are the translation and dilations in the jth term of the ith input xi2to the node of mother wavelet layer and n is the total number of the wavelets with respect to the input nodes.

  1. Layer 3: Wavelet Layer

Each node k in layer 3 (wavelet layer) is denoted by , which multiplies the incoming signal and outputs the result of the product. For the kth nodes:

netk3=jϖjk3xj3,yk3=fk3(netk3) =netk3    k=1,.......,mE77

Figure 8.

Integrated block diagram of the generator-side IFOC CRPWM voltage source converter using WNNC with IPSO control system.

where xj3represents the jth input to the node of the wavelet layer (layer 3), ϖjk3is the weights between the mother wavelet layer and the wavelet layer. These weights are also assumed to be unity; and m=(n/i)is the number of wavelets if each input node has the same mother wavelet nodes.

  1. Layer 4: Output Layer

The single node o in the output layer is denoted by , which computes the overall output as the summation of all incoming signals to obtain the final results.

neto4=kmϖko4xk4,yo4=fo4(neto4) =neto4 o=1E78
yo4=Uqs*WNNC(t)=δiqse*WNNC(t)E79

where the connecting weight ϖko4is the output action strength of the oth output associated with the kth wavelet and xk4represents the kth input to the node of output layer. The control problem is to design the WNNC to improve the convergence of the tracking error for the wind system.

Figure 9.

Integrated block diagram of the grid-side VFOC CRPWM voltage source inverter intelligent control system.

8.4. On-Line Training Algorithm Signal Analysis for WNNC

The essential part of the learning algorithm for an WNN concerns how to obtain a gradient vector in which each element in the learning algorithm is defined as the derivative of the energy function with respect to a parameter of the network using the chain rule. Since the gradient vector is calculated in the direction opposite to the flow of the output of each node, the method is generally referred to back-propagation learning rule in [15-23]. To describe the on-line learning algorithm of the WNNC using the supervised gradient descent method, the energy function is chosen as:

E=(1/2)(e)2E80
In the output layer (layer 4), the error term to be propagated is calculated as:
δo4=Eneto4=Eyo4.yo4neto4 =Ee.eneto4=Ee.eψ.ψneto4E81

Figure 10.

Four-layer wavelet–neural–network (WNN) structure.

The weight is updated by the amount:

Δϖko4=ηvEϖko4 =[ηvEyo4.yo4neto4].neto4ϖko4 =ηvδo4xk4E82

where η v is the learning rate parameter of the connecting weights of the output layer of the WNNC and will be optimized by the IPSO.

The weights of the output layer (layer 4) are updated according to the following equation.

ϖko4(N+1)=ϖko4(N)+Δϖko4=ϖko4(N)+ηvδo4xk4E83

where N denotes the number of iterations.

In wavelet layer (layer 3), only the error term needs to be computed and propagated because the weights in this layer are unity.

δk3=Enetk3=(Eyo4.yo4neto4).(neto4yk3.yk3netk3)=δo4ϖko4E84

In the mother wavelet layer (layer 2), the multiplication operation is done. The error term is calculated as follows:

δj2=Enetj2 =(Eyo4.yo4neto4.neto4yk3.yk3netk3).(netk3yj2.yj2netj2)=kδk3yk3E85

The update law of μ ij is given by:

Δμij=ημEvμij =[ημEyj2.yj2netj2.netj2μij ]=ημδj22(xi2μij)2(σij)2E86

The update law of σ ij is given by:

Δσij=ησEvμij =[ησEyj2.yj2netj2.netj2σij ]=ησδj22(xi2μij)2(σij)2E87

where η μ and η σ are the learning rate parameters of the translation and dilation of the mother wavelet which will be optimized by the IPSO. The translation and dilation of the mother wavelet are updated as follows:

μij(N+1)=μij(N)+ΔμijE88
σij(N+1)=σij(N)+ΔσijE89

To overcome the problem of uncertainties of the wind generation system due to parameter variations and to increase the on-line learning rate of the network parameters, a control law is proposed as follows.

δo4=e+kψE90

Moreover, the selection of the values for the learning rates η v , η μ and η σ has a significant effect on the network performance. In order to train the WNN effectively, three varied learning rates, which guarantee convergence of the tracking error based on the analyses of a discrete-type Lyapunov function, are adopted. The convergence analyses of the learning rates for assuring convergence of the tracking error is similar to [14] and is omitted here.

8.5. Improved Particle Swarm Optimization (IPSO)

In the PSO system, each particle adjusts its position according to its own experience and the experiences of neighbors, including the current velocity, position, and the best previous position experienced by itself and its neighbors. However, the efficiency of the PSO algorithm is affected by the randomly generated initial state. Therefore, the inertia weight Θ is adopted in the IPSO to balance between the local search ability and global search ability. Moreover, the inclusion of the worst experience component in the behavior of the particle in the IPSO gives additional exploration capacity to the swarm. Since the particle is made to remember its worst experience, it can explore the search space effectively to identify the promising solution region in [24]. Thus, the algorithm of the IPSO is derived as follows:

vid(k+1)=Θvid(k)+c1×r1×(Pbestidxid(k))+c2×r2×(Gbestidxid(k))+c3×r3×(Pworstidxid(k))E91
xid(k+1)=xid(k)+vid(k+1)E92

where vid(k)is the current velocity of ith particle, i = 1,..., P, in which P is the population size; the superscript d is the dimension of the particle; Pbestidis the best previous position of the ith particle; Pworstidis the worst previous position of the ith particle; Gbestidis the best previous position among all the particles in the swarm; xid(k)is the current position of the ith particle; c 1, c 2, and c 3 are the acceleration factors; and r 1, r 2 and r 3 represent the uniform random numbers between zero and one. In addition, the inertia weight Θ is set according to the following equation in [27]:

Θ=ΘmaxΘmaxΘminkmax×knE93

where k max is the maximum number of iterations and k n is the current number of iteration. Equation (92) restricts the value Θ to the range [Θmax, Θmin]. In this Chapter, the maximum and minimum values of the inertia weights are Θmax = 0.7 and Θmin = 0.4, respectively.

8.6. WNN Learning Rates Tuning Using IPSO

To further improve the online learning capability of the proposed WNN, the IPSO algorithm is adopted in this Chapter to adapt the learning rates ηvv, ημv, ησv, ηvP, ημP, ησP, ηvQ, ημQand ησQin the backpropagation learning methodology of the WNN. Moreover, the procedure of the IPSO algorithm is shown in Figure 11 and is described as follows.

Figure 11.

Flowchart implementation of the IPSO algorithm.

1) Initialization: Randomly generate the initial trial vectors xid(k), which indicate the possible solutions for the learning rates. Moreover, the population size is set to P = 15, and the dimension of the particle is set to d = 9 in this Chapter. This step is accomplished by setting xid=[xi0,xi1,xi2,xi3,xi4,xi5,xi6,xi7,xi8]represent the desired values of the learning rates ηvv, ημv, ησv, ηvP, ημP, ησP, ηvQ, ημQand ησQ, respectively. Furthermore, the elements in vector xidare randomly generated as follows:

xid~U[ηmind,ηmaxd]E94

where U[ηmind,ηmaxd]designates the outcome of a uniformly distributed random variable ranging over the given lower- and upper-bounded values η min and η max of the learning rate.

2) Determination of fitness function: For each trial vector xid, a fitness value should be assigned and evaluated. In this project, a suitable fitness function is selected to calculate the fitness value and defined as

FFIT=10.1+abs(Vdc*Vdc)+abs(P*P)+abs(Q*Q)E95

where F FIT is the fitness value and abs() is the absolute function; 0.1 is added in the dominant part to avoid the fitness value approaching infinite when the error of the DC-link voltage approaches zero.

3) Selection and memorization: Each particle xidmemorizes its own fitness value and chooses the maximum one that is the best so far as Pbestid, and the maximum vector in the population Pbest=[Pbset1d,Pbest2d,,Pbestpd]is obtained. Moreover, each particle xidis set directly to Pbestidin the first iteration, and the particle with the best fitness value among Pbestis set to be the global best Gbestd.

4) Modification of velocity and position: The modification of each particle is based on (90, 91).

5) Stopping rule: Repeat steps (1)–(4) until the best fitness value for Gbestis obviously improved or a set count of the generation is reached. The solution with the highest fitness value is chosen as the best learning rates of the WNN. By using the online tuning learning rates based on IPSO, the WNNC can regulate the DC-link voltage of the CRPWM AC/DC converter, active and reactive power of the CRPWM DC/AC inverter effectively.

In the IPSO, since the global best Gbestdhas higher priority than the local best Pbestidand local worst in the optimal algorithm, the acceleration factors are chosen to be c 1 = c 2 = 0.6 and c 3 = 3.10. Moreover, to achieve better global search ability for the IPSO, larger movement is required for the particle with the chosen larger inertia weight w in the beginning of the optimization process. Then, a smaller inertia weight Θ is required to improve the searching accuracy after several times of optimization. Furthermore, the inertia weight Θ must be less than one to avoid the divergence of the particle. Therefore, the maximum and minimum values of the inertia weights are chosen to be Θmax = 0.7 and Θmin = 0.4, respectively.

9. Numerical Simulation Results

In this section, a computer simulation results for the proposed wind generation system are provided to demonstrate the effectiveness of the proposed control schemes. The wind turbine SEIG system simulation is carried out using MATLAB/SIMULINK package. Since this Chapter is dealing with an isolated wind energy conversion system with maximum power control, the more realistic approach for an isolated wind power control system is to choose the DC-link voltage, active power and reactive power as the controlled variables.

Wind SpeedTip Speed Ratio λPower Coefficient CPReference Rotor Speed of WTEWind Turbine Output Power Pm (W)IG Output Power PIG (W)DC-Link Power PDC (W)
Vw =16 m/sec6.70.37≈ 296 rad/sec≈ 1580≈ 1500≈ 1400
Vw =14 m/sec6.70.37≈ 259 rad/sec≈ 1086≈ 1030≈ 965
Vw =12 m/sec6.70.37≈ 222 rad/sec≈ 705≈ 670≈ 637
Vw =10 m/sec6.70.37≈ 185 rad/sec≈ 422≈ 400≈ 392
Vw =8 m/sec6.70.37≈ 148 rad/sec≈235≈ 223≈ 212
Vw =6 m/sec6.70.37≈ 111 rad/sec≈ 110≈ 104≈ 95

Table 1.

Parameters of the wind turbine emulator (WTE) at various wind speeds.

Therefore, the DC-link voltage control, active power control and reactive power control using the PID controllers and WNNCs with IPSO are carried out for comparison. The dynamic performance of the wind generation system using double-sided CRPWM AC/DC/AC power converter system connected to utility grid subjected to three different wind speed variation profiles are shown in Figures (12-16). The first wind speed variation profile is the stepwise, the second is the sinusoidal variation profile and the last is the trapezoidal variation profile as given in the following section. The performance of the whole system at six operating conditions of wind speeds 6, 8, 10, 12, 14 and 16 m/sec is studied as shown in Table 1. The corresponding reference rotor speeds of the IG are 111, 148, 185, 222, 259 and 296 rad/sec, respectively. The respective wind turbine output power, DC-link power commands and IG output power are also shown in Table 1.

9.1. Wind Generation System Performance with CRPWM AC/DC/AC Converters Using Stepwise Wind Speed Profile

The dynamic response of the wind generation system feeding the double-sided CRPWM AC/DC/AC power converter connected to utility grid based on the maximum power point tracking (MPPT) control scheme using stepwise profile for wind speed variations of 10 m/s, 12 m/s, 14 m/s and 16 m/s are shown in Figures 12 and 13 utilizing both PID controller and WNNC with IPSO. These responses are the wind speed, rotor speed of the IG, the q-axis torque control current of the IG, the DC-link voltage V dc , the DC-link power P dc and the DC-link current i dc , respectively, for the CRPWM converter fed from the SEIG. Furthermore, the maximum active and reactive power injected to the grid at unity power factor, d-q axis currents, the phase voltage and currents, respectively, at the AC side of the CRPWM inverter connected to the utility grid. The dynamic responses of the wind speed, rotor speed of the IG, the q-axis torque control current of the IG, the DC-link voltage V dc , the DC-link power P dc and the DC-link current i dc , respectively, are shown in Figure (12-X) for both PID and WNNC with IPSO controllers for the CRPWM converter fed from the IG. In this simulation, the wind speed is changed from 10 m/s to 12 m/s, then changed back from 12 m/s to 10 m/s and the reference voltage for the DC-link is changed from 0 to 539 V. From the simulation results shown in Figure 12-Xa, sluggish DC-link voltage tracking response is obtained for the PID controller owing to the weak robustness of the linear controller. Moreover, approximately 2 sec is required for the PID-controlled SEIG system to generate the maximum output power. In addition, from the simulation results, fast dynamic response for the DC-link voltage can be obtained for the hybrid control of the SEIG wind generation system owing to the on-line training of the WNNC with IPSO. Moreover, the robust control performance of the proposed hybrid control system using the WNNC with IPSO at different operating conditions is obvious. Furthermore, approximately 1 sec is required for the SEIG to generate the maximum output power. In addition, the dynamic response of the wind generation system using the hybrid control scheme with the WNNC using IPSO is much better as shown in Figure 12-Xb. As a result, comparing the results of PID controller with the WNNC, the proposed hybrid voltage controller is more suitable to control the DC-link voltage of the CRPWM converter-based SEIG wind generation system under the possible occurrence of load disturbance and parameter variations.

The output voltage of the DC-link is fed to the CRPWM inverter connected to the utility grid. The dynamic response of the CRPWM inverter system feeding the utility grid using PID controllers and WNNC with IPSO for active and reactive power control at the same condition of wind speed variations and the DC-link voltage command is shown in Figure 12-Y with MPPT control scheme. These responses are the maximum active and reactive power, d-q axis currents of the CRPWM inverter, the grid voltages and currents at the AC side of the CRPWM inverter, respectively. It is obvious that zero reactive power and zero d-axis current which confirms unity power factor operation at different wind speeds. At the same time the q-axis current and the active power follow their references to give the MPPT. From the simulation results shown in Figure 12-Ya, sluggish active power tracking response is obtained for the PID controller owing to the weak robustness of the linear controller. Moreover, approximately 1.6 sec is required for the PID-controlled CRPWM inverter system to track the maximum power. In addition, from the simulation results, fast dynamic response for the active power can be obtained for the hybrid control of the CRPWM inverter system owing to the on-line training of the WNNC with IPSO. Moreover, the robust control performance of the proposed hybrid control system using the WNNC with IPSO at different operating conditions is obvious. Furthermore, approximately 0.8 sec is required for the CRPWM inverter system to track the maximum power. In addition, the dynamic response of the CRPWM inverter system connected to the utility grid using the hybrid control scheme with the WNNC with IPSO is much better as shown in Figure 12-Yb. As a result, comparing the results of PID with the WNNC-based IPSO, the proposed hybrid active and reactive power controllers are more suitable to control the power of the CRPWM converter/inverter system connected to the utility grid under the possible occurrence of parameter variations. Additionally, from these figures, it is evident that a unity power factor operation is achieved at different wind speeds. Furthermore, it is obvious that the proposed control scheme illustrates satisfactory performance and good tracking characteristics.

To confirm the effectiveness of the proposed control schemes, the wind speed is changed from 14 m/s to 16 m/s, then changed back from 16 m/s to 14 m/s. The dynamic response of the wind generation system using double-sided CRPWM AC/DC/AC power converters is shown in Figure 13. As result, comparing the results of PID controllers and the WNNCs with IPSO, the proposed hybrid controller gives robust performance for both the DC-link voltage, active and reactive power of the AC/DC/AC CRPWM converter considering the existence of parameter variations and load disturbances for the wind generation system.

9.2. Wind Generation System Performance with CRPWM AC/DC/AC Converters Using Sinusoidal Wind Speed Profile

In order to investigate the effectiveness of the proposed control schemes, the sinusoidal profile for wind speed variations. The dynamic response of the wind generation system using double-sided CRPWM AC/DC/AC power converters using both PID controllers and WNNCs with IPSO technique for the DC-link voltage, active and reactive power is shown in Figure 14. It is obvious from Figure 14 that good dynamic performance is achieved and the DC-link actual voltage, actual active and reactive power follow their references. In addition, the dynamic performance of the wind generation system using the hybrid control scheme with the WNNCs utilizing IPSO is much better as shown in Figure 14 and provide robust performance considering the existence of parameter variations and load disturbances for the wind generation system.

9.3. Wind Generation System Performance with CRPWM AC/DC/AC Converters Using Trapezoidal Wind Speed Profile

The wind generation system is re-subjected to trapezoidal profile for the wind speed variations to study the effectiveness of the proposed control schemes. The dynamic response of the wind generation system using double-sided CRPWM AC/DC/AC power converters using both PID controllers and WNNCs with IPSO technique for the DC-link voltage, active and reactive power is shown in Figure 15.

It is obvious that good dynamic performance is achieved and the DC-link actual voltage, actual active and reactive power follow their references. The line current and voltage at the AC side of the CRPWM inverter at different wind speeds showing unity power factor operation are shown in Figure 16. As a result, comparing the results of PID controller with the hybrid control scheme with the WNNC-based IPSO, the proposed hybrid controllers are more suitable to control the voltage and power of the CRPWM converter/inverter system connected to the utility grid under the possible occurrence of parameters variations. Additionally, it is evident that unity power factor operation is achieved at different wind speed profiles. It is clear that the proposed control scheme illustrates satisfactory performance and good tracking characteristics.

Figure 12.

Dynamic performance of the wind generation system using stepwise profile wind speed changed from V w =10 m/sec to V w =12 m/sec to V w =10 m/sec. (a) Using PID controller (b) Using WNNC with IPSO.

Figure 13.

Dynamic performance of the wind generation system using stepwise profile wind speed changed from V w =14 m/sec to V w =16 m/sec to V w =14 m/sec. (a) Using PID controller (b) Using WNNC with IPSO.

Figure 14.

Dynamic performance of the wind generation system using sinusoidal profile wind speed variations. (a) Using PID controller (b) Using WNNC with IPSO.

Figure 15.

Dynamic performance of the wind generation system using trapezoidal profile wind speed variations. (a) Using PID controller (b) Using WNNC with IPSO.

Figure 16.

Line side voltage and current showing unity power factor operation at different wind speeds V w =10 m/sec, V w =12 m/sec, V w =14 m/sec and V w =16 m/sec from top to bottom (a) Using PID controller (b) Using WNNC with IPSO

10. Conclusion

This Chapter proposed a hybrid control scheme utilizing WNNCs with IPSO for the voltage control of DC-link voltage, active power and reactive power of the CRPWM AC/DC/AC power converter feeding from a wind turbine SEIG system. The double-sided AC/DC/AC CRPWM converter is connected to the utility grid and operated under IFOC and VFOC which guarantees the robustness in the presence of parameter uncertainties and load disturbances. The IG is controlled by the maximum power point tracking (MPPT) control technique below the base speed and the maximum energy can be captured from the wind turbine. The proposed hybrid controller consists of a three feed-back PID controller in addition to a three on-line trained WNNC with IPSO. Also, this Chapter successfully demonstrated the application of the PID control and WNN control systems to control the voltage of the DC-link, active power and reactive power of the CRPWM AC/DC/AC power converter. Therefore, the DC-link voltage tracking response, active power and reactive power can be controlled to follow the response of the reference commands under a wide range of operating conditions. Simulation results have shown that the proposed hybrid control scheme using the WNNC with IPSO grants robust tracking response and good regulation characteristics in the presence of parameter uncertainties and external load disturbances. Moreover, simulations were carried out at different wind speeds to testify the effectiveness of the proposed hybrid controller. Finally, the main contributions of this Chapter are the successful development of the hybrid control system, in which a WNNC with IPSO is utilized to compensate the uncertainty bound in the wind generation system on-line and the successful application of the proposed hybrid control scheme methodology to control the DC-link voltage, active and reactive power of the AC/DC/AC CRPWM converter considering the existence of parameters uncertainties and external load disturbances.

© 2013 The Author(s). Licensee IntechOpen. This chapter is distributed under the terms of the Creative Commons Attribution 3.0 License, which permits unrestricted use, distribution, and reproduction in any medium, provided the original work is properly cited.

How to cite and reference

Link to this chapter Copy to clipboard

Cite this chapter Copy to clipboard

Fayez F. M. El-Sousy and Awad Kh. Al-Asmari (February 6th 2013). Wavelet–Neural–Network Control for Maximization of Energy Capture in Grid Connected Variable Speed Wind Driven Self- Excited Induction Generator System, Discrete Wavelet Transforms - A Compendium of New Approaches and Recent Applications, Awad Kh. Al - Asmari, IntechOpen, DOI: 10.5772/51253. Available from:

chapter statistics

1999total chapter downloads

More statistics for editors and authors

Login to your personal dashboard for more detailed statistics on your publications.

Access personal reporting

Related Content

This Book

Next chapter

Demodulation of FM Data in Free-Space Optical Communication Systems Using Discrete Wavelet Transformation

By Nader Namazi, Ray Burris, G. Charmaine Gilbreath, Michele Suite and Kenneth Grant

Related Book

First chapter

Finite Element Analysis on Strains of Viscoelastic Human Skull and Duramater

By Xianfang Yue

We are IntechOpen, the world's leading publisher of Open Access books. Built by scientists, for scientists. Our readership spans scientists, professors, researchers, librarians, and students, as well as business professionals. We share our knowledge and peer-reveiwed research papers with libraries, scientific and engineering societies, and also work with corporate R&D departments and government entities.

More About Us